Plan Review Notes
Plan Review Notes For Permit 06100071
Permit Number 06100071
Review Stop E
Sequence Number 1
Notes
Date Text
2006-10-22 19:39:28***** UNSAT ******
  
 1) NOTE: PLEASE SEE FLORIDA STATUTES 471.025 AND
 FLORIDA ADMINISTRATIVE CODE 61G15-23.001,.002 WHICH
 REQUIRES ALL SEALS ON SAID PLANS TO BE RAISED AND CLEAR
 AND VISABLE WITH ALL SAID INFORMATION REQUIRED ON SAID
 SEAL.
 PLEASE SEE M, P, FS SHEETS ARE NOT CLEAR.
 PLEASE ALSO SEE THE SAME STATUTES AND ADMINISTRATIVE
 SECTIONS ABOVE AS THE SIGNATURE OF THE ENGINEER OF
 RECORD SHALL BE THAT WHICH RECOGNIZED BY THIS OFFICE
 AND IS CURRENTLY ON FILE. PLEASE SEE PLANS ARE "NOT"
 SIGNED WITH SIGNATURE CURRENTLY ON FILE.
  
 2) NOTE: PLEASE SEEFS 471.023, FS 481.229(1)(C) AS A
 "DRAFTING/DESIGN" FIRM MAY NOT PRODUCE PLANS FOR SCOPE
 OF WORK AS SHOWN. PLEASE PROVIDE LICENSE INFORMATION
 FOR "TRONIX INC". PLEASE SEE SCOPE OF WORK SHOWN AND
 SUBMITTED IS REQUIRED TO BE DONE BY A LICENSED PE PER
 FS 471.003 (H)(2A).
 PLEASE SEE FAC 61G15-23.002
 IT IS CLEAR TO THIS OFFICE THAT PLANS ARE SIGNED DATED
 AND SEALED BY AN ENGINEER FOR THE ELECTRICAL SHEETS,
 HOWEVER THEY ARE PRODUCED BY WHAT APPEARS TO BE A
 DRAFTING FIRM AND THIS IS STATED ON SAID TITLE BLOCKS.
 NO CERTIFICATE OF AUTHORIZATION NUMBER COULD BE LOCATED
 FOR SAID FIRM NOR COULD WE LOCATE THE NAME ON A SEARCH
 WITH THE DEPARTMENT OF BUSINESS AND PROFESSIONAL
 REGULATION FOR THE FLORIDA BOARD OF PROFESSIONAL
 ENGINEERS. PLEASE KNOW THIS HAS BEEN VERIFIED WITH THE
 STATE INVESTIGATOR AND STATE PROSECUTING ATTORNEY.
 PLEASE ALSO SEE 471.025 (3).
  
 ** PLEASE KNOW AS THIS OFFICE HAS HAD SIMILAR COMMENTS
 AND INSTANCES FOR ABOVE ON PREVIOUS PROJECTS ON ONE OR
 MORE OF THE DESIGNERS ON PLANS,ONE COMPLETE SET OF
 PLANS WILL BE RETAINED BY THIS OFFICE AT THIS TIME FOR
 FILE.
 **** IMPORTANT****
 THE ABOVE COMMENTS 1&2 ARE REQUIRED FOR ALL SHEETS AND
 FOR ALL TRADES WHETHER OR NOT COMMENTS ARE MADE BY
 OTHER REVIEWER(S).
  
 3) NOTE: PLEASE BE SURE TO INCLUDE ALL RELEVANT CODES
 ON PLANS FOR DESIGN AT HAND. PLEASE SEE THE FOLLOWING
 AT A MINIMUM WILL BE REQUIRED: 2002 NFPA-70, 2002
 NFPA-110, NFPA-72, 2003 NFPA-101, 2004 FBC.
  
 4) NOTE: PLEASE SUBMIT AND PROVIDE ALL MANUFACTURES
 SPECS/CUT SHEETS FOR THE GENERATOR/SUB-BASE FUEL TANK/
 AND ATS DEVICE FOR REVIEW.
 PLEASE SEE 90.7, 110.3, ETC
 THERE ARE CODE COMPLIANCE ITEMS WHICH CAN NOT BE
 VERIFIED AT THIS TIME AS THESE ITEMS HAVE NOT BEEN
 SUBMITTED. PLEASE ALSO SEE OTHER NOTES WHICH WILL
 DIRECTLY AFFECT THIS.
  
