2007-03-20 19:40:52 | ** UNSAT 3RD REVIEW ** |
| |
| 1) NOTE: PLEASE SEE THE FOLLOWING MINIMUM CODES ARE |
| STILL MISSING FROM BEING STATED AND SHOWN ON PLANS. |
| PLEASE SEE THAT THE FOLLOWING ARE LISTED. |
| 2004 FBC |
| 2002 NFPA-70 (NEC). |
| 2002 NFPA-72 |
| |
| 2) NOTE: PLEASE SEE THAT THE PLANS DO NOT CONTAIN A |
| SIGNATURE AND PRINTED NAME OF THE PERSON RESPONSIBLE |
| FOR PLANS AND DESIGN. |
| FBC 106.1.2 |
| |
| 3) NOTE: PLEASE SEE THE MASTER BATHROOM WEST WALL SINK |
| AREA WHICH REQUIRES A GFI WITHIN 3FT OF THE SINKS EDGE. |
| THE GFI SHOWN BASED ON THE 3/16 SCALE ON PLANS DOES NOT |
| MEET THE WITHIN 3FT. |
| 210.52D. |
| |
| 4) NOTE: PLEASE SEE THE GROUNDING ELECTRODE TO THE LEFT |
| OF THE RISER CONTAINS A #3 FOR THE GEC. THE OTHERS WERE |
| CHANGED TO THE 1/0. |
| |
| 5) NOTE: PLEASE SEE THE SERVICE ENTRANCE CONDUCTORS |
| FROM THE METER TO THE 200AMP MAIN2OF 2 ARE NOT LARGE |
| ENOUGH. PLEASE SEE RISER SHOWS 1/0'S AND THE MINIMUM |
| MUST BE 2/0'S PER 310.15B6 |
| THIS WAS SHOWN THE SAME ON THE PREVIOUS PLANS, HOWEVER |
| WAS MISSED. PLEASE SEE THE 2/0'S SHOWN AFTER THE MAIN |
| ARE OK. |
| |
| 6) NOTE: PLEASE SEE THE CONDUIT SIZES BASED ON THE SCH |
| 80 AND BEING SHOWN AS 1 1/2 INCH IS NOT LARGE ENOUGH |
| FOR THE 3-2/0'S AND THE #6.MUST BE 2INCH MINIMUM. |
| THIS WAS SHOWN THIS WAY ON PREVIOUS RISER, HOWEVER WAS |
| NOT COMMENTED ON BY THIS REVIEWER. |
| |
| 7) NOTE: PLEASE SEE SHEET A-17 WAS NOT SEALED BY THE |
| ENGINEER WHICH IS SIGNED AND DATED ON PLANS AND SHEET |
| ALSO CONTAINS A TITLE BLOCK FOR SAID SHEETS. PLEASE SEE |
| FS 471.025, FAC 61G15-23.002 |
| THIS SHEET WAS VOIDED EVEN THOUGH THIS WAS STAMPED. |
| |
| ** PLANS ROUTED BACK TO MECHANICAL AS M SHEETS DO NOT |
| CONTAIN PRINTED NAME AND SIGNATURE FROM ANY RESPONSIBLE |
| DESIGNER. |
| |
| ** PLEASE ONLY VERIFY THE SPACE ON THE WALL BY THE |
| GARAGE WHICH INDICATES A 400AMP METER AND TWO 200AMP |
| DISCONNECTS IN A SPACE NOTE ON PLANS AS 4FT, 2INCHES? |
| THIS DOES NOT SEEM TO BE ENOUGH SPACE BASED ON THE |
| PLANS AND DIMENSIONS SHOWN WITH THE A/C EQUIPMENT AS |
| SHOWN. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |