Plan Review Notes For Permit 06100524 |
Permit Number |
06100524 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2007-02-26 16:53:49 | DENIED BY BUILDING | | | | 1) THE NOA SUBMITTED FOR THE SOUTHEASTERN METALS MFG. | | CO. METAL ROOF IS EXPIRED. THE NOA NUMBER 06-1012.08 | | HAS NOT BEEN APPROVED BY MIAMI-DADE PRODUCT CONTROL | | DIVISION AT THIS TIME. STATUS STATES THAT ADDITIONAL | | INFORMATION HAS BEEN REQUESTED. | | | | 2) SPECIFY WHICH ONE OF THE APPROVED SYSTEMS LISTED IN | | THE FIRESTONE MODIFIED SYSTEM PRODUCT APPROVAL WILL BE | | INSTALLED. SPECIFY THE FASTENING OPTION AND DESIGN | | PRESSURE FOR THE SELECTED SYSTEM. CIRCLE THE | | APPROPRIATE ITEMS ON THE PRODUCT APPROVALS. IF ENHANCED | | FASTENING IS REQUIRED TO MEET THE HIGHER UPLIFT | | PRESSURES IN THE PERIMETER OR CORNER AREAS, SUBMIT RAS | | 117 CALCULATIONS PER LIMITATION #7 ON PAGE 34 OF THE | | NOA. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | |
|