Plan Review Notes
Plan Review Notes For Permit 06100197
Permit Number 06100197
Review Stop E
Sequence Number 1
Notes
Date Text
2006-10-14 13:16:00***** UNSAT ****
  
 1) NOTE: PLEASESEE NOTES FROM ZONING AND BUILDING
 REVIEW AS THE POOL AND WALL WILL NOT PART OF THIS
 PERMIT AND WILL REQUIRE SEPARATE PERMIT APPLICATION FOR
 EACH ALONG WITH PLANS ETC. ANY WALL DETAILS ETC WOULD
 BE IN THESE PLANS.
 PLEASE KNOW, BESIDES THE SEPARATE ELECTRICAL PERMIT,
 SEPARATE PERMITS FOR LV PHONE/CATV /SPKRS ETC ARE
 SEPARATE. THESE MAY REFERENCE THESE PLANS AS TURN
 AROUND PERMIT HOWEVER WILL REQUIRE FEE BASED ON LV
 SCOPE OF WORK VALUE.
 ** PLEASE KNOW THE LV SECURITY PERMIT IS SEPARATE FROM
 ALL OF THE ABOVE AS THEY ARE REPORTED TO THE POLICE
 DEPT SEPARATELY.
  
 2) NOTE: PLEASE SEE THAT THE FOLLOWING MINIMUM CODES
 ARE REQUIRED ON PLANS. 2002 NFPA-70, 2002 NFPA-72.
  
 3) NOTE: PLEASE SEE SEC'S TO THE 200A MAIN 1OF 2 IS
 REQUIRED TO BE SIZED PER 310.16. (31.15B6DOES NOT
 APPLY)
  
 4) NOTE: PLEASE SEE MAIN PANEL 2OF 2 SHOWS A 200A PANEL
 SCHEDULE YET RISER SHOWS 100A'S WITH A LOAD EXCEEDING
 THE RATING OF THE 100A MAIN DISCONNECT.
 PLEASE ADJUST.
 230.70, 240, 240.4, 310.16 ETC.
  
 5) NOTE: PLEASE SEE PLANS DO NOT SHOW LOCATION OF THE
 MAINS. ONLY SHOWS THE LOCATIONS OF METER AND EACH
 PANEL. PLEASE SHOW AND PLEASE SEE 230.70, 230.72 FOR
 GROUPING OF MAINS REQUIRED.
  
 6) NOTE: PLEASE SEE GEC IS NOT LARGE ENOUGH. PLEASE SEE
 TABLE IN 250.66 AS #3 IS NOT ON TABLE AND #3 IS NOT
 LARGE ENOUGH. PLEASE KNOW, AS BASED ON THE MIN SEC'S
 WHICH WILL BE REQUIRED AS THE MAINS AS SHOWN WILL BE
 CHANGING, PLEASE SEE 250.66 1/0 AWG MIN.
  
 7) NOTE: PLEASE SEE BASED ON PREVIOUS NOTES AND LOADS
 SHOWN, IF INDEED SERVICE IS GOING CONTAIN A 400A METER
 AND 2-200A DISCONNECTS, PLEASE SEE 310.15B6 MAY BE USED
 TO PROVIDE MIN SEC'S ON RISER ONL.
  
 8) NOTE: PLEASE SEE NUMEROUS LOCATIONS ARE MISSING THE
 REQUIRED GFI RECEPT WITHIN 3' OF LAV/SINKS EDGE IN
 BATHRMS. 250.52D, 210.8A1
  
 9) NOTE: PLEASE SEE MANY LOCATION ARE MISSING THE GFI
 DESIGNATIONS AS REQUIRED PER 210.8A1, A2, A3.A7 <
 PLEASE SEE MANY OF THESE HAVE BEEN REDLINED, HOWEVER IT
 IS IN NO WAY ALL WHICH ARE MISSING THIS DESIGNATION.
  
