2006-12-10 10:27:27***** UNSAT 2ND REVIEW ****
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW WHICH ARE
 STILL IN NEED OF ADDRESSING. PLEASE SEE NOTES ARE TAKEN
 DIRECTLY FROM PREVIOUS REVIEW WITH A "OK" OR "NO" AT
 THE SAME NUMERICAL NOTE. PLEASE SEE SOME MAY BE NOTED
 AS "NO/OK", WHICH MEANS PART OF THE NOTE MAY HAVE BEEN
 ADDRESSED.
  
 1) NOTE: OK. LV SECURITY UNDER SEPARATE PERMIT ALONG
 WITH POOL.PLEASE KNOW POOL WILL BE UNDER THE 2005
 NEC. (PLEASE SEE GROUNDING CHANGES).
  
 2) NOTE: NO, COULD NOT LOCATE THESE NOTED ON PLANS.
 PLEASE KNOW AS THE CODE HAS CHANGED IT IS IMPORTANT THE
 RELEVANT CODES ARE SHOWN AS NOT TO FALL UNDER NEW CODE
 OF 2005 NEC AND THE REVISIONS TO THE 2004 FBC. (REV
 #6).
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THAT THE FOLLOWING MINIMUM CODES ARE
 REQUIRED ON PLANS. 2002 NFPA-70, 2002 NFPA-72.
  
 3) NOTE: OK.
  
 4) NOTE: OK.
  
 5) NOTE: OK.
  
 6) NOTE: OK.
  
 7) NOTE: OK.
  
 8) NOTE: NO, PLEASE SEE ? BATH WHICH DOES NOT INDICATE
 ANY GFI AS REQUIRED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE NUMEROUS LOCATIONS ARE MISSING THE REQUIRED
 GFI RECEPT WITHIN 3' OF LAV/SINKS EDGE IN BATHRMS.
 250.52D, 210.8A1
  
 9) NOTE: NO, PLEASE SEE STUDY AND LAUNDRY ROOMS WITH
 RECEPTS WITHIN 6' OF SINKS AND NOTE #8 ABOVE. REDLINED
 ONCE AGAIN.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MANY LOCATIONS ARE MISSING THE GFI
 DESIGNATIONS AS REQUIRED PER 210.8A1,A2, A3, A7< PLEASE
 SEE MANY OF THESE HAVE BEEN REDLINED, HOWEVER IT IS IN
 NO WAY ALL WHICH ARE MISSING THIS DESIGNATION.
  
 10) NOTE: OK.
  
 11) NOTE: OK.
  
 12) NOTE: OK.
  
 13) NOTE: OK.
  
 14) NOTE: OK.
  
 15) NOTE:NO, PLEASE SEE NO RATINGS SHOWN. THE LETTER
 FROM FPL DOES NOT GIVE THE RATINGS TO BE INSTALLED ONLY
 WHAT IS AVAILABLE AT THE POLE/TRANSFORMER.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE AIC RATINGS FOR ALL SERVICE EQUIPMENT
 AND SERIES RATINGS SHALL BE COORDINATED BY THE
 DESIGNERS. PLEASE SUBMIT. 110.9, 240.12
  
 16) NOTE: OK.
  
 17) NOTE: OK/NO, PLEASE SEE THREE CIRCUITS ARE SHOWN
 HOWEVER THEY ARE ALL SHOWN FOR BEDROOM #2.
 PLEASE ADJUST FOR OTHER CIRCUITS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE LIST ALL THE REQUIRED ARC FAULT PROTECTED
 CIRCUITS ON PANEL SCHEDULE(S) TO BE PROVIDED.
 PLEASE SEE 210.12, 408.4,
 * IT IS KNOWN THAT A NOTE IS ON PLANS, HOWEVER IT IS
 REQUIRED TO SHOW THE SPECIFIC BRANCH CIRCUITS AT THIS
 TIME.
 FBC 106.1.2 ADM IN SECT
  
 18) NOTE: OK.
  
