2006-10-18 09:10:08 | *** DENIED *** | | 1) SEE PAGE A13 A/C SCHEDULE UNIT #1 EQUIPMENT SENSIBLE | | BTU'S ARE MORE THAN THE TOTAL BTU'S, PLEASE CORRECT. | | | | 2) SEE A/C SCHEDULE UNIT #3 CONDENSER MODEL NUMBER IS | | FOR A 8 TON UNIT, PLEASE CORRECT. | | | | 3) SEE SECOND FLOOR STUDY ROOM 10" RETURN AIR DUCT IS | | TO SMALL FOR 786 CFM'S OF SUPPLY AIR,PER FBC/R M1602.4, | | PLEASE CORRECT. | | | | 4) PROVIDE RETURN SIR FOR AHU #1 TO FOYER SECOND FLOOR, | | PER 2004 FBC/R M 1602.4. | | | | 5)ATTIC ACCESS MUST BE WITHIN SIX FEET OF THE AHU'S | | SERVICE PANEL, PER 2004 FBC/R M 1305.1.3, PLEASE | | CORRECT. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. |
|