Plan Review Notes
Plan Review Notes For Permit 06100087
Permit Number 06100087
Review Stop E
Sequence Number 2
Notes
Date Text
2007-01-19 07:23:42 
  
  
 *** UNSAT 2ND REVIEW ***
  
 1) NOTE: PLEASE SEE THE EXACT SAME PLANS WHICH WERE
 PREVIOUSLY SUBMITTED ARE SUBMITTED BACK WITH OUT
 CORRECTIONS MADE.
 PLEASE SEE ONE SET HAS SOME HAND DRAWN CHANGES WHICH
 ARE NOT PERMITTED TO PLANS WHICH ARE SIGNED, DATED AND
 SEALED BY AN ARCHITECT OR ENGINEER. PLEASE GIVE PLANS
 BACK TO THE DESIGN PROFESSIONAL, SHEETS WILL BE
 REQUIRED TO BE RE-PRINTED AND SIGNED DATED AND SEALED
 AS PREVIOUSLY DONE.
 PLEASE SEE THE COMMENTS FROM THE PREVIOUS REVIEW ARE
 STILL ATTACHED TO PACKAGE.
  
 2) NOTE: PLEASE KNOW THAT A MEETING WAS HELD AT THE
 SOUTHERN SECTION MEETING IN OCT 06WHERE WE WERE
 DIRECTLY INFORMED BY NFPA THAT THE USE OF SD FOR SMOKE
 DETECTORS ON PLANS FOR RESIDENTIAL HOMES IS NOT
 ACCEPTABLE WHEN THESE DEVICES ANY ACTUALLY FALL UNDER
 THE DEFINITIONS OF SMOKE ALARMS WHICH WOULD BE SHOWN AS
 SA/SMOKE ALARMS.
 THIS INFORMATION WAS NEW TO THIS AHJ AS THE GENERAL USE
 OF THE SD FOR SMOKE DETECTORS WAS ALWAYS ACCEPTED.
 BY THE DEFINITIONS AS STATED IN NFPA-72 A SD/ SMOKE
 DETECTOR IS ONLY A DEVICE WHICH WILL DETECT AND WILL
 NOT SOUND AN AUDIBLE ALARM. THIS WOULD BE DONE BY
 HORN/SIREN TYPE DEVICES. PLEASE SEE THE DEFINITIONS OF
 SA/SMOKE ALARMS; THESE ARE DEVICES WHICH ARE 120V (AS
 SHOWN) AND WOULD DETECT AND SOUND AN ALARM. THIS IS
 SOMETHING THAT IS NOW BEING COMMENTED ON OTHER REVIEWS
 FOR OTHER NEW HOMES.
 ** PLEASE SEE THAT SMOKE ALARMS ARE STATED IN THE FBC
 RESIDENTIAL CODE/ FBC AND IN NFPA-72.
 PLANS ARE BEING CORRECTED FOR OTHER ITEMS, PLEASE MAKE
 THIS ADJUSTMENT.
 IF THERE ARE ANY QUESTIONS ON THIS COMMENT PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE.
  
 ** TAKEN FROM THE NFPA-72**
 11.5.1.1 SMOKE DETECTION.WHERE REQUIRED BY APPLICABLE
 LAWS, CODES, OR STANDARDS FOR THE SPECIFIED OCCUPANCY,
 APPROVED SINGLE- AND MULTIPLE-STATION SMOKE ALARMS
 SHALL BE INSTALLED AS FOLLOWS:
 (1)IN ALL SLEEPING ROOMS
 EXCEPTION:SMOKE ALARMS SHALL NOT BE REQUIRED IN
 SLEEPING ROOMS IN EXISTING ONE- AND TWO-FAMILY DWELLING
 UNITS.
 (2)OUTSIDE OF EACH SEPARATE SLEEPING AREA, IN THE
 IMMEDIATE VICINITY OF THE SLEEPING ROOMS
 (3)ON EACH LEVEL OF THE DWELLING UNIT, INCLUDING
 BASEMENTS
 EXCEPTION:IN EXISTING ONE- AND TWO-FAMILY DWELLING
 UNITS, APPROVED SMOKE ALARMS POWERED BY BATTERIES SHALL
 BE PERMITTED.
 11.5.1.2 NOTIFICATION.
 (A) FIRE-WARNING EQUIPMENT FOR DWELLING UNITS SHALL
 PROVIDE A SOUND THAT IS AUDIBLE IN ALL OCCUPIABLE
 DWELLING AREAS.
 (B) WHERE MORE THAN ONE SMOKE OR HEAT ALARM IS
 INSTALLED FOR NEW CONSTRUCTION, THEY SHALL BE ARRANGED
 SO THAT THE OPERATION OF ANY SMOKE OR HEAT ALARM CAUSES
 THE ALARM IN ALL SMOKE AND HEAT ALARMS WITHIN THE
 DWELLING UNIT TO SOUND
  
 11.8.3* SMOKE DETECTORS AND SMOKE ALARMS. SMOKE ALARMS,
 SMOKE DETECTORS, DEVICES, COMBINATION OF DEVICES, AND
 EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH THE
 MANUFACTURER'S LISTING AND INSTRUCTIONS, AND UNLESS
 SPECIFICALLY LISTED FOR THE APPLICATION, SHALL COMPLY
 WITH REQUIREMENTS IN11.8.3.1 THROUGH11.8.3.5.
  
 3) NOTE: PLEASE SEE COPY OF FLORIDA STATUTES
 553.80(2)(B) WITH RESPECT TO REPEAT NOTES FOR CODE
 COMPLIANCE. THIS IS BEING GIVEN ONLY AS NOTICE AT THIS
 TIME.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]