2007-01-19 07:23:42 | |
| |
| |
| *** UNSAT 2ND REVIEW *** |
| |
| 1) NOTE: PLEASE SEE THE EXACT SAME PLANS WHICH WERE |
| PREVIOUSLY SUBMITTED ARE SUBMITTED BACK WITH OUT |
| CORRECTIONS MADE. |
| PLEASE SEE ONE SET HAS SOME HAND DRAWN CHANGES WHICH |
| ARE NOT PERMITTED TO PLANS WHICH ARE SIGNED, DATED AND |
| SEALED BY AN ARCHITECT OR ENGINEER. PLEASE GIVE PLANS |
| BACK TO THE DESIGN PROFESSIONAL, SHEETS WILL BE |
| REQUIRED TO BE RE-PRINTED AND SIGNED DATED AND SEALED |
| AS PREVIOUSLY DONE. |
| PLEASE SEE THE COMMENTS FROM THE PREVIOUS REVIEW ARE |
| STILL ATTACHED TO PACKAGE. |
| |
| 2) NOTE: PLEASE KNOW THAT A MEETING WAS HELD AT THE |
| SOUTHERN SECTION MEETING IN OCT 06WHERE WE WERE |
| DIRECTLY INFORMED BY NFPA THAT THE USE OF SD FOR SMOKE |
| DETECTORS ON PLANS FOR RESIDENTIAL HOMES IS NOT |
| ACCEPTABLE WHEN THESE DEVICES ANY ACTUALLY FALL UNDER |
| THE DEFINITIONS OF SMOKE ALARMS WHICH WOULD BE SHOWN AS |
| SA/SMOKE ALARMS. |
| THIS INFORMATION WAS NEW TO THIS AHJ AS THE GENERAL USE |
| OF THE SD FOR SMOKE DETECTORS WAS ALWAYS ACCEPTED. |
| BY THE DEFINITIONS AS STATED IN NFPA-72 A SD/ SMOKE |
| DETECTOR IS ONLY A DEVICE WHICH WILL DETECT AND WILL |
| NOT SOUND AN AUDIBLE ALARM. THIS WOULD BE DONE BY |
| HORN/SIREN TYPE DEVICES. PLEASE SEE THE DEFINITIONS OF |
| SA/SMOKE ALARMS; THESE ARE DEVICES WHICH ARE 120V (AS |
| SHOWN) AND WOULD DETECT AND SOUND AN ALARM. THIS IS |
| SOMETHING THAT IS NOW BEING COMMENTED ON OTHER REVIEWS |
| FOR OTHER NEW HOMES. |
| ** PLEASE SEE THAT SMOKE ALARMS ARE STATED IN THE FBC |
| RESIDENTIAL CODE/ FBC AND IN NFPA-72. |
| PLANS ARE BEING CORRECTED FOR OTHER ITEMS, PLEASE MAKE |
| THIS ADJUSTMENT. |
| IF THERE ARE ANY QUESTIONS ON THIS COMMENT PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE. |
| |
| ** TAKEN FROM THE NFPA-72** |
| 11.5.1.1 SMOKE DETECTION.WHERE REQUIRED BY APPLICABLE |
| LAWS, CODES, OR STANDARDS FOR THE SPECIFIED OCCUPANCY, |
| APPROVED SINGLE- AND MULTIPLE-STATION SMOKE ALARMS |
| SHALL BE INSTALLED AS FOLLOWS: |
| (1)IN ALL SLEEPING ROOMS |
| EXCEPTION:SMOKE ALARMS SHALL NOT BE REQUIRED IN |
| SLEEPING ROOMS IN EXISTING ONE- AND TWO-FAMILY DWELLING |
| UNITS. |
| (2)OUTSIDE OF EACH SEPARATE SLEEPING AREA, IN THE |
| IMMEDIATE VICINITY OF THE SLEEPING ROOMS |
| (3)ON EACH LEVEL OF THE DWELLING UNIT, INCLUDING |
| BASEMENTS |
| EXCEPTION:IN EXISTING ONE- AND TWO-FAMILY DWELLING |
| UNITS, APPROVED SMOKE ALARMS POWERED BY BATTERIES SHALL |
| BE PERMITTED. |
| 11.5.1.2 NOTIFICATION. |
| (A) FIRE-WARNING EQUIPMENT FOR DWELLING UNITS SHALL |
| PROVIDE A SOUND THAT IS AUDIBLE IN ALL OCCUPIABLE |
| DWELLING AREAS. |
| (B) WHERE MORE THAN ONE SMOKE OR HEAT ALARM IS |
| INSTALLED FOR NEW CONSTRUCTION, THEY SHALL BE ARRANGED |
| SO THAT THE OPERATION OF ANY SMOKE OR HEAT ALARM CAUSES |
| THE ALARM IN ALL SMOKE AND HEAT ALARMS WITHIN THE |
| DWELLING UNIT TO SOUND |
| |
| 11.8.3* SMOKE DETECTORS AND SMOKE ALARMS. SMOKE ALARMS, |
| SMOKE DETECTORS, DEVICES, COMBINATION OF DEVICES, AND |
| EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH THE |
| MANUFACTURER'S LISTING AND INSTRUCTIONS, AND UNLESS |
| SPECIFICALLY LISTED FOR THE APPLICATION, SHALL COMPLY |
| WITH REQUIREMENTS IN11.8.3.1 THROUGH11.8.3.5. |
| |
| 3) NOTE: PLEASE SEE COPY OF FLORIDA STATUTES |
| 553.80(2)(B) WITH RESPECT TO REPEAT NOTES FOR CODE |
| COMPLIANCE. THIS IS BEING GIVEN ONLY AS NOTICE AT THIS |
| TIME. |
| |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |