Plan Review Notes
Plan Review Notes For Permit 06100474
Permit Number 06100474
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2006-12-08 12:47:33*****DENIED*****
  
  
  
 1.AS PER WEST PALM BEACH FIRE PREVENTION, DUCT SMOKE
 DETECTORS SHALL INITIATE A GENERAL FIRE ALARM.AMEND
 FIRE ALARM NOTE #14, DRAWING FA 0.1 TO REFLECT AS
 SUCH.
  
 2.THE SUITE NUMBER WHERE THE SCOPE OF WORK WILL BE
 CONDUCTED IS MISSING IN THE TITLE BLOCK OF THE
 SUBMITTED PLANS.
  
  
 PLEASE BE ADVISED THAT SUB-PERMITS SHALL NOT BE ISSUED
 UNTIL THE MASTER PERMIT HAS BEEN PRINTED.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIREPLAN REVIEW
 561-805-6722