Plan Review Notes For Permit 06100093 |
Permit Number |
06100093 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-10-17 16:23:38 | | | DENIED BY BUILDING | | | | 1) A RECORDED COPY OF THE NOTICE OF | | COMMENCEMENT MUST BE SUBMITTED BEFORE A | | PERMIT CAN BE ISSUED. | | | | 2) SPECIFY THE NUMBER OF FLOORS AND BUILDING HEIGHT ON | | THE PLANS. | | | | 3) THE CONSTRUCTION TYPE SPECIFIED ON THE PLANS IS | | INCORRECT. THIS STRUCTURE IS A TYPE II B SPRINKLERED | | BUILDING, USING 2004 FBC DESIGNATIONS. | | | | 4) PROVIDE A DETAIL OF THE BREAK ROOM CABINETS AND AND | | COUNTERS. THE BUILT-IN COUNTERS MUST COMPLY WITH FBC | | 11-4.32.4AND THE SINK MUST COMPLY WITH FBC 11-4.24. | | SHOW COMPLIANCE. | | | | 5)THE GLASS IN THE SWINGING DOORS IS REQUIRED TO BE | | SAFETY GLAZING PER FBC 2406.3(1). | | | | 6) WOOD FLOORING MUST COMPLY WITH FBC 804.4.2. | | | | 7) THE FIXED GLASS WINDOWS ADJACENT TO THE DOORS ARE | | REQUIRED TO BE SAFETY GLAZING PER FBC 2406.3(6). | | | | 8)DOOR HARDWARE SHALL COMPLY WITH FBC 11-4.13.9. | | | | 9) FIRE DOORS SHALL BE SELF CLOSING OR | | AUTOMATIC-CLOSING AS REQUIRE BY FBC 715.3.7. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | |
|