2006-10-18 09:10:08*** DENIED ***
 1) SEE PAGE A13 A/C SCHEDULE UNIT #1 EQUIPMENT SENSIBLE
 BTU'S ARE MORE THAN THE TOTAL BTU'S, PLEASE CORRECT.
  
 2) SEE A/C SCHEDULE UNIT #3 CONDENSER MODEL NUMBER IS
 FOR A 8 TON UNIT, PLEASE CORRECT.
  
 3) SEE SECOND FLOOR STUDY ROOM 10" RETURN AIR DUCT IS
 TO SMALL FOR 786 CFM'S OF SUPPLY AIR,PER FBC/R M1602.4,
 PLEASE CORRECT.
  
 4) PROVIDE RETURN SIR FOR AHU #1 TO FOYER SECOND FLOOR,
 PER 2004 FBC/R M 1602.4.
  
 5)ATTIC ACCESS MUST BE WITHIN SIX FEET OF THE AHU'S
 SERVICE PANEL, PER 2004 FBC/R M 1305.1.3, PLEASE
 CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.