 10) NOTE: PLEASE SEE 210.8A6 AS ALL RECEPTS SERVING
 KITCHEN COUNTER SPACE ARE REQUIRED TO BE GFI/GFI
 PROTECTED.
  
 11) NOTE: PLEASE SEE MISSING SMOKE ALARM AT FOYER/AREA
 LEADING TO FLR ABOVE. PLEASE KNOW THE LOCATION ATTHE
 TOP OF THE STAIRS IS ALSO REQUIRED. PLEASE KNOW EVEN IF
 THIS UNIT HAS TO BE WALL MOUNTED, IT MUST BE IN CLOSE
 PROXIMITY OF THE STAIRS LEADING TO THE FLOOR ABOVE.
 NFPA-72 11.5.1.1,
  
 12) NOTE: PLEASE SEE NFPA-72 AS ALL SA'S ARE REQUIRED
 TO BE LOCATED WITHIN 12' OF THE HIGHEST POINT OF ANY
 GIVEN ROOM'S FLAT CEILING. PLEASE SEE ANY AREAS WITH
 TRAY CEILINGS WHICH ARE 12" OR MORE WILL REQUIRE THE SA
 TO BE MOVED. PLEASE ALSO KNOW 3' W/IN THE PEAKS OF
 SLOPED CEILING, NONE NOTED AT THIS TIME. PLEASE SEE
 11.8.3
  
 13) NOTE: PLEASE VERIFY AND INDICATE OF THESE ARE
 INDEED GOING TO BE SMOKE DETECTORS ORSMOKE ALARMS?
 PLEASESEE NFPA-72 FOR DEFINITIONS. IF INDEED SA'S,
 PLEASE ADJUST DESIGNATIONS.
  
 14) NOTE: PLEASE PROVIDE INFORMATION FOR ELEVATOR AND
 POWER REQUIREMENTS ETC. PLEASE SEE NO INFORMATION
 /LOADS ETC ARE SHOWN ON PANEL SCHEDULE/LOAD CALCS. FBC
 106.1.2, NEC 2002.
 UNABLE TO VERIFY CODE COMPLIANCE FOR THIS AT THIS TIME
 AS ONLY A RECEPT IS BEING SHOWN.
  
 15) NOTE: PLEASE PROVIDE AIC RATINGS FOR ALL SERVICE
 EQUIPMENT AND SERIES RATINGS SHALL BE CO-ORDINATED BY
 THE DESIGNERS. PLEASE SUBMIT . 110.9, 240.12
  
 16) NOTE: PLEASE SEE 210.52E AS A WP LOCATION IS BEING
 SHOWN AT REAR OF DWELLING HOWEVERNORECEPT OR GFI?
 210.8A3
  
 17) NOTE; PLEASE LIST ALL THE REQUIRED ARC FAULT
 PROTECTED CIRCUITS ON PANEL SCHEDULE(S) TO BE
 PROVIDED.
 PLEASE SEE 210.12, 408.4,
 * IT IS KNOWN THAT A NOTE IS ON PLANS, HOWEVER IT IS
 REQUIRED TO SHOW THE SPECIFIC BRANCH CIRCUITS AT THIS
 TIME.
 FBC 106.1.2 ADM IN SECT
  
 18) NOTE: PLEASE SEE MISSING RECEPT /LT PER 210.63,
 210.70 FOR ATTIC EQUIPMENT.
  
 19) NOTE:*** IMPORTANT ** PLEASE SEE POSSIBLE
 MECHANICAL NOTES FOR THE LOCATION OF THE ATTIC ACCESS
 TO THE MECHANICAL EQUIPMENT. PLEASE KNOW, IT SEEMS THE
 EQUIPMENT IS FARTHER THAN SIX FT FROM ACCESS. PLEASE
 SEE MECH REVIEW COMMENTS, AS THIS WILL CLEARLY AFFECT
 THE ELECTRICAL PLANS.
  
