2007-04-05 17:24:14-----------------DENIED---------------------
  
 1. HVAC NOTE 1: PLEASE REFERENCE FBC,M 2004, NOT 2001.
  
 2. HVAC NOTE 12: PLEASE SHOW ON PLAN THE LOCATION OF
 FIRE DAMPERS IN RATED FLOOR/CEILING ASSEMBLIES PER
 FBC,M 607.8
  
 3. PLAN INDICATES 15X10 DUCT UP TO 2ND FLOOR BUT SHEET
 CVR STATES THAT THE 2ND FLOOR HAS BEEN DELETED. PLEASE
 CLARIFY PER FBC,M 106.1.1.
  
 4. BATHROOM WITH 3 STALLS: PLAN SHOWS 150 CFM EXHAUST
 AND 175 CFM SUPPLY. ALL AIR SUPPLIED TO SUCH SPACES
 SHALL BE EXHAUSTED, INCLUDING ANY AIR IN EXCESS OF THAT
 REQUIRED BY TABLE 403.3 PER FBC,M 403.2.1.
  