2006-12-02 08:57:27 | PAUL SCHMITZ |
| |
| FBC 2004 PLUMBING CODE PLAN REVIEW |
| FBC 2004 CH 11, FL ACESSIBILITY CODE |
| |
| DENIED |
| |
| (1) SHT A1.1 AND A1.2 |
| 106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN |
| UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS ARE |
| PERMITTED TO BE SUBMITTED WHEN APPROVED BY THE BUILDING |
| OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT |
| CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF |
| THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL |
| CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT |
| LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED |
| BY THE BUILDING OFFICIAL (SEE ALSO SECTION 106.3.5). |
| |
| (2) SEC 401 WATER SUPPLY. WATER RISER DIAGRAM |
| REQUIRED. |
| THIS CHAPTER SHALL GOVERN THE MATERIALS, DESIGN AND |
| INSTALLATION OF PLUMBING FIXTURES, FAUCETS AND FIXTURE |
| FITTINGS IN ACCORDANCE WITH THE TYPE OF OCCUPANCY, AND |
| SHALL PROVIDE FOR THE MINIMUM NUMBER OF FIXTURES FOR |
| VARIOUS TYPES OF OCCUPANCIES. |
| |
| |
| (3) TAB 403.1 SECTION |
| MINIMUM PLUMBING FACILITIES PROVIDE PLUMBING FIXTURE |
| SCHEDULE. |
| 403.1 MINIMUM NUMBER OF FIXTURES. |
| PLUMBING FIXTURES SHALL BE PROVIDED FOR THE TYPE OF |
| OCCUPANCY AND IN THE MINIMUM NUMBER SHOWN IN TABLE |
| 403.1. TYPES OF OCCUPANCIES NOT SHOWN IN TABLE 403.1 |
| SHALL BE CONSIDERED INDIVIDUALLY BY THE CODE OFFICIAL. |
| THE NUMBER OF OCCUPANTS SHALL BE DETERMINED BY THE |
| FLORIDA BUILDING CODE, BUILDING. OCCUPANCY |
| CLASSIFICATION SHALL BE DETERMINED IN ACCORDANCE WITH |
| THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 403.1.1 POTTY PARITY. |
| IN ASSEMBLY OCCUPANCIES, RESTROOMS WHICH ARE OPEN TO |
| THE PUBLIC MUST HAVE A RATIO OF 3:2 WATER CLOSETS |
| PROVIDED FOR WOMEN AS THE COMBINED TOTAL OF WATER |
| CLOSETS AND URINALS PROVIDED FOR MEN, UNLESS THESE ARE |
| TWO OR FEWER SUCH FIXTURES FOR MEN, IN ACCORDANCE WITH |
| ?553.86, FLORIDA STATUTES. |
| SHT A1.2 ELVATION DO NOT REFLECT THE FLOOR PLAN. |
| |
| (4) DRINKING FOUNTAIN AND SERVICE SINK REQUIRED. SHOW |
| LOCATION OF FIXTURES AND LABEL AS SUCH. |
| |
| (5) SHT A1.2SEC 905.3 DRY VENTS PROBHIBITED, DWV |
| RISER DIAGRAM. |
| |
| (6) SEE COMMENTS FROM OTHER PLAN REVIEWERS, AS IT MAY |
| EFFECT PLUMBING PLAN REVIEW |
| |
| END OF COMMENTS. QUESTIONS 561-805-6692 |