2006-11-02 10:16:09 | UNSAT |
| REFERENCE: FBC-2004 FUEL GAS |
| |
| THE FOLLOWING CORRECTIONS ARE REQUIRED FOR GAS PLAN |
| REVIEW ON THE RESUBMITTAL TO MEET CODE COMPLIANCE: |
| |
| 1. NOTE THE SUBMITTED PLANS REFERENCE FBC-2001 FUEL |
| GAS, TABLE 402(2), THIS IS WRONG THEY SHOULD REFERENCE |
| FBC-2004 FUEL GAS TABLE 402.4 (2). |
| |
| 2. THEGAS PIPING INDICATED ON SHEET P1 FLOOR PLAN AND |
| P2 GAS RISER MATERIAL IS INDICATED AS BEING 3/4" |
| SCHEDULE 40 BLACK STEEL BEING INSTALLED IN A SLEEVE |
| WITH THREE (3) 90 DEGREE TURNS.IT IS RECOMMENDED THAT |
| THE GAS PIPE MATERIAL IN THE SLEEVE BE CHANGED TO 3/4" |
| CSST {FBC-2004 FUEL GAS TABLE 404.4(14)} AND THAT THE |
| SLEEVE BE INSTALLED WITH TWO (2) 90 DEGREE TURNS. |
| PLEASE REFERENCE SHEETS P1 AND P2 INDICATING THESE |
| CHANGES. |
| |
| 3. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2004 |
| FUEL GAS CODE. |
| |
| 4. SHOW TYPE OF PIPING MATERIAL BEING |
| INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| NUMBER OF CORRUGATED STAINLESS STEEL |
| TUBING FOR EACH PIPE SIZE BEING USED. |
| |
| 5. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES A.3.1(4). |
| |
| **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| PLEASE REPLACE ONLY SHEETS |
| WHICH HAVE CHANGED AND PROVIDE ONE COPY |
| OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| ONLY. NOTE: ONLY ONE CORRECTED DRAWING |
| IN RED INK FOR REFERENCE FOR |
| RESUBMITTAL. |
| |
| END OF COMMENTS: |
| |