 20) NOTE:PLEASE CORRELATE ALL MECHANICAL EQUIPMENT
 WITH THE ELECTRICAL PLANS AS THE LOADS SHOWN ARE NOT
 THE SAME.
 FBC 106.1.2. PLEASE ALSO SEE NEXT COMMENT.
  
 21) NOTE: PLEASE SEE 424.3B AS THE MINIMUM OCP FOR THE
 AHU'S SHALL BE DONE AT 125% (MIN). PLEASE ADJUST ANY
 CONDUCTOR SIZES IF NEEDED.
  
 22) NOTE; PLEASE SEE BRANCH CIRCUIT CONDUCTOR FOR OVEN
 SHOWS 20A BRLR WITH #8?? PLEASE KNOW THIS CONDUCTOR
 WILL NOT FIT UNDER THE 20A BRKR SCREW/LUG/PLATE. IF THE
 WIRING IS GOING TO BE #8'S PLACE FOR POSSIBLE FUTURE
 ELECTRICAL RANGE/OVEN PLEASE NOTE.
 110.3,
  
 23 )NOTE: PLEASE SEE 220.3B4. PLEASE SHOW ALL RECESSED
 LTS BASED ON MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON LEGEND FOR
 FIXTURES BEING USED.
  
 24) NOTE: PLEASE INDICATE THE FIXTURE TYPE FOR RECESSED
 LIGHTINGPER CHAPTER 13 OF THE 2004 FBC FOR AIR TIGHT
 CANS ETC.
  
 25) NOTE:PLEASE SEE MISSING WATER HEATER DISCONNECT
 PER 422.31, AS A RECEPT IS NOW BEING SHOWN WHICH IS NOT
 PERMITTED.
 PLEASE SHOW DISCONNECT.
  
 26) NOTE: PLEASE BE SURE A GFI RECEPT LOCATION IN TH
 REAR OF THE DWELLING IS WITHIN 20' OF POOL AND AT LEAST
 10FT. PLEASE SEE 210.8, 680.22
  
 27) NOTE:: ** FOR FUTURE REFERENCE, WHEN APPLYING FOR
 POOL PERMIT , PLEASE SEE 680.8 FOR ANY OVER HEAD
 CONDUCTOR CLEARENCES AS THE SERVICE ON RISER SHOWS THE
 SEC'S AS OH.
  
 28) NOTE: PLEASE SEE "ENHANCED" GROUNDING ELECTRODE
 SYSTEM GROUNDING DETAIL SHOULD REFLECT THE INCREASED
 GEC AS REQUIRED PER NOTES ABOVE 250.66.
 250.50.
  
 29) NOTE: PLEASE SEE SOME BATH RM RECEPTS ARE BEING
 SHOW WITH A SYMBOL WHICH INDICATE THE DEVICE AT
 220V'S??
 PLEASE SEE PREVIOUS NOTE WITH RESPECT TO ALL BATH RMS.
 210.8A1, 210.52D.
  
 30) NOTE: PLEASE SEE FS 481.223 FOR REQUIREMENTS OF WHO
 IS AND IS NOT PERMITTED TO OFFER ARCHITECTURAL SERVICES
 AND PROVIDING SIGNED AND SEALED DOCUMENTS.PLEASE BE
 SURE THE ENGINEER OF RECORD AS SIGNING AND SEALING SAID
 DOCUMENT IS AWARE OF THIS AND FS 471.025. IF THERE ARE
 ANY QUESTIONS, ON THE THIS PLEASE CONTACT THE STATE'S
 LEGAL COUNSEL TO THE BOARD OF ARCHITECT'S.
 ** PLEASE KNOW ONE SET OF ELECTRICAL PLANS ARE BEING
 RETAINED BY THIS OFFICE AT THIS TIME.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
  
  
  
  
  
  
2006-10-13 20:32:38PLANS WILL BE PLACED INTO A "F" STATUS AND REVIEW NOTES
 ADDED ONCE COMPLETED.