Plan Review Notes
Plan Review Notes For Permit 06100197
Permit Number 06100197
Review Stop P
Sequence Number 4
Notes
Date Text
2007-07-26 11:42:13DENIED 4TH TIME
 REFERENCE:
 ** FBC-2004 PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE WITH THE
 ADDITION OF BATH 4 AND CABANA BATH.:
  
 1. SHEET A15 THE RESUBMITTED ISOMETRIC SANITARY RISER
 DIAGRAM DOES NOT REFLECT THE FLOOR PLAN IN THE
 FOLLOWING AREAS. PER FBC-2004 CHAPTER 1, SECTION
 106.1.1 CONSTRUCTION DOCUMENTS (ISOMETRIC) SHALL BE OF
 SUFFICIENT CLARITY TO THE LOCATION OF THE PROPOSED
 WORK.
  
 A. ALL OF THE GROUND FLOOR PLUMBING (1/2 BATH,
 KITCHEN, AND CABANA BATH). PLEASE REFERENCE THE
 CORRECTED ISOMETRIC GROUND FLOOR PLUMBING THAT REFLECTS
 THE FLOOR PLAN ON THIS SHEET FOR THE RESUBMITTAL.
  
 B. 2ND FLOOR MASTER BATH DOES NOT INDICATE THE 1/8
 BEND OFFSETS OR WYE FITTINGS AND THE LAV BY SHOWER
 BEING INDICATED IN THE WRONG PLACE. THE TRAP IS BEING
 INDICATED AS GOING OUT THE BACK WALL. PLEASE INDICATE
 THE WASTE ARM AND CORRECT LOCATION OF TRAP.
  
 C. 2ND FLOOR LAUNDRY: SINK IN LAUNDRY IS MISLABELED,
 IT SHOULD BE INDICATED AS A LAUNDRY TRAY (L.T.). THE
 LAUNDRY TRAY WASTE ARM IS BEING INDICATED IN THE WRONG
 PLACE.
  
 D. 2ND FLOOR STUDY: THE SINK IS BEING INDICATED ON THE
 WRONG SIDE OF THE 4" HORIZONTAL SANITARY PIPE.
  
 E. 2ND FLOOR BATH 2: THE LAV WASTE IS BEING INDICATED
 IN THE WRONG PLACE.
  
 F. 2ND FLOOR BATH 3 AND 4: FLOOR PLAN ON SHEET A6 ARE
 INDICATING A TUBS, BUT THE SANITARY ISOMETRIC ARE
 INDICATING SHOWERS. PLEASE CLARIFY OR CORRECT THIS ON
 THE RESUBMITTAL.
  
 2. SHEET A15 PLUMBING NOTES: PLEASE DELETE THE
 FOLLOWING "PROVIDE MINIMUM PITCH 1/4" AT ALL HORIZONTAL
 BRANCHES AND SEWER LINES PER 701.01. PLEASE ADD IN ITS
 PLACE THE FOLLOWING "SLOPE OF HORIZONTAL DRAIN PIPE PER
 TABLE 704.1" ON THE RESUBMITTAL.
  
 3. SHEET A15 SANITARY ISOMETRIC RISER PLEASE INDICATE
 THE FOLLOWING.
  
 A. PER FBC-2004 PLUMBING SECTION, 708.3.4: CLEANOUT AT
 THE BASE OF THE 4" SOIL STACK TO THE 2ND FLOOR.
  
 B. PER FBC-2004 PLUMBING SECTION, 708.3.5: PLEASE
 INDICATE A TWO-WAY CLEANOUT AT THE JUNCTION OF THE
 BUILDING DRAIN AND BUILDING SEWER.
  
 4.SHEET A15 2ND FLOOR PLUMBING PLAN: PLEASE CORRECT
 THE BRANCH DRAIN TO THE LAUNDRY TO THREE INCH (3") PER
 FBC-2004 PLUMBING SECTION 406.3.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  