Plan Review Notes
Plan Review Notes For Permit 06100087
Permit Number 06100087
Review Stop E
Sequence Number 1
Notes
Date Text
2006-10-06 00:00:00**** UNSAT ****
  
 1) NOTE: PLEASE SEE FAC 61G17 AND FS
 472.025 AS THE SURVEY'S ARE REQUIRED TO
 BE SEALED WHEN SIGNED TO BE VALID.
  
 2) NOTE: PLEASE SEE ALL SEALS ON PLANS
 SHALL BE CLEAR AND VISABLE WITH ALL
 INFORMATION ON SAID SEAL AS REQUIRED PER
 FAC 61G1-16.003, FS 481.221
  
 3) NOTE: PLEASE SEE MISSING DINING
 AREA/BREAKFEST AREAS AND THE LIKE FOR
 CIRCUTING AND MIN 20A #12 CIRCUITS
 REQUIRED TO MEET 210.52B1, 220.16,
 210.11C1
  
 4) NOTE: PLEASE OCP ON 50A RANGE RECEPT
 SHALL NOT EXCEED RATINGS AS PERMITTED IN
 TABLES 220.21B3
  
 5) NOTE: PLEASE SEE OCP FOR AHU, SHALL
 MEET 424.3B FOR MIN 125%.
 PLEASE ADJUST.
  
 2) NOTE: PLEASE LIST THE OCP FOR THE
 BRANCH CIRCUIT TO THE CU.
  
  
 PLEASE SEE NOTES ONE AND TWO ARE
 REQUIRED FOR ALL.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved