Date |
Text |
2006-11-02 10:08:52 | UNSAT |
| REFERENCE: FBC-2004 PLUMBING |
| |
| THE FOLLOWING CORRECTIONS ARE REQUIRED FOR PLUMBING |
| PLAN REVIEW ON THE RESUBMITTAL TO MEET CODE |
| COMPLIANCE: |
| |
| 1. NOTE: THE SUBMITTED PLANS REFERENCE FBC-2001 |
| PLUMBING, THIS IS WRONG THEY SHOULD REFERENCE FBC-2004 |
| PLUMBING. |
| |
| 2.THE SANITARY RISER DIAGRAM ON SHEET P2 DOES NOT |
| REFLECT THE FLOOR PLAN ON SHEETS A-1 AND P1. NOT ALL OF |
| THE PLUMBING FIXTURES ARE INDICATED ON THE SANTARY |
| RISER DIAGRAM. PLEASE REFERNCE SHEET A-1 IN THE |
| GARAGE-6 WHERE THE 24" MOP SINK IS INDICATED. |
| |
| 3. 1. PER FBC-2004, PLUMBING, SECTION 909.1 |
| WET VENT PERMITTED: ONLY THE FIXTURES |
| WITHIN THE BATHROOM GROUPS SHALL CONNECT |
| TO THE WET-VENTED HORIZONTAL BRANCH |
| DRAIN. ANY ADDITIONAL FIXTURES SHALL |
| DISCHARGE DOWNSTREAM OF THE WET VENT. (NOTE: PLEASE |
| REFERENCE THE CORRECTED SHEETS P1 AND P2 WHERE THE MOP |
| SINK ON SHEET A-1 IS ADDED TO SHEET P1 FLOOR PLAN AND |
| SHEET P2 SANITARY RISER FOR THE RESUBMITTAL.) |
| |
| 4. THE BRANCH DRAIN PIPING TO THE WASHING MACHINE IS |
| SIZED WRONG PER FBC-2004 PLUMBING SEC. 406.3. |
| (A) 406.3 WASTE CONNECTIONS.THE TRAP AND |
| FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES |
| WASHER SHALL BE A MINIMUM OF 2 INCHES |
| (51MM) IN DIAMETER. THE AUTOMATIC |
| CLOTHES WASHER FIXTURE DRAIN SHALL |
| CONNECT TO A BRANCH DRAIN OR DRAINAGE |
| STACK A MINIMUM OF 3 INCHES (76MM) IN |
| DIAMETER. (NOTE: PLEASE REFERENCE THE CORRECTED SHEETS |
| P1 AND P2 FOR THE RESUBMITTAL.) |
| |
| **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| PLEASE REPLACE ONLY SHEETS |
| WHICH HAVE CHANGED AND PROVIDE ONE COPY |
| OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| ONLY. NOTE: ONLY ONE CORRECTED DRAWING |
| IN RED INK FOR REFERENCE FOR |
| RESUBMITTAL. |
| |
| END OF COMMENTS: |
| |