2007-10-29 15:33:58REVISION DENIED
 REFERENCE:
 ** FBC-2004 WITH 05 & 06 REVISIONS, PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE (FAC).
 ** FLORIDA STATUTES (FS).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE ON THE
 REVISED PLANS:
  
 1. SHEET P1 SANITARY FLOOR PLAN DOES NOT REFLECT THE
 SANITARY ISOMETRIC ON SHEET P2: THE TRAP FOR THE MOP
 SINK IS MISSING. PER *701.1, SCOPE.
  
 2. SHEET P2 SANITARY ISOMETRIC RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN ON SHEET P1: THE WYE FITTING IS
 NOT INDICATED FOR THE WASHING MACHINE. PER *701.1,
 SCOPE.
  
 3. SHEET P2 SANITARY ISOMETRIC RISER DIAGRAM: THE
 FOLLOWING NEEDS TO BE INDICATED FOR THE WASHING
 MACHINE.
  
 (A) PER *708.7 MINIMUM SIZE. CLEANOUTS SHALL
 BE THE SAME NOMINAL SIZE AS THE PIPE
 THEY SERVE UP TO 4 INCHES (102MM)
 **NOTE: CLEANOUT FOR THE WASHING MACHINE SHALL BE THREE
 INCH (3").
  
 (B) PER *708.9 ACCESS. ACCESS SHALL BE
 PROVIDED TO ALL CLEANOUTS.
 **NOTE: CLEANOUT FOR THE WASHING MACHINE SHALL BE
 LOCATED AT FOUR FEET ABOVE FINNISH FLOOR (4' A.F.F.).
  
 END OF COMMENTS:
  