Plan Review Notes For Permit 06100197 |
Permit Number |
06100197 |
|
Review Stop |
M |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2007-07-18 10:01:36 | *** DENIED *** | | 1) SEE MECHANICAL PLANS PAGE A13, SEE YELLOW HIGH | | LIGHTED DUCTS THAT NEED TO BE SIZED, OR SHOW TWO | | DIFFERENT SIZES FOR THE SAME DUCT, OR DUCT (FLEX) | | MISSING, OR SIZED WRONG. PLEASE CORRECT. | | | | 2) SEE MECHANICAL PLANS LAUNDRY ROOM SHOWS A 4" METAL | | DUCT AND A 12X12 BOX PLEASE STATE ON PLAN WHAT THEY ARE | | FOR. | | | | 3) MECHANICAL PLAN ALSO NEEDS THE PRINTED NAME OF THE | | PERSON WHO SIGNED THEM. | | | | 4) MECHANICAL PLANS NEED THE JOB ADDRESS IN THE TITLE | | BLOCK. | | | | 5) PLEASE SHOW THE SEER IN THE EQUIPMENT SCHEDULE. | | | | 6) IS CLOTHES DRYER GAS OR ELECTRIC (NOT LISTED ON | | ELECTRICAL PANEL BUT SHOWN AS 220 VOLT) IF GAS PROVIDE | | COMBUSTION AIR. | | | | 7) ENERGY CALCULATIONS SHOW THE WATER HEATER AS GAS, | | THE ELECTRICAL PLANS SHOW IT AS 220 VOLT, PLEASE | | CORRECT. | | | | 8) SEE ENERGY CALCULATIONS ARE SHOWING THE WRONG BTU'S | | FOR THE ELECTRIC HEAT STRIPS, WHEN CONVERTED TO KW THEY | | DO NOT MATCH THE MECHANICAL PLANS, PLEASE CORRECT. | | | | 9) ENERGY CALCULATIONS LINE 11 SHOWS DUCT INSULATION IS | | R-30, THE MECHANICAL PLANS SHOW THE DUCTS AS R-6, | | PLEASE CORRECT ENERGY CALCULATIONS OR SUBMIT | | MANUFACTURER'S SPECIFICATION SHEET FOR THE DUCTS | | (FLEX). | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. |
|