2006-12-27 08:08:23 | ***** UNSAT2ND REVIEW **** |
| |
| |
| ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL |
| IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS, |
| SOME BASED ON PLANS NOW SUBMITTED, NEW DOCUMENTS BEING |
| REVIEWED FOR THE FIRST TIME AND SOME NEW COMMENTS NOT |
| MADE ON PREVIOUS REVIEWS. |
| |
| ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM |
| PREVIOUS REVIEW WITH A NO, OK OR A NO/OK. |
| THESE WILL BE FOR THE EXACT NUMERICAL NOTATION OF THE |
| PREVIOUS REVIEW NOTES. |
| |
| A NO IS IF THE COMMENT WAS NOT FULLY ADDRESSED AND/OR |
| FURTHER EXPLANATION OR CHANGES IN PLANS OR DOCUMENTS |
| ARE STILL NEEDED. THIS REVIEWER WILL TRY TO BETTER |
| EXPLAIN NOTE ABOVE PREVIOUS REVIEW COMMENT. |
| |
| AN OK WILL BE LABELED AS SUCH ON THE SAME NUMERICAL |
| COMMENT AND WILL HAVE OLD NOTE REMOVED FROM COMMENTS. |
| |
| A NO/OK MEANS PART OF THE COMMENT MAY HAVE BEEN |
| ADDRESSED, HOWEVER NOT ALL OF THE PREVIOUS REVIEW |
| COMMENT MAY HAVE BEEN FULLY ADDRESSED. |
| |
| ** PLEASE SEE ANY NEW NOTES WILL BE ADDED TO THE END OF |
| THE PREVIOUS REVIEW COMMENTS AND NOTED AS SUCH. |
| |
| |
| 1) NOTE: NO, PLEASE SEE THIS IS THE SAME NOTE. PLEASE |
| SEE THERE ARE STILL CODES ON ELECTRICAL PLANS WHICH ARE |
| FROM THE 1996 NEC. (NOTE #37) |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE BE SURE PLANS REFLECT THE FOLLOWING CODES AT A |
| MINIMUM. |
| 2002 NFPA-70 (NEC. |
| 2002 NFPA-72 FAC. |
| |
| 2) NOTE: OK/NO, SYMBOL WAS CHANGED; HOWEVER PLEASE SEE |
| THAT THE NOTE ON E-2 STILL INDICATES SMOKE DETECTORS. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SEE NFPA-72 DEFINITIONS, THE SYMBOL FOR SMOKE |
| DETECTION DEVICES SHOULD BE SA IF INDEED A DEVICE WHICH |
| WILL BE INSTALLED TO DETECT AND SOUND. IF THERE IS A |
| FIRE ALARM SYSTEM, THEN ONLY THEN WOULD THEY BE SD. |
| |
| 3) NOTE: NO/OK, PLEASE SEE NOTES ON PLANS ON E-2 WHICH |
| ARE LABELED AS KEYNOTES STILL ARE IN QUESTION. PLEASE |
| SEE MISSING #6. PLEASE ACTUALLY SHOW THE EQUIPMENT AND |
| LOCATIONS ON PLANS. COMPLIANCE FOR SOME CODE REVIEW |
| ITEMS CAN NOT BE DONE. |
| PLEASE SEE MANY OF THE PREVIOUS ITEMS FROM THIS COMMENT |
| WAS ADDRESSED, HOWEVER NOT ALL. |
| |
| |
| **PREVIOUS REVIEW NOTE ** |
| PLEASE CORRELATE RISER AND PLANS, AS PLANS CALL FOR A |
| NEW METER/MAIN COMBO, YET RISER SHOWS AND MAIN AND A |
| NEW PANEL?? |
| PLEASE SEE RISER SHOWS THE IDENTIFICATION OF THE |
| CONDUCTORS FROM THE METER TO THE MAIN AS "FEEDERS". |
| PLEASE KNOW, THESE ARE INDEED SERVICE ENTRANCE |
| CONDUCTORS TO THE MAIN. PLEASE KNOW FEEDERS ARE ONLY |
| AFTER THE FIRST MEANS OF DISCONNECT. |
| PLEASE SEE IN EITHER CASE THE CONDUCTOR SIZES ARE |
| MISSING FOR THE SEC'S AND THE FEEDERS FROM THE MAIN TO |
| PANELS? |
| PLEASE SEE 240.4, 310.16, 100, 215.5, 230.7 ETC |
| NO REVIEW FOR COMPLIANCE OF THESE CAN BE DONE AT THIS |
| TIME. |
| |
| 4) NOTE: OK/NO, PLEASE SEE NOTE #10 COMMENTS WITH |
| RESPECT TO CORRELATION OF OVER CURRENT PROTECTION, |
| CONDUCTOR SIZES AND SIZE OF LOADS. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE INDICATE ALL PANEL AND EQUIPMENT SIZE AND |
| CORRELATE WITH CONDUCTORS AND OCP. |
| 240., 230.310 ETC. |
| |
| 5) NOTE: OK. |
| |
| 6) NOTE: OK/NO, PLEASE SEE THE PANEL SCHEDULE WAS |
| SUBMITTED, HOWEVER THERE ARE ITEMS WHICH DO NO MEET |
| MINIMUM CODE FOR OCP, CONDUCTORS SIZES ETC. |
| PLEASE SEE COMMENTS ON THESE NOTES AND REDLINED PLANS. |
| |
| ** PREVIOUS REVIEW NOTE** |
| PLEASE SUBMIT A PANEL SCHEDULE INDICATING ALL MINIMUM |
| REQUIRED CIRCUITS FOR ALL NEW AND INDICATE EXISTING. |
| PLEASE BE SURE PANEL SCHEDULE SHOWS ALL OCP DEVICES AND |
| CONDUCTOR SIZES AS REQUIRED FOR MIN CIRCUITS. PLEASE |
| KNOW WE ARE UNABLE TO REVIEW FOR CODE COMPLIANCE AT |
| THIS TIME. |
| 240.4,310.16, 424.3B, 210.52, ETC. |
| FBC ADMIN SECTION 106.3.5.4(8). |
| |
| 7) NOTE: NO, PLEASE SEE 220.31B FOR MINIMUM LOAD |
| CALCULATIONS, THIS MAY ACTUALLY AFFECT THE SERVICE AND |
| SIZE. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE COMPLETE PANEL SCHEDULE AND CORRELATE LOAD |
| CALCULATIONS FOR ALL DEDICATED ELECTRICAL CIRCUITS ON |
| PLANS. PLEASE SEE THERE ARE SEVERAL DEDICATED CIRCUITS |
| WHICH ARE NOT FIGURED INTO THE LOAD CALCS. FRIG, GDO, |
| OTHERS SHOWN ETC. |
| 220.31B, 220.16, 210.11 |
| |
| 8) NOTE: NO, PLEASE SEE CIRCUIT(S) SHOWN; HOWEVER |
| PLEASE SEE THESE CAN NOT BE #14 OR 15A OCP. |
| PLEASE SEE MASTER BATH RECEPTS. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SEE MISSING DEDICATED BATH(S) CIRCUIT(S) PER |
| 210.52D, 210.11C3 |
| |
| 9) NOTE:NO, COULD NOT LOCATE ANY INDICATION OF THIS. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SEE MISSING DINING AREA/BREAKFAST AREA PER |
| 210.52B1, 210.11C1, 220.16 |
| |
| 10) NOTE: NO, PLEASE SEE THE OCP AND CONDUCTOR SIZES |
| FOR THE EACH OF THE CIRCUITS DO NOT MEET CODE. PLEASE |
| SEE PANEL SCHEDULE SHOWS 50A OCP AND #6 AND EACH |
| APPLIANCE CIRCUIT AS 240V? |
| PLEASE ADJUST AND CORRELATE. |
| |
| |
| **PREVIOUS REVIEW NOTE ** |
| PLEASE SEE DISPOSAL IS BEING SHOWN WITH 2KW LOAD. |
| PLEASE KNOW THIS UNIT IS MOST LIKELY A 120V UNIT AND |
| 2KW EXCEEDS THE RATING OF A 20A CIRCUIT. PLEASE KNOW AS |