 19) NOTE: OK, AS ONLY NOTED.
  
 ** PREVIOUS REVIEW NOTE **
 *** IMPORTANT ** PLEASE SEE POSSIBLE MECHANICAL NOTES
 FOR THE LOCATION OF THE ATTIC ACCESS TO THE MECHANICAL
 EQUIPMENT. PLEASE KNOW, IT SEEMS THE EQUIPMENT IS
 FARTHER THAN SIX FT FROM ACCESS. PLEASE SEE MECH REVIEW
 COMMENTS, AS THIS WILL CLEARLY AFFECT THE ELECTRICAL
 PLANS.
  
 20) NOTE:OK.
  
 21) NOTE: NO, PLEASE SEE 424.3B FOR MINIMUM OCP FOR
 10KW UNITS.
 REDLINED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE 424.3B AS THE MINIMUM OCP FOR THE AHU'S
 SHALL BE DONE AT 125% (MIN). PLEASE ADJUST ANY
 CONDUCTOR SIZES IF NEEDED.
  
 22) NOTE: OK.
  
 23) NOTE: NO, SAME NOTE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE 220.3B4. PLEASE SHOW ALL RECESSED LTS BASED
 ON MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT BE FIGURED
 IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON LEGEND FOR
 FIXTURES BEING USED.
  
 24) NOTE: NO. THE FIXTURE TYPE AS SHOWN DOES NOT MEET
 FBC 13-606.1.ABC.1.2.4
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE INDICATE THE FIXTURE TYPE FOR RECESSED LIGHTING
 PER CHAPTER 13 OF THE 2004 FBC FOR AIR TIGHT CANS ETC.
  
 25) NOTE: OK.
  
 26) NOTE: OK.
  
 27) NOTE: OK, HOWEVER SAME NOTE ONLY BEING NOTED, AS
 THE SERVICE IS STILL BEING SHOWN AS OVER HEAD. PLEASE
 KNOW, BASED ON THE FPL TRANSFORMER LOCATION AND THE
 FUTURE PROPOSED POOL AS SHOWN ON PLANS, THIS MAY BECOME
 AN ISSUE AT A FUTURE TIME
  
 ** PREVIOUS REVIEW NOTE**
 ** FOR FUTURE REFERENCE, WHEN APPLYING FOR POOL PERMIT,
 PLEASE SEE 680.8 FOR ANY OVER HEAD CONDUCTOR CLEARANCES
 AS THE SERVICE ON RISER SHOWS THE SEC'S AS OH.
  
 28) NOTE: OK.
  
 29) NOTE: OK.
  
 30) NOTE:NO/OK, PLEASE SEE PLANS DO NOT CONTAIN THE
 REQUIRED SIGNATURE OF PERSON RESPONSIBLE FOR PLANS
 DESIGN.
 FBC ADMIN SECTION 106.1.2
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE FS 481.223 FOR REQUIREMENTS OF WHO IS AND IS
 NOT PERMITTED TO OFFER ARCHITECTURAL SERVICES AND
 PROVIDING SIGNED AND SEALED DOCUMENTS.PLEASE BE SURE
 THE ENGINEER OF RECORD AS SIGNING AND SEALING SAID
 DOCUMENT IS AWARE OF THIS AND FS 471.025. IF THERE ARE
 ANY QUESTIONS, ON THIS PLEASE CONTACT THE STATE'S LEGAL
 COUNSEL TO THE BOARD OF ARCHITECT'S.
 ** PLEASE KNOW ONE SET OF ELECTRICAL PLANS ARE BEING
 RETAINED BY THIS OFFICE AT THIS TIME.
  
 ** NEW NOTE **
  
 1) NOTE: PLEASE SEE FLORIDA STATUTES 553.80(2)(B) WITH
 RESPECT TO REPEAT COMMENTS. PLEASE KNOW THIS IS ONLY A
 NOTICE GIVEN AT THIS TIME.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW