2006-10-17 11:32:48******UNSAT******
 REFERENCE: FBC-2004 FUEL GAS AND FBC-2004 CHAPTER 1
  
 THE FOLLOWING INFORMATION IS REQUIRED FOR GAS PLAN
 REVIEW:
  
 1. PER FBC-2004 CHAPTER 1, SECTION 106.1 SUBMITTAL
 DOCUMENTS: MINIMUM OF TWO (2) SETS OF DRAWINGS AND
 OTHER DATA REQUIRED WITH EACH APPLICATION FOR PERMIT.
 NOTE: ONLY ONE (1) SET WAS SUBMITTED.
  
 2. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. NOTE: PLEASE INDICATE THE CORRESPONDING
 LENGTHS OF THE NEW GENERATOR PIPING.
  
 3. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED. NOTE: PLEASE
 INDICATE THE MATERIAL TYPE AND PIPE SIZES OF THE NEW
 GENERATOR PIPING.
  
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33). NOTE: PLEASE INDICATE THEEXISTING BTU LOAD
 TO THE HOUSE
  
 5. FBC-2004 CHAPTER 1,SECTION 106.3.4.2:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING. PLEASE DO
 THIS PRIOR TO RESUBMITTING.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721