2006-12-11 13:12:52DENIED 2ND TIME
 REFERENCE: FBC-2004 PLUMBING
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED FOR PLUMBING
 PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. ON SHEET A15 THE PLUMBING FLOOR PLAN LAYOUTS ARE
 INDICATED WRONG. THE KITCHEN AND 1/2 BATH SHOULD BE
 INDICATED AS THE GROUND FLOOR AND THE LAUNDRY, MASTER
 BATH, BATH 2 AND BATH 3 SHOULD BE INDICATED AS THE 2ND
 FLOOR PLUMBING. PLEASE CORRECT FOR THE RESUBMITTAL.
  
 2. ON SHEET A15 SANITARY RISER DIAGRAM: THE VENT
 INDICATED ON THE 2ND FLOOR PLUMBING PLAN IS MISSING ON
 THE SANITARY RISER DIAGRAM. PLEASE CORRECT ON THE
 RESUBMITTAL.
  
 3. ON SHEET A15 SANITARY RISER DIAGRAM:PLEASE REMOVE
 THE PARTIALLY DRAWN VENT TO THE FIRST FLOOR 1/2 BATH IT
 IS ALREADY INDICATED.
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  