2006-10-25 07:17:55 
  
 DENIED
  
 1) PRODUCT APPROVALS FOR THE CASEMENT WINDOWS HAVE BEEN
 UPDATED THE NEW STATE OF FLORIDA COVER IS 245-R4 AND
 THE REQUIRED DOCUMENTATION IS MIAMI-DADE NOA #
 05-1129.11
  
 2) THE FIXED WINDOWS FOR 6A AND 6B ARE OUTSIDE THE
 MAXIMUM SIZE LIMIT COVERED UNDER THIS PRODUCT APPROVAL.
 PLEASE SEE FL# 6976 FOR SERIES PW 9000 RECTANGULAR
 WINDOW THAT MEETS YOUR SIZE REQUIREMENT FOR THESE 2
 WINDOWS
  
 3) 812 MULLION THAT WAS HILIGHTED ON PRODUCT APPROVAL
 IS NON IMPACT RATED. FOR IMPACT RATED WINDOWS AN IMPACT
 RATED MULLION SHALL BE USED
  
 4) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  