2006-10-31 19:59:19 | ***** UNSAT **** |
| |
| 1) NOTE: PLEASE BE SURE PLANS REFLECT THE FOLLOWING |
| CODES AT A MINIMUM. |
| 2002 NFPA-70 (NEC. |
| 2002 NFPA-72 FAC. |
| |
| 2) NOTE: PLEASE SEE NFPA-72 DEFINITIONS, THE SYMBOL FOR |
| SMOKE DETECTION DEVICES SHOULD BE SA IF INDEED A DEVICE |
| WHICH WILL BE INSTALLED TO DETECT AND SOUND. IF THERE |
| IS A FIRE ALARM SYSTEM, THEN ONLY THENWOULD THEY BE |
| SD. |
| |
| 3) NOTE: PLEASE CORRELATE RISER AND PLANS, AS PLANS |
| CALL FOR A NEW METER/MAIN COMBO, YET RISER SHOWS AND |
| MAIN AND A NEW PANEL?? |
| PLEASE SEE RISER SHOWS THE IDENTIFICATION OF THE |
| CONDUCTORS FROM THE METER TO THE MAIN AS "FEEDERS". |
| PLEASE KNOW, THESE ARE INDEED SERVICE ENTRANCE |
| CONDUCTORS TO THE MAIN. PLEASE KNOW FEEDERS ARE ONLY |
| AFTER THE FIRST MEANS OF DISCONNECT. |
| PLEASE SEE IN EITHER CASE THE CONDUCTOR SIZES ARE |
| MISSING FOR THE SEC'S AND THE FEEDERS FROM THE MAIN TO |
| PANELS? |
| PLEASE SEE 240.4, 310.16, 100, 215.5, 230.7 ETC |
| NO REVIEW FOR COMPLIANCE OF THESE CAN BE DONE AT THIS |
| TIME. |
| |
| 4) NOTE: PLEASE INDICATE ALL PANEL AND EQUIPMENT SIZE |
| AND CORRELATE WITH CONDUCTORS AND OCP. |
| 240., 230.310 ETC. |
| |
| 5) NOTE: PLEASE SUBMIT THE AIC RATINGS FOR NEW SERVICE |
| EQUIPMENT ALONG WITH SELECTIVE COORDINATION WHICH IS TO |
| BE DONE. |
| 110.9, 240.12 |
| |
| 6) NOTE: PLEASE SUBMIT A PANEL SCHEDULE INDICATING ALL |
| MINIMUM REQUIRED CIRCUITS FOR ALL NEW AND INDICATE |
| EXISTING. |
| PLEASE BE SURE PANEL SCHEDULE SHOWS ALL OCP DEVICES AND |
| CONDUCTOR SIZES AS REQUIRED FOR MIN CIRCUITS. PLEASE |
| KNOW WE ARE UNABLE TO REVIEW FOR CODE COMPLIANCE AT |
| THIS TIME. |
| 240.4,310.16, 424.3B, 210.52, ETC. |
| FBC ADMIN SECTION 106.3.5.4(8). |
| |
| 7) NOTE: PLEASE COMPLETE PANEL SCHEDULE AND CORRELATE |
| LOAD CALCULATIONS FOR ALL DEDICATED ELECTRICAL CIRCUITS |
| ON PLANS. PLEASE SEE THERE ARE SEVERAL DEDICATED |
| CIRCUITS WHICH ARE NOT FIGURED INTO THE LOAD CALCS. |
| FRIG, GDO, OTHERS SHOWN ETC. |
| 220.31B, 220.16, 210.11 |
| |
| 8) NOTE: PLEASE SEE MISSING DEDICATED BATH(S) |
| CIRCUIT(S) PER 210.52D, 210.11C3 |
| |
| 9) NOTE: PLEASE SEE MISSING DINING AREA/BREAKFAST AREA |
| PER 210.52B1, 210.11C1, 220.16 |
| |
| 10) NOTE: PLEASE SEE DISPOSAL IS BEING SHOWN WITH 2KW |
| LOAD. PLEASE KNOW THIS UNIT IS MOST LIKELY A 120V UNIT |
| AND 2KW EXCEEDS THE RATING OF A 20A CIRCUIT. PLEASE |
| KNOW AS NO PANEL SCHEDULE WAS SUBMITTED, IT IS UNCLEAR |
| OF THE OCP AND THE SIZE OF THE CONDUCTORS INTENDED. |
| 240.4, 310.16, ETC |
| |
| 11) NOTE: PLEASE SEE NOTE ON PLANS CALLS FOR AFCI |
| PROTECTION FOR RECEPTS, WHEREAS THIS IS UNDER THE 1999 |
| NEC REQUIREMENTS. PLEASE SEE WE ARE UNDER THE 2002 NEC |
| AND REQUIRES AFCI PROTECTIONS FOR ALL "OUTLETS" IN |
| BEDRM/SLEEPING AREAS. |
| PLEASE ALSO SEE THIS IS REQUIRED OF NEW SMOKE ALARMS, |
| FANS, LTS, RECEPTS ETC. |
| |
| 12) NOTE: PLEASE SEE MISSING EQUIPMENT GROUNDING |
| CONDUCTOR PER 250.6, 250.24B, 250.110, 250.122 |
| |
| 13) NOTE: PLEASE NOTE AND VERIFY THE EXISTING GROUNDING |
| ELECTRODE SYSTEM FOR THE NEW SERVICE. |
| 250.50 |
| |
| 14) NOTE: PLEASE SEE 210.8A6 AS ALL RECEPTS SERVING |
| KITCHEN COUNTER SPACE ARE REQUIRED TO GFI/ GFI |
| PROTECTED. |
| |
| 15) NOTE: PLEASE SEE THERE ARE SOME AREAS WHICH APPEAR |
| TO CONTAIN NEW WALLS, YET DO NOT MEET 210.52 FOR RECEPT |
| SPACING. |
| PLEASE INDICATED ALL NEW AND EXISTING (E) WHICH WILL OR |
| DO MEET ABOVE. |
| |
| 16) NOTE: PLEASE INDICATE ALL ROOM AND AREA |
| DESIGNATIONS ON ELECTRICAL PLANS. |
| 106.1.2 |
| |
| 17) NOTE: PLEASE INCLUDE ANY NEW A/C EQUIPMENT AND |
| DISCONNECTS IF APPLICABLE. |
| |
| 18) NOTE: PLEASE SEE NEW EQUIPMENT WHICH SEEMS TO BE |
| SHOWN IN GARAGE BUT NOT IDENTIFIED? |
| WASHER/ DRYER? |
| |
| ** PLEASE KNOW AT THIS TIME AS THERE ARE MANY ITEMS NOT |
| YET SUBMITTED, THERE MAY BE NEW COMMENTS ON NEW PLANS |
| SUBMITTED. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
| |
| |
| |
| |
| |
| |
2006-10-31 19:21:11 | IN ELEC ON 10/31 |