2007-02-05 10:27:02 | DENIED BY BUILDING |
| |
| 1)ON SHEET S2 THE TYPE AND NUMBER OF FASTENERS IS |
| REQUIRED IN THE TRUSS CONNECTOR SCHEDULE FOR EACH OF |
| THE UPLIFT VALUES LISTED. |
| |
| 2)SHOW COMPLIANCE WITH R320.1 FOR TERMITE |
| PROTECTION. |
| |
| TERMITE PROTECTION SHALL BE PROVIDED BY REGISTERED |
| TERMITICIDES, INCLUDING SOIL APPLIED PESTICIDES, |
| BAITING SYSTEMS, AND PESTICIDES APPLIED TO WOOD, OR |
| OTHER APPROVED METHODS OF TERMITE PROTECTION LABELED |
| FOR USE AS A PREVENTATIVE TREATMENT TO NEW CONSTRUCTION |
| (SEE SECTION 202 , REGISTERED TERMITICIDE). UPON |
| COMPLETION OF THE APPLICATION OF THE TERMITE PROTECTIVE |
| TREATMENT, A CERTIFICATE OF COMPLIANCE SHALL BE ISSUED |
| TO THE BUILDING DEPARTMENT BY THE LICENSED PEST CONTROL |
| COMPANY THAT CONTAINS THE FOLLOWING STATEMENT: ?THE |
| BUILDING HAS RECEIVED A COMPLETE TREATMENT FOR THE |
| PREVENTION OF SUBTERRANEAN TERMITES. TREATMENT IS IN |
| ACCORDANCE WITH RULES AND LAWS ESTABLISHED BY THE |
| FLORIDA DEPARTMENT OF AGRICULTURE AND CONSUMER |
| SERVICES.? |
| |
| 3) SHOW COMPLIANCE WITH R319.1 WHERE FLOOR JOISTS ARE |
| INSTALLED OVER EXISTING SLAB. |
| IN AREAS SUBJECT TO DECAY DAMAGE AS ESTABLISHED BY |
| TABLE R301.2(1) , THE FOLLOWING LOCATIONS SHALL REQUIRE |
| THE USE OF AN APPROVED SPECIES AND GRADE OF LUMBER, |
| PRESSURE TREATED IN ACCORDANCE WITH AWPA C1, C2, C3, |
| C4, C9, C15, C18, C22, C23, C24, C28, C31, C33, P1, P2 |
| AND P3, OR DECAY-RESISTANT HEARTWOOD OF REDWOOD, BLACK |
| LOCUST, OR CEDARS |
| 3.SILLS AND SLEEPERS ON A CONCRETE OR MASONRY |
| SLAB THAT IS IN DIRECT CONTACT WITH THE GROUND UNLESS |
| SEPARATED FROM SUCH SLAB BY AN IMPERVIOUS MOISTURE |
| BARRIER. |
| |
| 4) SHOW COMPLIANCE WITH R506.2.3 VAPOR RETARDER. |
| A 6 MIL (0.006 INCH; 152 ?M) POLYETHYLENE OR APPROVED |
| VAPOR RETARDER WITH JOINTS LAPPED NOT LESS THAN 6 |
| INCHES (152 MM) SHALL BE PLACED BETWEEN THE CONCRETE |
| FLOOR SLAB AND THE BASE COURSE OR THE PREPARED SUBGRADE |
| WHERE NO BASE COURSE EXISTS. |
| EXCEPTION: THE VAPOR RETARDER MAY BE OMITTED: |
| 1.FROM GARAGES, UTILITY BUILDINGS AND OTHER |
| UNHEATED ACCESSORY STRUCTURES. |
| 2.FROM DRIVEWAYS, WALKS, PATIOS AND OTHER FLATWORK |
| NOT LIKELY TO BE ENCLOSED AND HEATED AT A LATER DATE. |
| 3.WHERE APPROVED BY THE BUILDING OFFICIAL, BASED |
| ON LOCAL SITE CONDITIONS. |
| NOTE: EXISTING SCREEN PORCH SLAB THAT IS BEING LEFT IN |
| PLACE MAY NOT HAVE VAPOR RETARDER. |
| |
| 5) IN THE SECTION THROUGH THE GARAGE SLAB, SECTION 6 ON |
| S5,THE SLAB IS SHOWN AT THE SAME ELEVATION AS THE |
| EXTERIOR GRADE. THE SLAB IS REQUIRED TO BE A MINIMUM OF |
| 4' ABOVE GRADE. SEE R404.1.6. |
| |
| 6)SHOW COMPLIANCE WITH WPB ADMIN CODE 106.3* PRODUCT |
| APPROVALS. THOSE PRODUCT WHICH ARE |
| REGULATED BY DCA RULE 9B-72 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| FOR JURISDICTIONAL APPROVAL. |
| |
| 7)SUBMIT PRODUCT APPROVALS FOR THE LARGE MISSLE |
| IMPACT RATED DOUBLE AND SINGLE OUTSWING GLAZED FRENCH |
| DOORS WITHOUT SIDELITES. THE ONES THAT WERE SUBMITTED |
| ARE FOR DOORS WITH SIDELITES. |
| |
| 8)SUBMIT PRODUCT APPROVALS FOR THE NEW BAHAMA |
| HURRICANE SHUTTERS. |
| |
| 9)SUBMIT PRODUCT APPROVALS FOR THE METAL ROOF. THE |
| NOA SUBMITTED FOR THE SOUTHEASTERN METALS MFG. CO. |
| METAL ROOF IS EXPIRED. |
| |
| 10) SUBMIT PRODUCT APPROVALS FOR THE ROOFING THAT WILL |
| BE INSTALLED ON THE FLAT DECK. |
| |
| 11) SUBMIT TWO SETS OF TRUSS DRAWINGS THAT HAVE BEEN |
| SIGNED AND SEALED BY THE TRUSS ENGINEER AND HAVE BEEN |
| REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD FOR THE PROJECT PRIOR TO INSTALLATION. SEE |
| R802.1.6. |
| |