Plan Review Notes
Plan Review Notes For Permit 06100197
Permit Number 06100197
Review Stop E
Sequence Number 3
Notes
Date Text
2007-03-20 19:40:52** UNSAT 3RD REVIEW **
  
 1) NOTE: PLEASE SEE THE FOLLOWING MINIMUM CODES ARE
 STILL MISSING FROM BEING STATED AND SHOWN ON PLANS.
 PLEASE SEE THAT THE FOLLOWING ARE LISTED.
 2004 FBC
 2002 NFPA-70 (NEC).
 2002 NFPA-72
  
 2) NOTE: PLEASE SEE THAT THE PLANS DO NOT CONTAIN A
 SIGNATURE AND PRINTED NAME OF THE PERSON RESPONSIBLE
 FOR PLANS AND DESIGN.
 FBC 106.1.2
  
 3) NOTE: PLEASE SEE THE MASTER BATHROOM WEST WALL SINK
 AREA WHICH REQUIRES A GFI WITHIN 3FT OF THE SINKS EDGE.
 THE GFI SHOWN BASED ON THE 3/16 SCALE ON PLANS DOES NOT
 MEET THE WITHIN 3FT.
 210.52D.
  
 4) NOTE: PLEASE SEE THE GROUNDING ELECTRODE TO THE LEFT
 OF THE RISER CONTAINS A #3 FOR THE GEC. THE OTHERS WERE
 CHANGED TO THE 1/0.
  
 5) NOTE: PLEASE SEE THE SERVICE ENTRANCE CONDUCTORS
 FROM THE METER TO THE 200AMP MAIN2OF 2 ARE NOT LARGE
 ENOUGH. PLEASE SEE RISER SHOWS 1/0'S AND THE MINIMUM
 MUST BE 2/0'S PER 310.15B6
 THIS WAS SHOWN THE SAME ON THE PREVIOUS PLANS, HOWEVER
 WAS MISSED. PLEASE SEE THE 2/0'S SHOWN AFTER THE MAIN
 ARE OK.
  
 6) NOTE: PLEASE SEE THE CONDUIT SIZES BASED ON THE SCH
 80 AND BEING SHOWN AS 1 1/2 INCH IS NOT LARGE ENOUGH
 FOR THE 3-2/0'S AND THE #6.MUST BE 2INCH MINIMUM.
 THIS WAS SHOWN THIS WAY ON PREVIOUS RISER, HOWEVER WAS
 NOT COMMENTED ON BY THIS REVIEWER.
  
 7) NOTE: PLEASE SEE SHEET A-17 WAS NOT SEALED BY THE
 ENGINEER WHICH IS SIGNED AND DATED ON PLANS AND SHEET
 ALSO CONTAINS A TITLE BLOCK FOR SAID SHEETS. PLEASE SEE
 FS 471.025, FAC 61G15-23.002
 THIS SHEET WAS VOIDED EVEN THOUGH THIS WAS STAMPED.
  
 ** PLANS ROUTED BACK TO MECHANICAL AS M SHEETS DO NOT
 CONTAIN PRINTED NAME AND SIGNATURE FROM ANY RESPONSIBLE
 DESIGNER.
  
 ** PLEASE ONLY VERIFY THE SPACE ON THE WALL BY THE
 GARAGE WHICH INDICATES A 400AMP METER AND TWO 200AMP
 DISCONNECTS IN A SPACE NOTE ON PLANS AS 4FT, 2INCHES?
 THIS DOES NOT SEEM TO BE ENOUGH SPACE BASED ON THE
 PLANS AND DIMENSIONS SHOWN WITH THE A/C EQUIPMENT AS
 SHOWN.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]