2006-11-02 10:16:09UNSAT
 REFERENCE: FBC-2004 FUEL GAS
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED FOR GAS PLAN
 REVIEW ON THE RESUBMITTAL TO MEET CODE COMPLIANCE:
  
 1. NOTE THE SUBMITTED PLANS REFERENCE FBC-2001 FUEL
 GAS, TABLE 402(2), THIS IS WRONG THEY SHOULD REFERENCE
 FBC-2004 FUEL GAS TABLE 402.4 (2).
  
 2. THEGAS PIPING INDICATED ON SHEET P1 FLOOR PLAN AND
 P2 GAS RISER MATERIAL IS INDICATED AS BEING 3/4"
 SCHEDULE 40 BLACK STEEL BEING INSTALLED IN A SLEEVE
 WITH THREE (3) 90 DEGREE TURNS.IT IS RECOMMENDED THAT
 THE GAS PIPE MATERIAL IN THE SLEEVE BE CHANGED TO 3/4"
 CSST {FBC-2004 FUEL GAS TABLE 404.4(14)} AND THAT THE
 SLEEVE BE INSTALLED WITH TWO (2) 90 DEGREE TURNS.
 PLEASE REFERENCE SHEETS P1 AND P2 INDICATING THESE
 CHANGES.
  
 3. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 4. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
  
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  