Notes |
Date |
Text |
2006-10-27 12:31:45 | *****DENIED***** | | | | | | | | 1.THE SUBMITTED PLANS INDICATE THAT THE SCOPE OF WORK | | WILL BE CONDUCTED AT 5405 NO. HAVERHILL ROAD.AS PER | | WEST PALM BEACH ADDRESSING DEPARTMENT, THE CORRECT | | ADDRESS FOR THIS BUILDING IS 5407.THE CORRECT ADDRESS | | SHOULD BE REFLECTED IN THE TITLE BLOCK. | | | | 2.PROVIDE EXISTING FLOOR PLAN TO DETERMINE IF BAY 44 | | & 45 WILL BE ONE UNIT SPACE.IF SO, WHAT WILL THE UNIT | | SPACE NUMBER BE? | | | | 3.NFPA 101 - 2003 EDITION, AND FLORIDA FIRE | | PREVENTION CODE - 2004 EDITION SHALL BE REFERENCED. | | | | 4.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | 5.FIRE EXTINGUISHERS ARE RATED 2A-10BC RATED, | | CERTIFIED AND TAGGED.(SEE SHEET A2) | | | | 6.ONLY TWO OF THE THREE FIRE EXTINGUISHERS COULD BE | | LOCATED. | | | | 7.INTERIOR FINISH FOR WALLS AND CEILING IN EXITS AND | | EXIT ACCESS CORRIDORS SHALL BE CLASS "A" OR CLASS"B". | | (SEE SHEET A2) | | | | 8.SHOW THE LOCATION OF THE FIRE SPRINKLERS.HOW WILL | | THEY BE AFFECTED BY THE SCOPE OF THE WORK? | | | | 9.IF THE SCOPE OF THE INTERIOR BUILDOUT REQUIRES | | MODIFICATION OF THE SPRINKLER SYSTEM, SEPARATE PERMIT | | AND PLANS ARE TO BE SUBMITTED. | | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|