Plan Review Notes For Permit 06100093 |
Permit Number |
06100093 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-10-23 13:34:25 | DENIED; | | 1.PLEASE SHOW PLUMBING RISER FOR BREAK SINK, SIZE OF | | SANITARY DRAIN AND VENT. SHOW ON PLANS WERE THE | | BUILDING | | VENT AND SOIL STACKS ARE LOCATED. | | 2. SHOW A DETAIL OF THE BREAK SINK. SINK MUST COMPY | | WITH FBC-2004 CHAPTER 11 SECTIONS; | | 11-4.24.2 HEIGHT OF SINK. | | 11-4.24.3 KNEE CLEARANCE; 27" HIGH, 30" WIDE, AND | | 19" DEEP. | | 11-4.24.4 DEPTH OF SINK, A MAXIMUM OF 6 1/2" DEEP. | | 11-4.24.5 CLEAR FLOOR SPACE 30" X 48" SHOW ON FLOOR | | PLAN. | | 11-4.24.6 EXPOSED PIPES TO BE INSULATED. | | 11-4.24.7 FAUCET LEVER HANDLES ETC. | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 805-6695 |
|