Plan Review Notes
Plan Review Notes For Permit 06100093
Permit Number 06100093
Review Stop B
Sequence Number 3
Notes
Date Text
2007-02-12 09:05:49DENIED BY BUILDING
  
 1) THE REVISED SHEETS SUBMITTED ARE FOR THE 2ND FLOOR
 (SUITE 200) OF 307 EVERNIA STREET. THE PERMIT NUMBER ON
 THE REVISION SUBMITTAL FORM (06100093) IS FOR THE THIRD
 FLOOR TENANT BUILD OUT.
  
 2) SHOW THAT THE DOOR TO THE LOUNGE COMPLIES WITH FBC
 11-4.13.6 FOR REQUIRED MANEUVERING CLEARANCES AT DOORS.
 A MINIMUM OF 18" IS REQUIRED AT THE LATCH ON THE PULL
 SIDE OF DOORS.
  
 3) THE LOUNGE CABINET DETAILS ON A6.2.1 DO NOT CLEARLY
 SHOW COMPLIANCE WITH FBC 11-4.24. PROVIDE BETTER
 DETAIL.
  
 4) ALL PLAN SHEETS THAT ARE AFFECTED THE CHANGES ARE
 REQUIRED TO BE REVISED. SHEET A5.1 IS MISSING.
  
 - ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714