Plan Review Notes
Plan Review Notes For Permit 06100093
Permit Number 06100093
Review Stop E
Sequence Number 1
Notes
Date Text
2006-10-13 09:17:08**** UNSAT ***
  
  
 1) NOTE: PLEASE SEE FBC CHAPTER 13 13-415.1.ABC.1.1,
 .1.2 AND .1.3.
 PLEASE ALSO SEE 13-415.2.ABC.1. PLEASE SEE THIS SPACE
 WAS A "SHELL" SPACE AND IS NOW BEING BUILT OUT UNDER
 THE 2004 FBC. PLEASE ADJUST AS NEEDED.
  
 2) NOTE: PLEASE SEE ALL AREAS WHICH ARE BEING SHOWN AS
 "COMMON AREAS" MAY NOT BE FED FROM PANELS WHICH ARE FOR
 TENANT SPACE.210.25
  
 3) NOTE: PLEASE SEE ELECTRICAL PANELS MAY NOT BE IN
 RATED EXIT CORRIDOR SEE FBC BUILDING REVIEW COMMENTS.
 IF INDEED THIS IS GOING TO BE TWO TENANT SPACES PLEASE
 VERIFY AS ONLY ONE METER IS BEING SHOWN AND MAY NOT
 FEED TWO TENANTS/SEPARATE OCCUPANCIES FROM ONE
 METER/MAIN.
 PLEASE SEE COMMENTS FROM OTHER REVIEWS WHICH MAY AFFECT
 THE AMOUNT OF TENANTS ALLOWED PER FLOOR , CORRIDORS
 ETC.
 PLEASE SEE PREVIOUS NOTE WITHE RESPECT TO THE COMMON
 AREA NOT BEING FED OR CONTAINING THE ELECTRICAL FROM
 TENANT PANEL.
  
 4) NOTE: PLEASE CLARIFY THE PANEL SCHEDULE MENTIONS A
 INSTA-HOT., YET COULD NOT FIND THIS ON PLANS.PLEASE SEE
 430.30, 430.31 ETC AS LOAD OF THIS SIZE WHEN UNIT IS
 REQUIRED TO CONTAIN A DISCONNECT , A PLUG MAY NOT BE
 USED. PLEASE ALSO VERIFY IF THE DISCONNECTING MEANS
 CONTAINS OCP, IF SO ,PLEASE SEE 110.26.
  
 4) NOTE:PLEASE PROVIDE SPECIFIC ROOMS AND AREAS ON
 PANEL SCHEDULE WHICH WILL CORRELATE WITH THE PLANS AND
 LAYOUT. 408.6, PLEASE ALSO BE SURE TO INDICATE ALL
 CONDUCTOR SIZES ON PANEL SCHEDULE.
 310.16, 240.4
 FBC 106.1.2.
  
 5) NOTE: PLEASE SEE VALUE FOR COMPLETE SCOPE OF WORK
 SHALL BE BASED ON ALL LABOUR AND MATERIALS EVEN IF
 OWNER SUPPLIED.
 FBC 108.3
 PLEASE SEE $25K IS WAY LOW. PLEASE KNOW, USING TABLES
 BASED ON THE FBCONE WILL BE ASSESSED. FEES WILL BE
 OWED.
 PLEASE KNOW, ONCE THE SQ FT HAS BEEN VERIFIED FOR
 ACTUAL SCOPE OF WORK, THIS VALUE MAY CHANGE.
  
 6) NOTE: PLEASE KNOW, THIS INTERIOR BUILD OUT WILL
 REQUIRE A NEW NOTICE OF COMMENCEMENT AS THE ONE UNDER
 THE BUILDING HAS EXPIRED AND IS NOT PARTOF THIS SCOPE
 OF WORK. FS 713.13
  
 7) NOTE: PLEASE INDICATE AND SHOW ON LOAD SUMMARY AND
 CALCULATIONS ALL CONTINUOUS LOADS AT 125%.
 215.3, 230.42
  
 ** PLEASE KNOW, AS PLANS FOR MANY ITEMS WILL CHANGE ,
 ALL NOTES MAY NOT BE COMPLETE AT THIS TIME.
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717