Date |
Text |
2006-10-14 13:16:00 | ***** UNSAT **** |
| |
| 1) NOTE: PLEASESEE NOTES FROM ZONING AND BUILDING |
| REVIEW AS THE POOL AND WALL WILL NOT PART OF THIS |
| PERMIT AND WILL REQUIRE SEPARATE PERMIT APPLICATION FOR |
| EACH ALONG WITH PLANS ETC. ANY WALL DETAILS ETC WOULD |
| BE IN THESE PLANS. |
| PLEASE KNOW, BESIDES THE SEPARATE ELECTRICAL PERMIT, |
| SEPARATE PERMITS FOR LV PHONE/CATV /SPKRS ETC ARE |
| SEPARATE. THESE MAY REFERENCE THESE PLANS AS TURN |
| AROUND PERMIT HOWEVER WILL REQUIRE FEE BASED ON LV |
| SCOPE OF WORK VALUE. |
| ** PLEASE KNOW THE LV SECURITY PERMIT IS SEPARATE FROM |
| ALL OF THE ABOVE AS THEY ARE REPORTED TO THE POLICE |
| DEPT SEPARATELY. |
| |
| 2) NOTE: PLEASE SEE THAT THE FOLLOWING MINIMUM CODES |
| ARE REQUIRED ON PLANS. 2002 NFPA-70, 2002 NFPA-72. |
| |
| 3) NOTE: PLEASE SEE SEC'S TO THE 200A MAIN 1OF 2 IS |
| REQUIRED TO BE SIZED PER 310.16. (31.15B6DOES NOT |
| APPLY) |
| |
| 4) NOTE: PLEASE SEE MAIN PANEL 2OF 2 SHOWS A 200A PANEL |
| SCHEDULE YET RISER SHOWS 100A'S WITH A LOAD EXCEEDING |
| THE RATING OF THE 100A MAIN DISCONNECT. |
| PLEASE ADJUST. |
| 230.70, 240, 240.4, 310.16 ETC. |
| |
| 5) NOTE: PLEASE SEE PLANS DO NOT SHOW LOCATION OF THE |
| MAINS. ONLY SHOWS THE LOCATIONS OF METER AND EACH |
| PANEL. PLEASE SHOW AND PLEASE SEE 230.70, 230.72 FOR |
| GROUPING OF MAINS REQUIRED. |
| |
| 6) NOTE: PLEASE SEE GEC IS NOT LARGE ENOUGH. PLEASE SEE |
| TABLE IN 250.66 AS #3 IS NOT ON TABLE AND #3 IS NOT |
| LARGE ENOUGH. PLEASE KNOW, AS BASED ON THE MIN SEC'S |
| WHICH WILL BE REQUIRED AS THE MAINS AS SHOWN WILL BE |
| CHANGING, PLEASE SEE 250.66 1/0 AWG MIN. |
| |
| 7) NOTE: PLEASE SEE BASED ON PREVIOUS NOTES AND LOADS |
| SHOWN, IF INDEED SERVICE IS GOING CONTAIN A 400A METER |
| AND 2-200A DISCONNECTS, PLEASE SEE 310.15B6 MAY BE USED |
| TO PROVIDE MIN SEC'S ON RISER ONL. |
| |
| 8) NOTE: PLEASE SEE NUMEROUS LOCATIONS ARE MISSING THE |
| REQUIRED GFI RECEPT WITHIN 3' OF LAV/SINKS EDGE IN |
| BATHRMS. 250.52D, 210.8A1 |
| |
| 9) NOTE: PLEASE SEE MANY LOCATION ARE MISSING THE GFI |
| DESIGNATIONS AS REQUIRED PER 210.8A1, A2, A3.A7 < |
| PLEASE SEE MANY OF THESE HAVE BEEN REDLINED, HOWEVER IT |
| IS IN NO WAY ALL WHICH ARE MISSING THIS DESIGNATION. |
| |
| 10) NOTE: PLEASE SEE 210.8A6 AS ALL RECEPTS SERVING |
| KITCHEN COUNTER SPACE ARE REQUIRED TO BE GFI/GFI |
| PROTECTED. |
| |
