Plan Review Notes
Plan Review Notes For Permit 06100087
Permit Number 06100087
Review Stop E
Sequence Number 3
Notes
Date Text
2007-04-25 18:01:04** UNSAT 3RD REVIEW **
  
  
 ***** PLEASE SEE THE PLANS HAVE NOW BEEN REVISED
 REMOVING MANY CODE COMPLIANT ITEMS WHICH WERE OK ON
 PREVIOUS PLANS????
 PLEASE SEE THERE ARE SEVERAL ITEMS WHICH WERE ON PLANS
 WHICH HAVE NOW BEEN REMOVED.
 IT IS UNCLEAR WHY SO MANY OF THESE ITEMS WERE REMOVED
 OR CHANGED FROM PREVIOUS PLANS WHICH WERE SUBMITTED ON
 THE FIRST REVIEW.
  
 ** ONE COPY OF EACH WAS RETAINED BY THIS OFFICE.
  
 1) NOTE: PLEASE INDICATE THE AIC RATINGS ON PLANS AS
 PREVIOUSLY SHOWN.
 110.9
 FBC 106.1.2
  
 2) NOTE: PLEASE SEE MISSING RECEPTACLE FOR MASTER
 BEDROOM 2FT OR MORE OF WALL PER 210.52
  
 3) NOTE: PLEASE SEE MISSING DESIGNATIONS ON PANEL
 SCHEDULE AS PREVIOUSLY DONE ON PANEL SCHEDULE. PLEASE
 SEE THE FOLLOWING TEXT WHICH IS TAKEN DIRECTLY FROM THE
 NEC>
 * CODE TO REQUIRE THAT THE IDENTIFICATION FOR EVERY
 CIRCUIT SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE
 LEGIBLE AND CLEARLY STATE THE SPECIFIC PURPOSE FOR
 WHICH THE CIRCUIT IS USED. CIRCUITS USED FOR THE SAME
 PURPOSE MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR
 EXAMPLE, SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY
 OUTLETS IN THE KITCHEN, DINING ROOM, AND KITCHEN
 COUNTERTOPS. IDENTIFYING THE CIRCUITS AS SMALL
 APPLIANCE BRANCH CIRCUITS IS NOT ACCEPTABLE; INSTEAD,
 THEY SHOULD BE IDENTIFIED AS ``KITCHEN WALL
 RECEPTACLES,'' ``DINING ROOM FLOOR RECEPTACLE,'' OR
 ``KITCHEN COUNTERTOP RECEPTACLES LEFT OF SINK.''
 CIRCUIT DIRECTORIES CONTAINING MULTIPLE ENTRIES WITH
 ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT PROVIDE THE
 SUFFICIENT DETAIL REQUIRED BY THIS SECTION.*
 408.4, 310.16, 240.4 ETC
 FBC 106.3.5.4
  
 4) NOTE: PLEASE SEE THE KW RATING WHICH IS 7KW ON
 MECHANICAL PLANS IS NOW SHOWN AS 6.5KW ON ELECTRICAL
 PLANS.??
 PLEASE COORDINATE.
 424.3, 310.16, 240.4 ETC.
  
 5) NOTE: PLEASE SEE MISSING AFCI NOTE WHICH MENTIONS
 ALL REQUIRED PROTECTED OUTLETS IN BEDROOMS PER 210.12.
 (PREVIOUS PLANS NOTES WERE OK)
  
 6) NOTE: PLEASE SEE MISSING REQUIRED CODES TO BE STATED
 ON ELECTRICAL PLANS AS PREVIOUSLY DONE.
 NFPA-70 2002
 NFPA-72 2002
 THE 2004 FBC.
  
 7) NOTE: PLEASE SEE MISSING GFI FOR CU OUTSIDE PER
 210.8, 210.63
  
 8) NOTE: PLEASE SEE MISSING DISCONNECT FOR WATER HEATER
 PER 422.31.
 THIS MENTIONS *HARD-WIRED* WHICH IS REQUIRED PER THE
 NEC ALSO, HOWEVER THE SYMBOL USED FOR THIS IS A
 RECEPTACLE??
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  