Date |
Text |
2006-11-27 11:25:52 | DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 FUEL GAS |
| FBC-2004 CHAPTER 1 |
| FBC-2004 CHAPTER 11 |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| |
| 1. COVER SHEET & MECHANICAL SHEETS. LNI CONSULTING |
| ENGINEERS ADDRESS DOES NOT REFLECT THE ADDRESS |
| INFORMATION ON RECORD ON THE DBPR WEBSITE. PLEASE |
| CORRELATE ADDRESS INFORMATION. FAC 61G15-23.002(2) & FS |
| 471.025 (SEE ATTACHED SHEET FROM DBPR WEBSITE) |
| |
| 2. SUBMIT A DETAIL FOR THE DRINKING FOUNTAIN SHOWING |
| ALL THE REQUIREMENTS OF SECTION 11-4.15 AND ALL |
| SUBSECTIONS. |
| |
| 3. SUBMIT A DETAIL FOR THE ACCESSIBLE UNINAL. SHOW THE |
| FOLLOWING: |
| A. 11-4.18.2 HEIGHT |
| B. 11-4.18.3 CLEAR FLOOR SPACE |
| C. 11-4.18.4 FLUSH CONTROLS |
| |
| 4. SHT A-4 ACCESSIBLE BATHROOM ELEVATIONS. PLEASE SHOW |
| COMPLIANCE WITH SECTION 11-4.19.5 FAUCETS. |
| |
| 5. SUBMIT A DETAIL FOR THE CONFERENCE/BREAK ROOM SINK |
| SHOWING COMPLIANCE WITH SECTION 11-4.24 AND ALL |
| SUBSECTIONS. (FORWARD APPROACH MAXIMUM 19" UNDERNEATH |
| THE SINK REQUIRED. CABINET DOORS ARE NOT APPROVED IN |
| THE CLEAR FLOOR SPACE.). |
| |
| 6. PLUMBING SHEETS. AN EMBOSSED SEAL SHALL IMPRESS ALL |
| INFORMATION REQUIRED ON EACH SHEET PER FAC |
| 61G15-23.002(1)(2) & FS 471.025. NO INFORMATION CAN BE |
| GLEANED FROM THE SEAL TO DETERMINE IF THE SEAL IS |
| APPROIATE. PLEASE RESEAL THE PLANS. |
| |
| 7. SHT P-1 IN THE INSTALLATION OR REMOVAL OF ANY PART |
| OF A DRAINAGE SYSTEM, DEAD ENDS SHALL BE PROHIBITED. |
| SECTION 704.5. NOTE STATES TO "CAP& CONCEAL ALL |
| PLUMBING STUBS OUT OF THE LINE OF SITE". CHANGE NOTE TO |
| ENSURE NOT DEAD ENDS ARE LEFT AT THE DEMO PORTION OF |
| THE WORK. |
| |
| 8. SHT P-1 WOMENS TOILET ROOM SHOWS ONE LAV OUTSIDE THE |
| ACCESSIBLE STALL, BUT THE SANT SHOW WASTE LINES TO TWO |
| LAVS. PLEASE CORRELATE FLOOR PLAN AND SANT PIPING. |
| SECTION 106..1.1. |
| |
| 9. SHT P-2 WATER RISER DIAGRAM AND PLUMBING LEGEND |
| INDICATE AIR CHAMBERS. AIR CHAMBERS ARE NOT APPROVED. |
| SECTION 604.9 & PDI-WH 201. DELETE FROM RISER AND |
| LEGEND. WATER HAMMER ARRESTORS ARE REQUIRED TO BE |
| INSTALLED NEAR THE FIXTURES WITH QUICK CLOSING VALVES, |
| (ICE MAKERS, DISH WASHERS, WASH MACHINES ETC.), PER |
| SECTION 604.9. |
| |
| 10. SHT P-2 WATER RISER DIAGRAM IS INDICATING THE |
| URINAL (P-3H) BEING PIPED TO THE WOMENS TOILET ROOM. |
| PLEASE CLARIFY. SECTION 106.1.1. |
| |
| 11. SHT P-2 SEPARATE GAS PERMIT REQUIRED. SUBMIT THE |
| FOLLOWING INFORMATION REQUIRED FOR GAS PERMIT: |
| |
| A. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2004 |
| FUEL GAS CODE. - LENGTHS NOT SHOWN. |
| |
| B. SHOW TYPE OF PIPING MATERIAL BEING |
| INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| NUMBER OF CORRUGATED STAINLESS STEEL |
| TUBING FOR EACH PIPE SIZE IF BEING USED. |
| |
| C. INDICATE THE DELIVERY PRESSURE (PSI) |
| PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| |
| G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND THE |
| FBC-2004 FUEL GAS CODE SEC 402.2. INCLUDING |
| INSTALLATION SHEETS. |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 805-6731 |
| E-MAIL [email protected] |