| 11) NOTE: PLEASE SEE MISSING SMOKE ALARM AT FOYER/AREA |
| LEADING TO FLR ABOVE. PLEASE KNOW THE LOCATION ATTHE |
| TOP OF THE STAIRS IS ALSO REQUIRED. PLEASE KNOW EVEN IF |
| THIS UNIT HAS TO BE WALL MOUNTED, IT MUST BE IN CLOSE |
| PROXIMITY OF THE STAIRS LEADING TO THE FLOOR ABOVE. |
| NFPA-72 11.5.1.1, |
| |
| 12) NOTE: PLEASE SEE NFPA-72 AS ALL SA'S ARE REQUIRED |
| TO BE LOCATED WITHIN 12' OF THE HIGHEST POINT OF ANY |
| GIVEN ROOM'S FLAT CEILING. PLEASE SEE ANY AREAS WITH |
| TRAY CEILINGS WHICH ARE 12" OR MORE WILL REQUIRE THE SA |
| TO BE MOVED. PLEASE ALSO KNOW 3' W/IN THE PEAKS OF |
| SLOPED CEILING, NONE NOTED AT THIS TIME. PLEASE SEE |
| 11.8.3 |
| |
| 13) NOTE: PLEASE VERIFY AND INDICATE OF THESE ARE |
| INDEED GOING TO BE SMOKE DETECTORS ORSMOKE ALARMS? |
| PLEASESEE NFPA-72 FOR DEFINITIONS. IF INDEED SA'S, |
| PLEASE ADJUST DESIGNATIONS. |
| |
| 14) NOTE: PLEASE PROVIDE INFORMATION FOR ELEVATOR AND |
| POWER REQUIREMENTS ETC. PLEASE SEE NO INFORMATION |
| /LOADS ETC ARE SHOWN ON PANEL SCHEDULE/LOAD CALCS. FBC |
| 106.1.2, NEC 2002. |
| UNABLE TO VERIFY CODE COMPLIANCE FOR THIS AT THIS TIME |
| AS ONLY A RECEPT IS BEING SHOWN. |
| |
| 15) NOTE: PLEASE PROVIDE AIC RATINGS FOR ALL SERVICE |
| EQUIPMENT AND SERIES RATINGS SHALL BE CO-ORDINATED BY |
| THE DESIGNERS. PLEASE SUBMIT . 110.9, 240.12 |
| |
| 16) NOTE: PLEASE SEE 210.52E AS A WP LOCATION IS BEING |
| SHOWN AT REAR OF DWELLING HOWEVERNORECEPT OR GFI? |
| 210.8A3 |
| |
| 17) NOTE; PLEASE LIST ALL THE REQUIRED ARC FAULT |
| PROTECTED CIRCUITS ON PANEL SCHEDULE(S) TO BE |
| PROVIDED. |
| PLEASE SEE 210.12, 408.4, |
| * IT IS KNOWN THAT A NOTE IS ON PLANS, HOWEVER IT IS |
| REQUIRED TO SHOW THE SPECIFIC BRANCH CIRCUITS AT THIS |
| TIME. |
| FBC 106.1.2 ADM IN SECT |
| |
| 18) NOTE: PLEASE SEE MISSING RECEPT /LT PER 210.63, |
| 210.70 FOR ATTIC EQUIPMENT. |
| |
| 19) NOTE:*** IMPORTANT ** PLEASE SEE POSSIBLE |
| MECHANICAL NOTES FOR THE LOCATION OF THE ATTIC ACCESS |
| TO THE MECHANICAL EQUIPMENT. PLEASE KNOW, IT SEEMS THE |
| EQUIPMENT IS FARTHER THAN SIX FT FROM ACCESS. PLEASE |
| SEE MECH REVIEW COMMENTS, AS THIS WILL CLEARLY AFFECT |
| THE ELECTRICAL PLANS. |
| |
| 20) NOTE:PLEASE CORRELATE ALL MECHANICAL EQUIPMENT |
| WITH THE ELECTRICAL PLANS AS THE LOADS SHOWN ARE NOT |
| THE SAME. |
| FBC 106.1.2. PLEASE ALSO SEE NEXT COMMENT. |
| |
