Plan Review Notes
Plan Review Notes For Permit 06100093
Permit Number 06100093
Review Stop E
Sequence Number 2
Notes
Date Text
2006-12-05 18:41:12**** UNSAT 2ND REVIEW ***
  
 ** PLEASE SEE SOME NOTES FROM THE PREVIOUS REVIEW ARE
 STILL IN QUESTION. PLEASE ALSO SEE ANY NEW NOTES DUE TO
 PLANS SUBMITTED.
 ** PLEASE SEE A NOTE OF "NO" OR "OK" IS BEING NOTED AT
 EACH NOTE WHICH IS TAKEN DIRECTLY FROM PREVIOUS REVIEW.
 PLEASE SEE IF NO, A FURTHER EXPLANATION IS NOTED TO
 BETTER CLEAR UP COMMENT FROM PREVIOUS REVIEW. PLEASE
 KNOW SOME MAY SHOW NO/OK, THIS MAY BE THAT PART OF THE
 COMMENT WAS ADDRESSED AND PART OF THE COMMENT MAY STILL
 BE OUTSTANDING.
  
  
 1) NOTE:NO, PLEASE SEE BASED ON THE LIGHTING
 DENSITIES SHOWN, PLEASE SEE TABLES IN 13-415.2.ABC.1,
 415.2.B.1.
 PLEASE BE SURE ALL SEPARATE SPACES INDICATE A CONTROL
 DEVICE.
 PLEASE SEE THAT ALL MAXIMUM TIMES ON DEVICES SHOWN BE
 NOTED ON THE LEGEND.
 PLEASE SEE IF THE EXISTING CORRIDOR IS GOING TO BE PART
 OF THE TENANT SPACE, SEE THAT CONTROLS WILL BE
 REQUIRED.
 PLEASE SEE THAT A DETAIL OR NOTE IS PROVIDED TO
 INDICATE THE CIRCUITING OF ALL EM/EXT LTS SHALL BE
 WIRED TO ANY LOCAL BRANCH CIRCUIT AHEAD OF ANY CONTROL
 SWITCHING DEVICES. PLEASE SEE 700.12E.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE FBC CHAPTER 13 13-415.1.ABC.1.1, .1.2 AND
 .1.3.
 PLEASE ALSO SEE 13-415.2.ABC.1. PLEASE SEE THIS SPACE
 WAS A "SHELL" SPACE AND IS NOW BEING BUILT OUT UNDER
 THE 2004 FBC. PLEASE ADJUST AS NEEDED.
  
 2) NOTE: NO, THIS IS NOT CLEAR YET AS TENANT SPACES
 WITH RATE WALL ETC ARE STILL BE SHOWN, PLEASE SEE NOTE
 #3.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE ALL AREAS WHICH ARE BEING SHOWN AS "COMMON
 AREAS" MAY NOT BE FED FROM PANELS WHICH ARE FOR TENANT
 SPACE.210.25
  
 3) NOTE:NO, PLEASE SEE RESPONSE MENTIONS THIS IS ALL
 GOING TO BE ONE TENANT SPACE, HOWEVER PLANS CLEARLY
 STILL INDICATE TWO TENANTS. PLEASE SEE NOTE #1 WHICH
 SPEAKS OF CIRCUITING OF FIXTURES FOR EXISTING CORRIDOR
 AND CIRCUITING TO RECESSED LIGHTS ETC?
 PLEASE SEE TENANT SEPARATION WALLS AND MULTIPLE TENANTS
 ARE STILL BEING SHOWN. IF THIS "IS" ONE TENANT, PLEASE
 ADJUST PLANS ACCORDINGLY.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE SEE ELECTRICAL PANELS MAY NOT BE IN RATED EXIT
 CORRIDOR SEE FBC BUILDING REVIEW COMMENTS. IF INDEED
 THIS IS GOING TO BE TWO TENANT SPACES PLEASE VERIFY AS
 ONLY ONE METER IS BEING SHOWN AND MAY NOT FEED TWO
 TENANTS/SEPARATE OCCUPANCIES FROM ONE METER/MAIN.
 PLEASE SEE COMMENTS FROM OTHER REVIEWS WHICH MAY AFFECT
 THE AMOUNT OF TENANTS ALLOWED PER FLOOR, CORRIDORS
 ETC.
 PLEASE SEE PREVIOUS NOTE WITH RESPECT TO THE COMMON
 AREA NOT BEING FED OR CONTAINING THE ELECTRICAL FROM
 TENANT PANEL.
  
 4) NOTE: NO, MAY NOT USE A "PLUG-IN" FOR THE REQUIRED
 DISCONNECTING MEANS. THIS WAS CHANGED IN THE CODE
 BEFORE THE 93 CODE. PLEASE SEE BASED ON THE LOAD AS
 SHOWN A HARDWIRED DISCONNECT IS REQUIRED. PLEASE KNOW
 IF THE EXISTING INST-HOT IS A PLUG TYPE, THE LOAD MUST
 BE LESS THAN 750VA.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE CLARIFY THE PANEL SCHEDULE MENTIONS AN
 INSTA-HOT., YET COULD NOT FIND THIS ON PLANS. PLEASE
 SEE 430.30, 430.31 ETC AS LOAD OF THIS SIZE WHEN UNIT
 IS REQUIRED TO CONTAIN A DISCONNECT. A PLUG MAY NOT BE
 USED. PLEASE ALSO VERIFY IF THE DISCONNECTING MEANS
 CONTAINS OCP, IF SO, PLEASE SEE 110.26.
  
 4) NOTE: OK, HOWEVER PLEASE SEE NOTE ABOVE AS IF THE
 SPACE IS ONE, THEN CIRCUITING WILL BE REVISED AND WILL
 RESULT IN SOME CHANGES TO CIRCUITS ON PLANS AS WELL AS
 POSSIBLE PANEL SCHEDULE REVISIONS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE SPECIFIC ROOMS AND AREAS ON PANEL
 SCHEDULE WHICH WILL CORRELATE WITH THE PLANS AND
 LAYOUT. 408.6, PLEASE ALSO BE SURE TO INDICATE ALL
 CONDUCTOR SIZES ON PANEL SCHEDULE.
 310.16, 240.4
 FBC 106.1.2.
  
 5) NOTE: NO/OK, PLEASE SEE THE APPLIED VALUE ON THE
 APPLICATION ALONG WITH THE CORRECT SQ FOOT FOR BUILD
 OUT MUST BE ADJUSTED BY THE CONTRACTOR TO CORRELATE
 WITH PLANS. PLEASE SEE A VALUE HAS BEEN ADJUST TO $50K,
 HOWEVER THIS VALUE MAY STILL BE ADJUSTED BY THE
 BUILDING REVIEWER BASED ON THE TABLES AS SET FORTH IN
 THE FBC. THIS VALUE AMY NOT BE FINAL.
 FEES WERE NOTE PAID FOR ADDITIONAL VALUE AND ALL FEES
 ARE DUE AT THE TIME OF SUBMITIAL UP TO A VALUE OF
 $200K.ONLY THEN CAN A VALUE OF OVER 200K BE ALLLOWED
 TO PAY A % UPFRONT. PLEASE KNOW PLANS WILL NOT BE
 REVIEWED IF ALL FEES ARE NOT PAID BEFORE RESUBMITTING
 PLANS. THIS IS STATE IN 108.3 OF THE ADMINISTRATIVE
 CODE AS ADOPTED INTO CITY ORDINANCEANDADMIN CODE.
  
 **PREVIOUS REVIEW NOTE**
 PLEASE SEE VALUE FOR COMPLETE SCOPE OF WORK SHALL BE
 BASED ON ALL LABOR AND MATERIALS EVEN IF OWNER
 SUPPLIED.
 FBC 108.3
 PLEASE SEE $25K IS WAY LOW. PLEASE KNOW, USING TABLES
 BASED ON THE FBC ONE WILL BE ASSESSED. FEES WILL BE
 OWED.
 PLEASE KNOW, ONCE THE SQ FT HAS BEEN VERIFIED FOR
 ACTUAL SCOPE OF WORK, THIS VALUE MAY CHANGE.
  
 6) NOTE: NO, SEE THE MASTER PERMIT # FOR THE BUILDING
 WAS REMOVED FROM BEING REFERENCE IN OUR SYSTEM AND
 NOTES WERE ADDED THAT A NEW RECORD NOC WAS NEEDED.
 PLEASE KNOW THIS IS REQUIRED BEFORE PICKING UP PERMIT.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE KNOW THIS INTERIOR BUILD OUT WILL REQUIRE A NEW
 NOTICE OF COMMENCEMENT AS THE ONE UNDER THE BUILDING
 HAS EXPIRED AND IS NOT PART OF THIS SCOPE OF WORK. FS
 713.13
  
 7) NOTE:OK, HOWEVER SEE LOAD CALCULATIONS AS
 SUBMITTED DO NOT CORRELATE WITH PANEL SCHEDULE.
 PLEASE ALSO SEE WHEN THE RECEPT LOADS ARE KNOWN, PLEASE
 SEE 220.13.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE INDICATE AND SHOW ON LOAD SUMMARY AND
 CALCULATIONS ALL CONTINUOUS LOADS AT 125%.
 215.3, 230.42
  
 ** NEW NOTE **
  
 1) NOTE: PLEASE SEE FBC 11-4.28.1,.2 AND .3(4). PLEASE
 DETAIL ALL NEW HORNS AND STROBES AT THE MINIMUM LEVELS
 AS REQUIRED IN CHAPTER 11 OF THE 2004 FBC.
 THIS WAS NOT NOTED IN PREVIOUS REVIEW AS IT HAS NOW
 BECOME AN ELECTRICAL REVIEW ITEM TO BE REVIEWED FOR.
  
 2) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS. PLEASE SEE THIS ONLY BEING GIVEN AS A
 NOTICE AT THIS TIME.
  
 ** PLEASE KNOW, AS PLANS FOR MANY ITEMS WILL CHANGE,
 ALL NOTES MAY NOT BE COMPLETE AT THIS TIME.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  