Plan Review Notes
Plan Review Notes For Permit 06100522
Permit Number 06100522
Review Stop P
Sequence Number 1
Notes
Date Text
2006-12-02 08:57:27PAUL SCHMITZ
  
 FBC 2004 PLUMBING CODE PLAN REVIEW
 FBC 2004 CH 11, FL ACESSIBILITY CODE
  
 DENIED
  
 (1) SHT A1.1 AND A1.2
 106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS ARE
 PERMITTED TO BE SUBMITTED WHEN APPROVED BY THE BUILDING
 OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL (SEE ALSO SECTION 106.3.5).
  
 (2) SEC 401 WATER SUPPLY. WATER RISER DIAGRAM
 REQUIRED.
 THIS CHAPTER SHALL GOVERN THE MATERIALS, DESIGN AND
 INSTALLATION OF PLUMBING FIXTURES, FAUCETS AND FIXTURE
 FITTINGS IN ACCORDANCE WITH THE TYPE OF OCCUPANCY, AND
 SHALL PROVIDE FOR THE MINIMUM NUMBER OF FIXTURES FOR
 VARIOUS TYPES OF OCCUPANCIES.
  
  
 (3) TAB 403.1 SECTION
 MINIMUM PLUMBING FACILITIES PROVIDE PLUMBING FIXTURE
 SCHEDULE.
 403.1 MINIMUM NUMBER OF FIXTURES.
 PLUMBING FIXTURES SHALL BE PROVIDED FOR THE TYPE OF
 OCCUPANCY AND IN THE MINIMUM NUMBER SHOWN IN TABLE
 403.1. TYPES OF OCCUPANCIES NOT SHOWN IN TABLE 403.1
 SHALL BE CONSIDERED INDIVIDUALLY BY THE CODE OFFICIAL.
 THE NUMBER OF OCCUPANTS SHALL BE DETERMINED BY THE
 FLORIDA BUILDING CODE, BUILDING. OCCUPANCY
 CLASSIFICATION SHALL BE DETERMINED IN ACCORDANCE WITH
 THE FLORIDA BUILDING CODE, BUILDING.
  
 403.1.1 POTTY PARITY.
 IN ASSEMBLY OCCUPANCIES, RESTROOMS WHICH ARE OPEN TO
 THE PUBLIC MUST HAVE A RATIO OF 3:2 WATER CLOSETS
 PROVIDED FOR WOMEN AS THE COMBINED TOTAL OF WATER
 CLOSETS AND URINALS PROVIDED FOR MEN, UNLESS THESE ARE
 TWO OR FEWER SUCH FIXTURES FOR MEN, IN ACCORDANCE WITH
 ?553.86, FLORIDA STATUTES.
 SHT A1.2 ELVATION DO NOT REFLECT THE FLOOR PLAN.
  
 (4) DRINKING FOUNTAIN AND SERVICE SINK REQUIRED. SHOW
 LOCATION OF FIXTURES AND LABEL AS SUCH.
  
 (5) SHT A1.2SEC 905.3 DRY VENTS PROBHIBITED, DWV
 RISER DIAGRAM.
  
 (6) SEE COMMENTS FROM OTHER PLAN REVIEWERS, AS IT MAY
 EFFECT PLUMBING PLAN REVIEW
  
 END OF COMMENTS. QUESTIONS 561-805-6692