| 21) NOTE: PLEASE SEE 424.3B AS THE MINIMUM OCP FOR THE |
| AHU'S SHALL BE DONE AT 125% (MIN). PLEASE ADJUST ANY |
| CONDUCTOR SIZES IF NEEDED. |
| |
| 22) NOTE; PLEASE SEE BRANCH CIRCUIT CONDUCTOR FOR OVEN |
| SHOWS 20A BRLR WITH #8?? PLEASE KNOW THIS CONDUCTOR |
| WILL NOT FIT UNDER THE 20A BRKR SCREW/LUG/PLATE. IF THE |
| WIRING IS GOING TO BE #8'S PLACE FOR POSSIBLE FUTURE |
| ELECTRICAL RANGE/OVEN PLEASE NOTE. |
| 110.3, |
| |
| 23 )NOTE: PLEASE SEE 220.3B4. PLEASE SHOW ALL RECESSED |
| LTS BASED ON MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT |
| BE FIGURED IN W/ 3W/PER SQ FT. |
| PLEASE PROVIDE FIXTURE INFORMATION ON LEGEND FOR |
| FIXTURES BEING USED. |
| |
| 24) NOTE: PLEASE INDICATE THE FIXTURE TYPE FOR RECESSED |
| LIGHTINGPER CHAPTER 13 OF THE 2004 FBC FOR AIR TIGHT |
| CANS ETC. |
| |
| 25) NOTE:PLEASE SEE MISSING WATER HEATER DISCONNECT |
| PER 422.31, AS A RECEPT IS NOW BEING SHOWN WHICH IS NOT |
| PERMITTED. |
| PLEASE SHOW DISCONNECT. |
| |
| 26) NOTE: PLEASE BE SURE A GFI RECEPT LOCATION IN TH |
| REAR OF THE DWELLING IS WITHIN 20' OF POOL AND AT LEAST |
| 10FT. PLEASE SEE 210.8, 680.22 |
| |
| 27) NOTE:: ** FOR FUTURE REFERENCE, WHEN APPLYING FOR |
| POOL PERMIT , PLEASE SEE 680.8 FOR ANY OVER HEAD |
| CONDUCTOR CLEARENCES AS THE SERVICE ON RISER SHOWS THE |
| SEC'S AS OH. |
| |
| 28) NOTE: PLEASE SEE "ENHANCED" GROUNDING ELECTRODE |
| SYSTEM GROUNDING DETAIL SHOULD REFLECT THE INCREASED |
| GEC AS REQUIRED PER NOTES ABOVE 250.66. |
| 250.50. |
| |
| 29) NOTE: PLEASE SEE SOME BATH RM RECEPTS ARE BEING |
| SHOW WITH A SYMBOL WHICH INDICATE THE DEVICE AT |
| 220V'S?? |
| PLEASE SEE PREVIOUS NOTE WITH RESPECT TO ALL BATH RMS. |
| 210.8A1, 210.52D. |
| |
| 30) NOTE: PLEASE SEE FS 481.223 FOR REQUIREMENTS OF WHO |
| IS AND IS NOT PERMITTED TO OFFER ARCHITECTURAL SERVICES |
| AND PROVIDING SIGNED AND SEALED DOCUMENTS.PLEASE BE |
| SURE THE ENGINEER OF RECORD AS SIGNING AND SEALING SAID |
| DOCUMENT IS AWARE OF THIS AND FS 471.025. IF THERE ARE |
| ANY QUESTIONS, ON THE THIS PLEASE CONTACT THE STATE'S |
| LEGAL COUNSEL TO THE BOARD OF ARCHITECT'S. |
| ** PLEASE KNOW ONE SET OF ELECTRICAL PLANS ARE BEING |
| RETAINED BY THIS OFFICE AT THIS TIME. |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
| |
| |
| |
| |
| |
| |
| |
| |
| |
2006-10-13 20:32:38 | PLANS WILL BE PLACED INTO A "F" STATUS AND REVIEW NOTES |
| ADDED ONCE COMPLETED. |