2006-11-21 17:39:19 | BUILDING PLAN REVIEW |
| PERMIT:06100080 |
| ADD:2143 REGENTS BLVD |
| CONT: PIONEER HURRICANE PROTECTION. |
| TEL: (561)755- |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| * WEST PALM BEACH AMENDMENTS |
| |
| REVIEW2ND |
| ACTION: DENIED |
| |
| |
| 1)__XX__1.A NOTICE OF COMMENCEMENT MUST BE FILED |
| WITH THE CLERK OF COURTS BEFORE A PERMIT CAN BE ISSUED, |
| FS713.13. |
| |
| __XX__2.PROVIDE BUILDING HEIGHT ON THE PLAN. DESIGN |
| PRESSURES FOR BUILDINGS OVER 60FEET ARE REQUIRED TO BE |
| DESIGNED USING ASCE7, FBC1609.1.1 AND MUST BE DONE BY |
| AN ENGINEER. DOCUMENTS PREPARED BY AN ENGINEER AND |
| SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED SEALED |
| ORIGINALS FAC61G15-23.002. |
| |
| __XX__3.PROVIDE A COPY OF THE CONDO ASSOCIATION |
| APPROVAL. |
| |
| __XX_4.COMPLETE THE ATTACHED INSTALLATION SCHEDULE |
| OR PROVIDE ALL INFORMATION TO SHOW CODE COMPLIANCE IN |
| ANOTHER FORMAT. |
| |
| _XX___5.FLORIDA STATE OR LOCAL PRODUCT APPROVAL |
| REQUIRED, FAC9B72, WWW.FLORIDABUILDING.ORG. |
| |
| __6.ON THE PRODUCT APPROVAL, MARK WHICH DETAILS |
| APPLY TO THIS JOB.PLEASE USE INK RATHER THAN A |
| HIGHLIGHTER. |
| |
| _XX___7.SHOW THE EMERGENCY MEANS OF ESCAPE, FBC |
| R310. |
| |
| _XX___8.PROVIDE A FLOOR PLAN SHOWING WHERE THE |
| SHUTTERS WILL BE INSTALLED AND PANEL SIZES WHICH |
| CORRELATES WITH THE INSTALLATION SCHEDULE, ITEM 4 |
| ABOVE. |
| |
| 2) 106.1.1.CONSTRUCTION DOCUMENTS SHALL BE OF |
| SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| DETERMINED BY THE BUILDING OFFICIAL (SEE ALSO SECTION |
| 106.3.5). |
| |
| MYRON JACOBS |
| BUILDING PLAN REVIEWER |