2007-04-25 18:01:04 | ** UNSAT 3RD REVIEW ** |
| |
| |
| ***** PLEASE SEE THE PLANS HAVE NOW BEEN REVISED |
| REMOVING MANY CODE COMPLIANT ITEMS WHICH WERE OK ON |
| PREVIOUS PLANS???? |
| PLEASE SEE THERE ARE SEVERAL ITEMS WHICH WERE ON PLANS |
| WHICH HAVE NOW BEEN REMOVED. |
| IT IS UNCLEAR WHY SO MANY OF THESE ITEMS WERE REMOVED |
| OR CHANGED FROM PREVIOUS PLANS WHICH WERE SUBMITTED ON |
| THE FIRST REVIEW. |
| |
| ** ONE COPY OF EACH WAS RETAINED BY THIS OFFICE. |
| |
| 1) NOTE: PLEASE INDICATE THE AIC RATINGS ON PLANS AS |
| PREVIOUSLY SHOWN. |
| 110.9 |
| FBC 106.1.2 |
| |
| 2) NOTE: PLEASE SEE MISSING RECEPTACLE FOR MASTER |
| BEDROOM 2FT OR MORE OF WALL PER 210.52 |
| |
| 3) NOTE: PLEASE SEE MISSING DESIGNATIONS ON PANEL |
| SCHEDULE AS PREVIOUSLY DONE ON PANEL SCHEDULE. PLEASE |
| SEE THE FOLLOWING TEXT WHICH IS TAKEN DIRECTLY FROM THE |
| NEC> |
| * CODE TO REQUIRE THAT THE IDENTIFICATION FOR EVERY |
| CIRCUIT SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE |
| LEGIBLE AND CLEARLY STATE THE SPECIFIC PURPOSE FOR |
| WHICH THE CIRCUIT IS USED. CIRCUITS USED FOR THE SAME |
| PURPOSE MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR |
| EXAMPLE, SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY |
| OUTLETS IN THE KITCHEN, DINING ROOM, AND KITCHEN |
| COUNTERTOPS. IDENTIFYING THE CIRCUITS AS SMALL |
| APPLIANCE BRANCH CIRCUITS IS NOT ACCEPTABLE; INSTEAD, |
| THEY SHOULD BE IDENTIFIED AS ``KITCHEN WALL |
| RECEPTACLES,'' ``DINING ROOM FLOOR RECEPTACLE,'' OR |
| ``KITCHEN COUNTERTOP RECEPTACLES LEFT OF SINK.'' |
| CIRCUIT DIRECTORIES CONTAINING MULTIPLE ENTRIES WITH |
| ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT PROVIDE THE |
| SUFFICIENT DETAIL REQUIRED BY THIS SECTION.* |
| 408.4, 310.16, 240.4 ETC |
| FBC 106.3.5.4 |
| |
| 4) NOTE: PLEASE SEE THE KW RATING WHICH IS 7KW ON |
| MECHANICAL PLANS IS NOW SHOWN AS 6.5KW ON ELECTRICAL |
| PLANS.?? |
| PLEASE COORDINATE. |
| 424.3, 310.16, 240.4 ETC. |
| |
| 5) NOTE: PLEASE SEE MISSING AFCI NOTE WHICH MENTIONS |
| ALL REQUIRED PROTECTED OUTLETS IN BEDROOMS PER 210.12. |
| (PREVIOUS PLANS NOTES WERE OK) |
| |
| 6) NOTE: PLEASE SEE MISSING REQUIRED CODES TO BE STATED |
| ON ELECTRICAL PLANS AS PREVIOUSLY DONE. |
| NFPA-70 2002 |
| NFPA-72 2002 |
| THE 2004 FBC. |
| |
| 7) NOTE: PLEASE SEE MISSING GFI FOR CU OUTSIDE PER |
| 210.8, 210.63 |
| |
| 8) NOTE: PLEASE SEE MISSING DISCONNECT FOR WATER HEATER |
| PER 422.31. |
| THIS MENTIONS *HARD-WIRED* WHICH IS REQUIRED PER THE |
| NEC ALSO, HOWEVER THE SYMBOL USED FOR THIS IS A |
| RECEPTACLE?? |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
| |