2006-12-10 10:27:27 | ***** UNSAT 2ND REVIEW **** |
| |
| ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW WHICH ARE |
| STILL IN NEED OF ADDRESSING. PLEASE SEE NOTES ARE TAKEN |
| DIRECTLY FROM PREVIOUS REVIEW WITH A "OK" OR "NO" AT |
| THE SAME NUMERICAL NOTE. PLEASE SEE SOME MAY BE NOTED |
| AS "NO/OK", WHICH MEANS PART OF THE NOTE MAY HAVE BEEN |
| ADDRESSED. |
| |
| 1) NOTE: OK. LV SECURITY UNDER SEPARATE PERMIT ALONG |
| WITH POOL.PLEASE KNOW POOL WILL BE UNDER THE 2005 |
| NEC. (PLEASE SEE GROUNDING CHANGES). |
| |
| 2) NOTE: NO, COULD NOT LOCATE THESE NOTED ON PLANS. |
| PLEASE KNOW AS THE CODE HAS CHANGED IT IS IMPORTANT THE |
| RELEVANT CODES ARE SHOWN AS NOT TO FALL UNDER NEW CODE |
| OF 2005 NEC AND THE REVISIONS TO THE 2004 FBC. (REV |
| #6). |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SEE THAT THE FOLLOWING MINIMUM CODES ARE |
| REQUIRED ON PLANS. 2002 NFPA-70, 2002 NFPA-72. |
| |
| 3) NOTE: OK. |
| |
| 4) NOTE: OK. |
| |
| 5) NOTE: OK. |
| |
| 6) NOTE: OK. |
| |
| 7) NOTE: OK. |
| |
| 8) NOTE: NO, PLEASE SEE ? BATH WHICH DOES NOT INDICATE |
| ANY GFI AS REQUIRED. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SEE NUMEROUS LOCATIONS ARE MISSING THE REQUIRED |
| GFI RECEPT WITHIN 3' OF LAV/SINKS EDGE IN BATHRMS. |
| 250.52D, 210.8A1 |
| |
| 9) NOTE: NO, PLEASE SEE STUDY AND LAUNDRY ROOMS WITH |
| RECEPTS WITHIN 6' OF SINKS AND NOTE #8 ABOVE. REDLINED |
| ONCE AGAIN. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SEE MANY LOCATIONS ARE MISSING THE GFI |
| DESIGNATIONS AS REQUIRED PER 210.8A1,A2, A3, A7< PLEASE |
| SEE MANY OF THESE HAVE BEEN REDLINED, HOWEVER IT IS IN |
| NO WAY ALL WHICH ARE MISSING THIS DESIGNATION. |
| |
| 10) NOTE: OK. |
| |
| 11) NOTE: OK. |
| |
| 12) NOTE: OK. |
| |
| 13) NOTE: OK. |
| |
| 14) NOTE: OK. |
| |
| 15) NOTE:NO, PLEASE SEE NO RATINGS SHOWN. THE LETTER |
| FROM FPL DOES NOT GIVE THE RATINGS TO BE INSTALLED ONLY |
| WHAT IS AVAILABLE AT THE POLE/TRANSFORMER. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE PROVIDE AIC RATINGS FOR ALL SERVICE EQUIPMENT |
| AND SERIES RATINGS SHALL BE COORDINATED BY THE |
| DESIGNERS. PLEASE SUBMIT. 110.9, 240.12 |
| |
| 16) NOTE: OK. |
| |
| 17) NOTE: OK/NO, PLEASE SEE THREE CIRCUITS ARE SHOWN |
| HOWEVER THEY ARE ALL SHOWN FOR BEDROOM #2. |
| PLEASE ADJUST FOR OTHER CIRCUITS. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE LIST ALL THE REQUIRED ARC FAULT PROTECTED |
| CIRCUITS ON PANEL SCHEDULE(S) TO BE PROVIDED. |
| PLEASE SEE 210.12, 408.4, |
| * IT IS KNOWN THAT A NOTE IS ON PLANS, HOWEVER IT IS |
| REQUIRED TO SHOW THE SPECIFIC BRANCH CIRCUITS AT THIS |
| TIME. |
| FBC 106.1.2 ADM IN SECT |
| |
| 18) NOTE: OK. |
| |
| 19) NOTE: OK, AS ONLY NOTED. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| *** IMPORTANT ** PLEASE SEE POSSIBLE MECHANICAL NOTES |
| FOR THE LOCATION OF THE ATTIC ACCESS TO THE MECHANICAL |
| EQUIPMENT. PLEASE KNOW, IT SEEMS THE EQUIPMENT IS |
| FARTHER THAN SIX FT FROM ACCESS. PLEASE SEE MECH REVIEW |
| COMMENTS, AS THIS WILL CLEARLY AFFECT THE ELECTRICAL |
| PLANS. |
| |
| 20) NOTE:OK. |
| |
| 21) NOTE: NO, PLEASE SEE 424.3B FOR MINIMUM OCP FOR |
| 10KW UNITS. |
| REDLINED. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SEE 424.3B AS THE MINIMUM OCP FOR THE AHU'S |
| SHALL BE DONE AT 125% (MIN). PLEASE ADJUST ANY |
| CONDUCTOR SIZES IF NEEDED. |
| |
| 22) NOTE: OK. |
| |
| 23) NOTE: NO, SAME NOTE. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SEE 220.3B4. PLEASE SHOW ALL RECESSED LTS BASED |
| ON MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT BE FIGURED |
| IN W/ 3W/PER SQ FT. |
| PLEASE PROVIDE FIXTURE INFORMATION ON LEGEND FOR |
| FIXTURES BEING USED. |
| |
| 24) NOTE: NO. THE FIXTURE TYPE AS SHOWN DOES NOT MEET |
| FBC 13-606.1.ABC.1.2.4 |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE INDICATE THE FIXTURE TYPE FOR RECESSED LIGHTING |
| PER CHAPTER 13 OF THE 2004 FBC FOR AIR TIGHT CANS ETC. |
| |
| 25) NOTE: OK. |
| |
| 26) NOTE: OK. |
| |
| 27) NOTE: OK, HOWEVER SAME NOTE ONLY BEING NOTED, AS |
| THE SERVICE IS STILL BEING SHOWN AS OVER HEAD. PLEASE |
| KNOW, BASED ON THE FPL TRANSFORMER LOCATION AND THE |
| FUTURE PROPOSED POOL AS SHOWN ON PLANS, THIS MAY BECOME |
| AN ISSUE AT A FUTURE TIME |
| |
| ** PREVIOUS REVIEW NOTE** |
| ** FOR FUTURE REFERENCE, WHEN APPLYING FOR POOL PERMIT, |
| PLEASE SEE 680.8 FOR ANY OVER HEAD CONDUCTOR CLEARANCES |
| AS THE SERVICE ON RISER SHOWS THE SEC'S AS OH. |
| |
| 28) NOTE: OK. |
| |
| 29) NOTE: OK. |
| |
| 30) NOTE:NO/OK, PLEASE SEE PLANS DO NOT CONTAIN THE |
| REQUIRED SIGNATURE OF PERSON RESPONSIBLE FOR PLANS |
| DESIGN. |
| FBC ADMIN SECTION 106.1.2 |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SEE FS 481.223 FOR REQUIREMENTS OF WHO IS AND IS |
| NOT PERMITTED TO OFFER ARCHITECTURAL SERVICES AND |
| PROVIDING SIGNED AND SEALED DOCUMENTS.PLEASE BE SURE |
| THE ENGINEER OF RECORD AS SIGNING AND SEALING SAID |
| DOCUMENT IS AWARE OF THIS AND FS 471.025. IF THERE ARE |
| ANY QUESTIONS, ON THIS PLEASE CONTACT THE STATE'S LEGAL |
| COUNSEL TO THE BOARD OF ARCHITECT'S. |
| ** PLEASE KNOW ONE SET OF ELECTRICAL PLANS ARE BEING |
| RETAINED BY THIS OFFICE AT THIS TIME. |
| |
| ** NEW NOTE ** |
| |
| 1) NOTE: PLEASE SEE FLORIDA STATUTES 553.80(2)(B) WITH |
| RESPECT TO REPEAT COMMENTS. PLEASE KNOW THIS IS ONLY A |
| NOTICE GIVEN AT THIS TIME. |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |