2007-03-27 19:00:04REVISED PAGE M2.1
  
 -----------------PROVISO-------------------
  
 EXHAUST DUCTS UNDER POSITIVE PRESSURE (WHETHER EXISTING
 OR NEW) SHALL NOT EXTEND INTO OR PASS THROUGH A PLENUM