Plan Review Notes
Plan Review Notes For Permit 06100071
Permit Number 06100071
Review Stop P
Sequence Number 1
Notes
Date Text
2006-11-27 11:25:52DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. COVER SHEET & MECHANICAL SHEETS. LNI CONSULTING
 ENGINEERS ADDRESS DOES NOT REFLECT THE ADDRESS
 INFORMATION ON RECORD ON THE DBPR WEBSITE. PLEASE
 CORRELATE ADDRESS INFORMATION. FAC 61G15-23.002(2) & FS
 471.025 (SEE ATTACHED SHEET FROM DBPR WEBSITE)
  
 2. SUBMIT A DETAIL FOR THE DRINKING FOUNTAIN SHOWING
 ALL THE REQUIREMENTS OF SECTION 11-4.15 AND ALL
 SUBSECTIONS.
  
 3. SUBMIT A DETAIL FOR THE ACCESSIBLE UNINAL. SHOW THE
 FOLLOWING:
 A. 11-4.18.2 HEIGHT
 B. 11-4.18.3 CLEAR FLOOR SPACE
 C. 11-4.18.4 FLUSH CONTROLS
  
 4. SHT A-4 ACCESSIBLE BATHROOM ELEVATIONS. PLEASE SHOW
 COMPLIANCE WITH SECTION 11-4.19.5 FAUCETS.
  
 5. SUBMIT A DETAIL FOR THE CONFERENCE/BREAK ROOM SINK
 SHOWING COMPLIANCE WITH SECTION 11-4.24 AND ALL
 SUBSECTIONS. (FORWARD APPROACH MAXIMUM 19" UNDERNEATH
 THE SINK REQUIRED. CABINET DOORS ARE NOT APPROVED IN
 THE CLEAR FLOOR SPACE.).
  
 6. PLUMBING SHEETS. AN EMBOSSED SEAL SHALL IMPRESS ALL
 INFORMATION REQUIRED ON EACH SHEET PER FAC
 61G15-23.002(1)(2) & FS 471.025. NO INFORMATION CAN BE
 GLEANED FROM THE SEAL TO DETERMINE IF THE SEAL IS
 APPROIATE. PLEASE RESEAL THE PLANS.
  
 7. SHT P-1 IN THE INSTALLATION OR REMOVAL OF ANY PART
 OF A DRAINAGE SYSTEM, DEAD ENDS SHALL BE PROHIBITED.
 SECTION 704.5. NOTE STATES TO "CAP& CONCEAL ALL
 PLUMBING STUBS OUT OF THE LINE OF SITE". CHANGE NOTE TO
 ENSURE NOT DEAD ENDS ARE LEFT AT THE DEMO PORTION OF
 THE WORK.
  
 8. SHT P-1 WOMENS TOILET ROOM SHOWS ONE LAV OUTSIDE THE
 ACCESSIBLE STALL, BUT THE SANT SHOW WASTE LINES TO TWO
 LAVS. PLEASE CORRELATE FLOOR PLAN AND SANT PIPING.
 SECTION 106..1.1.
  
 9. SHT P-2 WATER RISER DIAGRAM AND PLUMBING LEGEND
 INDICATE AIR CHAMBERS. AIR CHAMBERS ARE NOT APPROVED.
 SECTION 604.9 & PDI-WH 201. DELETE FROM RISER AND
 LEGEND. WATER HAMMER ARRESTORS ARE REQUIRED TO BE
 INSTALLED NEAR THE FIXTURES WITH QUICK CLOSING VALVES,
 (ICE MAKERS, DISH WASHERS, WASH MACHINES ETC.), PER
 SECTION 604.9.
  
 10. SHT P-2 WATER RISER DIAGRAM IS INDICATING THE
 URINAL (P-3H) BEING PIPED TO THE WOMENS TOILET ROOM.
 PLEASE CLARIFY. SECTION 106.1.1.
  
 11. SHT P-2 SEPARATE GAS PERMIT REQUIRED. SUBMIT THE
 FOLLOWING INFORMATION REQUIRED FOR GAS PERMIT:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. - LENGTHS NOT SHOWN.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 C. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2. INCLUDING
 INSTALLATION SHEETS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]