Plan Review Notes
Plan Review Notes For Permit 06100071
Permit Number 06100071
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2006-11-30 10:38:03*****DENIED*****
  
  
  
 1.THE NUMERICAL ADDRESS OF THE JOB SITE SHALL BE IN
 THE TITLE BLOCK OF EACH PLAN SHEET, SPECIFICATION
 PAPERWORK, OR ANY OTHER INFORMATIONAL DOCUMENT WHICH IS
 SUBMITTED FOR PLAN REVIEW.IF ADDITIONAL INFORMATION
 IS NEEDED CONCERNING THE ADDRESS, CONTACT LILI URSA AT
 561-822-1239.
  
 2.ON SHEET LS-1 IN THE FIRE EXTINGUISHER CABINET
 NOTE, CLARIFY THE WORDING (AFETY) WHICH WAS USED.
  
 3.PROVIDE INTERIOR FINISH CLASSIFICATION.INTERIOR
 FINISH CLASSIFICATION IN EXITS AND EXIT ACCESS
 CORRIDORS SHALL BE CLASS "A" OR CLASS "B".
  
 4.SEAL MISSING OR UNRECOGNIZABLE ON SHEETS FS-1 AND
 FS-2.
  
 5.HOW WILL THE SCOPE OF WORK AFFECT THE COMPONENTS OF
 THE FIRE ALARM SYSTEM?IF THE FIRE ALARM SYSTEM IS
 MODIFIED, SEPARATE SHOP DRAWING/PLANS ARE REQUIRED.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722