 5) NOTE: PLEASE INDICATE IF GENERATOR WILL BE A
 SEPARATELY DERIVED SYSTEMM? PLEASE KNOW, IT IS KNOWN
 FROM THIS OFFICE THAT ALL KOHLER GEN'S SHIPPED FROM THE
 MANUFACTURE COME WIRED FOR "SD" SYSTEMS. IF INDEED THIS
 IS HOW SYSTEM WILL BE INSTALLED PLEASE BE SURE TO SHOW
 AND INDICATE GROUNDING ELECTRODE SYSTEM AT THE GEN FOR
 A SD SYSTE, 250.50, 250.56 ETC.
 250.20, 250.30, ETC.
 PLEASE ALSO BE SURE TO UPDATE THE ATS AS THIS WILL BE
 REQUIRED TO BE A 4POLE UNIT. PLEASE BE SURE TO ADJUST
 PLANS AND SPECS ACCORDINGLY.
 PLEASE SEE RISER AS SHOWN DOES NOT INDICATE A SD
 SYSTEM.? PLEASE SEE MANUFACTURES SPECS/CUT SHEETS.
  
 6) NOTE: PLEASE SEE PLANS, BY NOTES WHICH IS STATED ON
 PLANS AND HOW SYSTEM IS SHOWN, THIS IS A "LEGALLY
 REQUIRED" STANDBY SYSTEM. PLEASE SEE ALL REQUIREMENTS
 IN 701. PLEASE BE SURE TO PROVIDE ALL MIN ON-SITE FUEL
 REQUIREMENTS.
 IF NOT A LSS. PLEASE ADJUST LIGHTING ETC. PLEASE SEE
 NEXT COMMENT.
  
 7) NOTE: PLEASE PROVIDE MINIMUM REQUIRED BATTERY BACK
 UP FIXTURES FOR ALL MEANS OF EGRESSS AREAS WHICH IS
 REQUIRED TO PROVIDE A MIN OF 1FT CANDLE UNDER EMERGENCY
 POWER. PLEASE SEE NFPA-101 7.8, 7.9.2.2.
 PLEASE UPDATE FIXTURE SCHEDULE AS SOME SORT OF BATTERY
 BACK UP FIXTURES WILL BE REQUIRED FOR EM LTS. PLEASE
 SEE 700.12E FOR CIRCUITING OF FIXTURES TO THE NORMAL
 LIGHTING CIRCUITS IN ANY ONE AREA. NO SINGLE MEANS OF
 THE TRIPPINGOF A SWITCH/BREAKER OR OVER-CURRENT
 PROTECTIVE DEVICE CAN LEAVE ANY ONE AREA IN TOTAL
 DARKNESS.
  
 8) NOTE: PLEASE SEE FBC 11-4.28.1, 11-4.28.3(4) AS MIN
 LIGHTING LEVELS IN ALL AREAS REQUIRED AT A MIN OF 75
 CANDELA. PLEASE ADJUST AS SOME AREAS DO NOT MEET THIS.
  
 9) NOTE: PLEASE SEE FBC CHAPTER 13, 13-415.1.ABC.1.1,
 .1.2 AND .1.3 FOR MINLIGHTING CONTROLS FOR NEW BUILD
 OUT.
 PLEASE PROVIDE/SHOW SYSTEM.
 PLEASE PROVIDE SCHEDULING.
 PLEASE INDICATE ALL DEVICES REQUIRED IN SEPARATE
 SPACES.
 PLEASE SEE REQUIRMENTS FOR DEVICES LOCATED AT THE
 LOCATION OF INGRESS/EGRES FOR THE OCCUPANT TO OVER RIDE
 ANY TIME OF DAY SCHEDULED SYSTEM.
 PLEASE PROVIDE MAX OVER RIDE DEVICE TIMES AND LIST
 DEVICES WHICH WILL BE USED ON SYMBOL LEGEND. PLEASE
 KNOW A MAX OF 30MINS FOR OCCUPANT TYPE DEVICES AND A
 MAX OF 4HRS FOR TIMER TYPE DEVICES.
 PLEASE PROVIDE MIN PERFORMANCE CALCULATIONS FOR
 LIGHTING LEVELS. PLEASE SEE 13-415.2, 13-415.2.ABC.1,
 PLEASE SEE SPACE BY SPACE METHODS AS SOME AREAS CAN NOT
 BE FIGURED INTO ALL OFFICE AREA. PLEASE SEE THERE ARE
 SOME EXCEPTIONS FOR MEANS OF EGRESS ETC.
 PLEASE SEE TABLES 415.2.B ETC
  
 10) NOTE: PLEASE SEE MISSING DISCONNECTING MEANS
 REQUIRED FOR FEEDERS FROM GENERATOR. PLEASE SEE THIS
 SHALL BE LOCATED IN CLOSE PROXIMITY OF THE EXISTING NEW
 MAIN FOR SPACE. PLEASE SEE 225.31-225.39.
 PLEASE SEE 701 OR 702 AS SYSTEM AS SHOWN IS NOT YET
 CLEAR WHICH IT WILL BE.
  
 11) NOTE: PLEASE701.6 OR 702.5 AS THE SYSTEM
 INCLUDING THE ATS SHALL ALL BE RATED FOR THE AVAILABLE
 FAULT CURRENT FROM NORMAL AND EM SIDE.
 PLEASE SEE SPECS AND FAULT CURRENT CALCULATIONS WILL BE
 REQUIRED TO BE NOTED. 110.9, 240.12
 PLEASE ALSO SEE NFPA-110 2002 "6.5.2 SHORT CIRCUIT
 CURRENT. THE MAXIMUM AVAILABLE SHORT CIRCUIT CURRENT
 FROM BOTH THE UTILITY SOURCE AND THE EMERGENCY ENERGY
 SOURCE SHALL BE EVALUATED FOR ABILITY TO SATISFY THIS
 COORDINATION CAPABILITY."
  
 12) NOTE: PLEASE PROVIDE AIC RATINGS FOR ALL NEW
 SERVICE EQUIPMENT. PANELS INDICATE 10K, HOWEVER NOTHING
 SHOWN FOR MAIN? PLEASE SEE 240.12 FOR COORDINATION OF
 SYSTEMS. 110.9
  
 13) NOTE: PLEASE PROVIDE INFORMATION ON RISER AS RISER
 DOES NOT INDICATE OF THERE IS A MAIN DISCONNECT LOCATED
 AHEAD OF THE NEW METER AND MAIN DISCONNECT. PLEASE SEE
 250.6, 250.24, AS AN "EQUIPMENT GROUNDING CONDUCTOR" IS
 BEING SHOWN AHEAD OF METER WHICHIS NOT PERMITTED.
 PLEASE KNOW HOWEVER IF INDEED THERE IS A MAIN LOCATED
 AHEAD OF THIS METER AND MAIN, PLEASE NOTE AND INDICATE
 A "FLOATING NEUTRAL KIT REQUIRED" AT METER TO
 ALLEAVIATE OBJECTIONABLE CURRENTS.250.6
  
 14) NOTE: PLEASE SEE THAT PANEL SCHEDULE SHALL BE
 SPECIFIC TO ALL AREAS AND ROOMS FOR BRANCH CIRCUITING
 AS SHOWN. PLEASE SEE "GEN LTS" AND GEN RECEPTS' ARE NOT
 SPECIFIC TO ROOMS AND AREAS. PLEASE SEE 408.4. IT IS
 KNOWN TO THE OFFICE THAT DURING CONSTRUCTION CIRCUITING
 MAY CHANGE, HOWEVER THIS CAN BE REVISED AT A LATER DATE
 ALONG WITH ANY OTHER REVISIONS WHICH MAY TAKE PLACE.
 THIS IS REQUIRED AT THIS TIME> IE: ACCOUNTING RECEPTS,
 GEN MGR LTS, BATH RECEPTS ETC.
  
 15) NOTE: PLEASE SEE RISER IS SHOWING THE SAME FEEDERS
 FORM THE HV PANEL "A" TO TRANSFORMER AS THE FEEDERS
 FROM THE TRANSFORMER TO THE PANEL "A1 ". PLEASE SEE
 THIS IS A SD SYSTEM STEP DOWN UNIT. 250.30, 250.20 ETC
  
 NEUTRAL IS NOT INSTALLED TO TRANSFORMER).
  
 16) NOTE: PLEASE SEE BUILDING REVIEW NOTES AS THE
 SPECIFICATIONS FOR THE GENERATOR SLAB SHALL BE PROVIDED
 AT THIS TIME WITH ALL INFORMATION REQUIRED FOR
 STRUCTURAL INTEGRITYOF SYSTEM'S REQUIRED PER NFPA-110
 CHAPTER 7.
  
 17) NOTE: PLEASE KNOW AS THERE IS MISSING INFORMATION
 REQUIRED AT THIS TIME FOR REVIEW, THERE MAY BE COMMENTS
 ON NEXT REVIEW.
  
 ** PLEASE BE SURE TO SEE COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT THE ELECTRICLA PLANS.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
  
2006-10-22 18:18:52IN ELEC FOR REVIEW.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved