Plan Review Notes
Plan Review Notes For Permit 06100524
Permit Number 06100524
Review Stop E
Sequence Number 2
Notes
Date Text
2006-12-27 08:08:23***** UNSAT2ND REVIEW ****
  
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS,
 SOME BASED ON PLANS NOW SUBMITTED, NEW DOCUMENTS BEING
 REVIEWED FOR THE FIRST TIME AND SOME NEW COMMENTS NOT
 MADE ON PREVIOUS REVIEWS.
  
 ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM
 PREVIOUS REVIEW WITH A NO, OK OR A NO/OK.
 THESE WILL BE FOR THE EXACT NUMERICAL NOTATION OF THE
 PREVIOUS REVIEW NOTES.
  
 A NO IS IF THE COMMENT WAS NOT FULLY ADDRESSED AND/OR
 FURTHER EXPLANATION OR CHANGES IN PLANS OR DOCUMENTS
 ARE STILL NEEDED. THIS REVIEWER WILL TRY TO BETTER
 EXPLAIN NOTE ABOVE PREVIOUS REVIEW COMMENT.
  
 AN OK WILL BE LABELED AS SUCH ON THE SAME NUMERICAL
 COMMENT AND WILL HAVE OLD NOTE REMOVED FROM COMMENTS.
  
 A NO/OK MEANS PART OF THE COMMENT MAY HAVE BEEN
 ADDRESSED, HOWEVER NOT ALL OF THE PREVIOUS REVIEW
 COMMENT MAY HAVE BEEN FULLY ADDRESSED.
  
 ** PLEASE SEE ANY NEW NOTES WILL BE ADDED TO THE END OF
 THE PREVIOUS REVIEW COMMENTS AND NOTED AS SUCH.
  
  
 1) NOTE: NO, PLEASE SEE THIS IS THE SAME NOTE. PLEASE
 SEE THERE ARE STILL CODES ON ELECTRICAL PLANS WHICH ARE
 FROM THE 1996 NEC. (NOTE #37)
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE BE SURE PLANS REFLECT THE FOLLOWING CODES AT A
 MINIMUM.
 2002 NFPA-70 (NEC.
 2002 NFPA-72 FAC.
  
 2) NOTE: OK/NO, SYMBOL WAS CHANGED; HOWEVER PLEASE SEE
 THAT THE NOTE ON E-2 STILL INDICATES SMOKE DETECTORS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE NFPA-72 DEFINITIONS, THE SYMBOL FOR SMOKE
 DETECTION DEVICES SHOULD BE SA IF INDEED A DEVICE WHICH
 WILL BE INSTALLED TO DETECT AND SOUND. IF THERE IS A
 FIRE ALARM SYSTEM, THEN ONLY THEN WOULD THEY BE SD.
  
 3) NOTE: NO/OK, PLEASE SEE NOTES ON PLANS ON E-2 WHICH
 ARE LABELED AS KEYNOTES STILL ARE IN QUESTION. PLEASE
 SEE MISSING #6. PLEASE ACTUALLY SHOW THE EQUIPMENT AND
 LOCATIONS ON PLANS. COMPLIANCE FOR SOME CODE REVIEW
 ITEMS CAN NOT BE DONE.
 PLEASE SEE MANY OF THE PREVIOUS ITEMS FROM THIS COMMENT
 WAS ADDRESSED, HOWEVER NOT ALL.
  
  
 **PREVIOUS REVIEW NOTE **
 PLEASE CORRELATE RISER AND PLANS, AS PLANS CALL FOR A
 NEW METER/MAIN COMBO, YET RISER SHOWS AND MAIN AND A
 NEW PANEL??
 PLEASE SEE RISER SHOWS THE IDENTIFICATION OF THE
 CONDUCTORS FROM THE METER TO THE MAIN AS "FEEDERS".
 PLEASE KNOW, THESE ARE INDEED SERVICE ENTRANCE
 CONDUCTORS TO THE MAIN. PLEASE KNOW FEEDERS ARE ONLY
 AFTER THE FIRST MEANS OF DISCONNECT.
 PLEASE SEE IN EITHER CASE THE CONDUCTOR SIZES ARE
 MISSING FOR THE SEC'S AND THE FEEDERS FROM THE MAIN TO
 PANELS?
 PLEASE SEE 240.4, 310.16, 100, 215.5, 230.7 ETC
 NO REVIEW FOR COMPLIANCE OF THESE CAN BE DONE AT THIS
 TIME.
  
 4) NOTE: OK/NO, PLEASE SEE NOTE #10 COMMENTS WITH
 RESPECT TO CORRELATION OF OVER CURRENT PROTECTION,
 CONDUCTOR SIZES AND SIZE OF LOADS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE INDICATE ALL PANEL AND EQUIPMENT SIZE AND
 CORRELATE WITH CONDUCTORS AND OCP.
 240., 230.310 ETC.
  
 5) NOTE: OK.
  
 6) NOTE: OK/NO, PLEASE SEE THE PANEL SCHEDULE WAS
 SUBMITTED, HOWEVER THERE ARE ITEMS WHICH DO NO MEET
 MINIMUM CODE FOR OCP, CONDUCTORS SIZES ETC.
 PLEASE SEE COMMENTS ON THESE NOTES AND REDLINED PLANS.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE SUBMIT A PANEL SCHEDULE INDICATING ALL MINIMUM
 REQUIRED CIRCUITS FOR ALL NEW AND INDICATE EXISTING.
 PLEASE BE SURE PANEL SCHEDULE SHOWS ALL OCP DEVICES AND
 CONDUCTOR SIZES AS REQUIRED FOR MIN CIRCUITS. PLEASE
 KNOW WE ARE UNABLE TO REVIEW FOR CODE COMPLIANCE AT
 THIS TIME.
 240.4,310.16, 424.3B, 210.52, ETC.
 FBC ADMIN SECTION 106.3.5.4(8).
  
 7) NOTE: NO, PLEASE SEE 220.31B FOR MINIMUM LOAD
 CALCULATIONS, THIS MAY ACTUALLY AFFECT THE SERVICE AND
 SIZE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE COMPLETE PANEL SCHEDULE AND CORRELATE LOAD
 CALCULATIONS FOR ALL DEDICATED ELECTRICAL CIRCUITS ON
 PLANS. PLEASE SEE THERE ARE SEVERAL DEDICATED CIRCUITS
 WHICH ARE NOT FIGURED INTO THE LOAD CALCS. FRIG, GDO,
 OTHERS SHOWN ETC.
 220.31B, 220.16, 210.11
  
 8) NOTE: NO, PLEASE SEE CIRCUIT(S) SHOWN; HOWEVER
 PLEASE SEE THESE CAN NOT BE #14 OR 15A OCP.
 PLEASE SEE MASTER BATH RECEPTS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING DEDICATED BATH(S) CIRCUIT(S) PER
 210.52D, 210.11C3
  
 9) NOTE:NO, COULD NOT LOCATE ANY INDICATION OF THIS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING DINING AREA/BREAKFAST AREA PER
 210.52B1, 210.11C1, 220.16
  
 10) NOTE: NO, PLEASE SEE THE OCP AND CONDUCTOR SIZES
 FOR THE EACH OF THE CIRCUITS DO NOT MEET CODE. PLEASE
 SEE PANEL SCHEDULE SHOWS 50A OCP AND #6 AND EACH
 APPLIANCE CIRCUIT AS 240V?
 PLEASE ADJUST AND CORRELATE.
  
  
 **PREVIOUS REVIEW NOTE **
 PLEASE SEE DISPOSAL IS BEING SHOWN WITH 2KW LOAD.
 PLEASE KNOW THIS UNIT IS MOST LIKELY A 120V UNIT AND
 2KW EXCEEDS THE RATING OF A 20A CIRCUIT. PLEASE KNOW AS
 NO PANEL SCHEDULE WAS NOT SUBMITTED, IT IS UNCLEAR OF
 THE OCP AND THE SIZE OF THE CONDUCTORS INTENDED. 240.4,
 310.16, ETC
  
 11) NOTE: OK.
  