| NO PANEL SCHEDULE WAS NOT SUBMITTED, IT IS UNCLEAR OF |
| THE OCP AND THE SIZE OF THE CONDUCTORS INTENDED. 240.4, |
| 310.16, ETC |
| |
| 11) NOTE: OK. |
| |
| 12) NOTE: OK. |
| |
| 13) NOTE:OK. |
| |
| 14) NOTE: OK. |
| |
| 15) NOTE:NO, PLEASE CLARIFY THE EXISTING AREAS AND |
| NEW, AND MUCH IF THE EXISTING DWELLING IS BEING |
| REMODELED AND CODE COMPLIANCE FOR RECEPT SPACING NEEDS |
| TO BE VERIFIED. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SEE THERE ARE SOME AREAS WHICH APPEAR TO CONTAIN |
| NEW WALLS, YET DO NOT MEET 210.52 FOR RECEPT SPACING. |
| PLEASE INDICATED ALL NEW AND EXISTING (E) WHICH WILL OR |
| DO MEET ABOVE. |
| |
| 16) NOTE: OK. |
| |
| 17) NOTE:OK/NO, PLEASE SEE A/C UNITS AS NOW SHOWN, |
| HOWEVER PLEASE SEE MISSING DISCONNECTS FOR THE AHU?S |
| WHICH SHOWS A RECEPT FOR UNIT. PLEASE SEE 440.11, |
| 440.12 AS RECEPTS ARE NOT PERMITTED FOR THE CONNECTION |
| OF THESE UNITS AND TO USE AS DISCONNECT EITHER. |
| PLEASE ALSO SEE NEW NOTES WITH RESPECT TO CU?S. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE INCLUDE ANY NEW A/C EQUIPMENT AND DISCONNECTS |
| IF APPLICABLE. |
| |
| 18) NOTE:NO, PLEASE SEE THE WASHER AND DRYER WAS |
| IDENTIFIED, HOWEVER THERE ARE STILL TWO OTHER LOCATION |
| WHICH APPEARS TO BE EQUIPMENT OF SOME KIND.PLEASE SEE |
| PANEL SCHEDULE MENTIONS A WATER HEATER AND ELECTRIC FOR |
| THIS UNIT, HOWEVER THIS IS NOT SHOWN ON PLANS. PLEASE |
| SEE REDLINED SET. |
| |
| **PREVIOUS REVIEW NOTE ** |
| PLEASE SEE NEW EQUIPMENT WHICH SEEMS TO BE SHOWN IN |
| GARAGE BUT NOT IDENTIFIED? |
| WASHER/ DRYER? |
| |
| **** NEW NOTES*** |
| |
| 1) NOTE: PLEASE SEE MISSING GFI RECEPTS PER 210.63 , |
| 210.8A3. |
| |
| 2) NOTE: PLEASE SEE PREVIOUS REVIEW WHICH CONTAIN A |
| NOTE IN ASTERISK ** WHICH SAID ** IMPORTANT**, WHICH |
| REQUESTED FOR ALL OLD/VOIDED SHEETS TO BE COMPLETELY |
| REMOVED FROM SETS AND ONLY INSERT NEW SHEETS INTO THE |
| TWO COMPLETE SETS FOR REVIEW. PLEASE KNOW THIS WILL |
| HELP IN THE REVIEW PROCESS TO EXPEDITE PLANS IN THE |
| REVIEW AND PROCESSING. IF THESE ARE NOT REMOVED, THE |
| CONTRACTOR WILL BE CONTACTED TO COME IN AND DO THIS |
| BEFORE PLANS CAN BE PROCESSED FOR ISSUANCE. |
| PLEASE SEE THAT ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE ONLY. |
| |
| 3) NOTE: PLEASE SEE ATTACHED NOTICE TO FLORIDA STATUTES |
| 553.80(2)(B) WITH RESPECT TO REPEAT COMMENTS FOR CODE |
| COMPLIANCE. THIS IS ONLY A NOTICE GIVEN AT THIS TIME. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| |
| |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |