2006-10-31 19:59:19***** UNSAT ****
  
 1) NOTE: PLEASE BE SURE PLANS REFLECT THE FOLLOWING
 CODES AT A MINIMUM.
 2002 NFPA-70 (NEC.
 2002 NFPA-72 FAC.
  
 2) NOTE: PLEASE SEE NFPA-72 DEFINITIONS, THE SYMBOL FOR
 SMOKE DETECTION DEVICES SHOULD BE SA IF INDEED A DEVICE
 WHICH WILL BE INSTALLED TO DETECT AND SOUND. IF THERE
 IS A FIRE ALARM SYSTEM, THEN ONLY THENWOULD THEY BE
 SD.
  
 3) NOTE: PLEASE CORRELATE RISER AND PLANS, AS PLANS
 CALL FOR A NEW METER/MAIN COMBO, YET RISER SHOWS AND
 MAIN AND A NEW PANEL??
 PLEASE SEE RISER SHOWS THE IDENTIFICATION OF THE
 CONDUCTORS FROM THE METER TO THE MAIN AS "FEEDERS".
 PLEASE KNOW, THESE ARE INDEED SERVICE ENTRANCE
 CONDUCTORS TO THE MAIN. PLEASE KNOW FEEDERS ARE ONLY
 AFTER THE FIRST MEANS OF DISCONNECT.
 PLEASE SEE IN EITHER CASE THE CONDUCTOR SIZES ARE
 MISSING FOR THE SEC'S AND THE FEEDERS FROM THE MAIN TO
 PANELS?
 PLEASE SEE 240.4, 310.16, 100, 215.5, 230.7 ETC
 NO REVIEW FOR COMPLIANCE OF THESE CAN BE DONE AT THIS
 TIME.
  
 4) NOTE: PLEASE INDICATE ALL PANEL AND EQUIPMENT SIZE
 AND CORRELATE WITH CONDUCTORS AND OCP.
 240., 230.310 ETC.
  
 5) NOTE: PLEASE SUBMIT THE AIC RATINGS FOR NEW SERVICE
 EQUIPMENT ALONG WITH SELECTIVE COORDINATION WHICH IS TO
 BE DONE.
 110.9, 240.12
  
 6) NOTE: PLEASE SUBMIT A PANEL SCHEDULE INDICATING ALL
 MINIMUM REQUIRED CIRCUITS FOR ALL NEW AND INDICATE
 EXISTING.
 PLEASE BE SURE PANEL SCHEDULE SHOWS ALL OCP DEVICES AND
 CONDUCTOR SIZES AS REQUIRED FOR MIN CIRCUITS. PLEASE
 KNOW WE ARE UNABLE TO REVIEW FOR CODE COMPLIANCE AT
 THIS TIME.
 240.4,310.16, 424.3B, 210.52, ETC.
 FBC ADMIN SECTION 106.3.5.4(8).
  
 7) NOTE: PLEASE COMPLETE PANEL SCHEDULE AND CORRELATE
 LOAD CALCULATIONS FOR ALL DEDICATED ELECTRICAL CIRCUITS
 ON PLANS. PLEASE SEE THERE ARE SEVERAL DEDICATED
 CIRCUITS WHICH ARE NOT FIGURED INTO THE LOAD CALCS.
 FRIG, GDO, OTHERS SHOWN ETC.
 220.31B, 220.16, 210.11
  
 8) NOTE: PLEASE SEE MISSING DEDICATED BATH(S)
 CIRCUIT(S) PER 210.52D, 210.11C3
  
 9) NOTE: PLEASE SEE MISSING DINING AREA/BREAKFAST AREA
 PER 210.52B1, 210.11C1, 220.16
  
 10) NOTE: PLEASE SEE DISPOSAL IS BEING SHOWN WITH 2KW
 LOAD. PLEASE KNOW THIS UNIT IS MOST LIKELY A 120V UNIT
 AND 2KW EXCEEDS THE RATING OF A 20A CIRCUIT. PLEASE
 KNOW AS NO PANEL SCHEDULE WAS SUBMITTED, IT IS UNCLEAR
 OF THE OCP AND THE SIZE OF THE CONDUCTORS INTENDED.
 240.4, 310.16, ETC
  
 11) NOTE: PLEASE SEE NOTE ON PLANS CALLS FOR AFCI
 PROTECTION FOR RECEPTS, WHEREAS THIS IS UNDER THE 1999
 NEC REQUIREMENTS. PLEASE SEE WE ARE UNDER THE 2002 NEC
 AND REQUIRES AFCI PROTECTIONS FOR ALL "OUTLETS" IN
 BEDRM/SLEEPING AREAS.
 PLEASE ALSO SEE THIS IS REQUIRED OF NEW SMOKE ALARMS,
 FANS, LTS, RECEPTS ETC.
  
 12) NOTE: PLEASE SEE MISSING EQUIPMENT GROUNDING
 CONDUCTOR PER 250.6, 250.24B, 250.110, 250.122
  
 13) NOTE: PLEASE NOTE AND VERIFY THE EXISTING GROUNDING
 ELECTRODE SYSTEM FOR THE NEW SERVICE.
 250.50
  
 14) NOTE: PLEASE SEE 210.8A6 AS ALL RECEPTS SERVING
 KITCHEN COUNTER SPACE ARE REQUIRED TO GFI/ GFI
 PROTECTED.
  
 15) NOTE: PLEASE SEE THERE ARE SOME AREAS WHICH APPEAR
 TO CONTAIN NEW WALLS, YET DO NOT MEET 210.52 FOR RECEPT
 SPACING.
 PLEASE INDICATED ALL NEW AND EXISTING (E) WHICH WILL OR
 DO MEET ABOVE.
  
 16) NOTE: PLEASE INDICATE ALL ROOM AND AREA
 DESIGNATIONS ON ELECTRICAL PLANS.
 106.1.2
  
 17) NOTE: PLEASE INCLUDE ANY NEW A/C EQUIPMENT AND
 DISCONNECTS IF APPLICABLE.
  
 18) NOTE: PLEASE SEE NEW EQUIPMENT WHICH SEEMS TO BE
 SHOWN IN GARAGE BUT NOT IDENTIFIED?
 WASHER/ DRYER?
  
 ** PLEASE KNOW AT THIS TIME AS THERE ARE MANY ITEMS NOT
 YET SUBMITTED, THERE MAY BE NEW COMMENTS ON NEW PLANS
 SUBMITTED.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW