Plan Review Notes For Permit 06100524 |
Permit Number |
06100524 |
|
Review Stop |
B |
Sequence Number |
5 |
|
Notes |
Date |
Text |
2007-07-10 16:35:25 | REVISION OF SHEETS S1 - S6 IS DENIED | | | | 1) THIS REVISION INCREASES THE VALUE OF THE JOB. | | INDICATE THE AMOUNT OF THE INCREASE ON THE REVISION | | FORM AND HAVE THE INTAKE CLERK ADD THIS TO THE ORIGINAL | | VALUE. | | | | 2) ON SHEET S3 ONE OF THE PORCH DIMENSIONS IS MISSING. | | SEE RED MARKS ON THE DRAWING. | | | | 3) PROVIDE A SECTION THROUGH THE STAIRS SHOWN AT THE | | MASTER BEDROOM PORCH ON SHEET S3. | | | | 4) ON SHEET S4 THERE IS A SECTION TAG FOR 13/S6 AND | | THERE IS NO SUCH SECTION ON SHEET S6. PLEASE CORRECT. | | | | 5) ON SHEET S4, (2) 1-3/4"X 11-1/4" 1.95 MICROLAMS | | ARE SPECIFIED AND IN SECTION 9/S6 (2) 1-3/4" X 11-3/4" | | 1.9E MICROLAM BEAMS ARE SPECIFIED. PLEASE CORRECT. | | | | 6) SPECIFY THE TRUSS CONNECTORS FOR THE MASTER BEDROOM | | PORCH. | | | | 7) SECTION 5/S6 ON S4 IS IN THE WRONG LOCATION. IT | | NEEDS TO BE REVISED TO SHOW THE NEW MASTER BEDROOM | | PORCH. | | | | 8) IN DETAIL 3 ON S6 SPECIFY WHAT THE 5/8" DIA | | FASTENERS @ 24"OC ARE. ALSO CHECK THE SIMPSON | | CONNECTORS THAT ARE SPECIFIED ( LUZ10 AND HSTC 78). | | THESE COULD NOT BE FOUND IN THE SIMPSON CATALOG. SHOULD | | THESE BE LU210 AND MSTC 78 ? | | | | 9) ADDRESS ZONING COMMENTS. | | | | - ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 |
|