 12) NOTE: OK.
  
 13) NOTE:OK.
  
 14) NOTE: OK.
  
 15) NOTE:NO, PLEASE CLARIFY THE EXISTING AREAS AND
 NEW, AND MUCH IF THE EXISTING DWELLING IS BEING
 REMODELED AND CODE COMPLIANCE FOR RECEPT SPACING NEEDS
 TO BE VERIFIED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THERE ARE SOME AREAS WHICH APPEAR TO CONTAIN
 NEW WALLS, YET DO NOT MEET 210.52 FOR RECEPT SPACING.
 PLEASE INDICATED ALL NEW AND EXISTING (E) WHICH WILL OR
 DO MEET ABOVE.
  
 16) NOTE: OK.
  
 17) NOTE:OK/NO, PLEASE SEE A/C UNITS AS NOW SHOWN,
 HOWEVER PLEASE SEE MISSING DISCONNECTS FOR THE AHU?S
 WHICH SHOWS A RECEPT FOR UNIT. PLEASE SEE 440.11,
 440.12 AS RECEPTS ARE NOT PERMITTED FOR THE CONNECTION
 OF THESE UNITS AND TO USE AS DISCONNECT EITHER.
 PLEASE ALSO SEE NEW NOTES WITH RESPECT TO CU?S.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE INCLUDE ANY NEW A/C EQUIPMENT AND DISCONNECTS
 IF APPLICABLE.
  
 18) NOTE:NO, PLEASE SEE THE WASHER AND DRYER WAS
 IDENTIFIED, HOWEVER THERE ARE STILL TWO OTHER LOCATION
 WHICH APPEARS TO BE EQUIPMENT OF SOME KIND.PLEASE SEE
 PANEL SCHEDULE MENTIONS A WATER HEATER AND ELECTRIC FOR
 THIS UNIT, HOWEVER THIS IS NOT SHOWN ON PLANS. PLEASE
 SEE REDLINED SET.
  
 **PREVIOUS REVIEW NOTE **
 PLEASE SEE NEW EQUIPMENT WHICH SEEMS TO BE SHOWN IN
 GARAGE BUT NOT IDENTIFIED?
 WASHER/ DRYER?
  
 **** NEW NOTES***
  
 1) NOTE: PLEASE SEE MISSING GFI RECEPTS PER 210.63 ,
 210.8A3.
  
 2) NOTE: PLEASE SEE PREVIOUS REVIEW WHICH CONTAIN A
 NOTE IN ASTERISK ** WHICH SAID ** IMPORTANT**, WHICH
 REQUESTED FOR ALL OLD/VOIDED SHEETS TO BE COMPLETELY
 REMOVED FROM SETS AND ONLY INSERT NEW SHEETS INTO THE
 TWO COMPLETE SETS FOR REVIEW. PLEASE KNOW THIS WILL
 HELP IN THE REVIEW PROCESS TO EXPEDITE PLANS IN THE
 REVIEW AND PROCESSING. IF THESE ARE NOT REMOVED, THE
 CONTRACTOR WILL BE CONTACTED TO COME IN AND DO THIS
 BEFORE PLANS CAN BE PROCESSED FOR ISSUANCE.
 PLEASE SEE THAT ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE ONLY.
  
 3) NOTE: PLEASE SEE ATTACHED NOTICE TO FLORIDA STATUTES
 553.80(2)(B) WITH RESPECT TO REPEAT COMMENTS FOR CODE
 COMPLIANCE. THIS IS ONLY A NOTICE GIVEN AT THIS TIME.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2006-12-26 16:38:042006-12-26 18:07:32
 NOTES TO FOLLOW, REVIEW STOPPED.