2006-10-13 07:19:21 | **** UNSAT *** |
| |
| |
| 1) NOTE: PLEASE SEE FBC CHAPTER 13 13-415.1.ABC.1.1, |
| .1.2 AND .1.3. |
| PLEASE ALSO SEE 13-415.2.ABC.1. PLEASE SEE THIS SPACE |
| WAS A "SHELL" SPACE AND IS NOW BEING BUILT OUT UNDER |
| THE 2004 FBC. PLEASE ADJUST AS NEEDED. |
| |
| 2) NOTE: PLEASE VERIFY THE EXISTING EXIT LT BEING SHOWN |
| FROM SPACE LEADING TO STAIR TOWER. PLEASE KNOW, THE |
| CIRCUITING SHALL MEET 700.12E. PLEASE SHOW. |
| |
| 3) NOTE: PLEASE CLARIFY THE PANEL SCHEDULE MENTIONS A |
| "RECEPT" FOR THE INSTA-HOT. PLEASE SEE 430.30, 430.31 |
| ETC AS LOAD OF THIS SIZE WHEN UNIT IS REQUIRED TO |
| CONTAIN A DISCONNECT , A PLUG MAY NOT BE USED. PLEASE |
| ALSO VERIFY IF THE DISCONNECTING MEANS CONTAINS OCP, IF |
| SO ,PLEASE SEE 110.26. |
| |
| 4) NOTE: PLEASE SEE PLANS ARE CALLING THE ROOM WHERE |
| THE ELECTRICAL PANELS ARE LOCATED AS "IT" ROOM?? PLEASE |
| VERIFY AS IF THIS IS INDEED GOING TO BE AN "IT" ROOM, |
| PLEASE SEE NFPA-75, AND NFPA-70 645 FOR REQUIREMENTS. |
| PLEASE SEE CHAPTER TWO OF 75 AS TO DEFINITION AND |
| CHARACTERISTICS OF SUCH A ROOM. |
| |
| 5) NOTE: PLEASE SEE VALUE FOR COMPLETE SCOPE OF WORK |
| SHALL BE BASED ON ALL LABOUR AND MATERIALS EVEN IF |
| OWNER SUPPLIED. |
| FBC 108.3 |
| PLEASE SEE $25K IS WAY LOW. PLEASE KNOW, USING TABLES |
| BASED ON THE FBCONE WILL BE ASSESSED. FEES WILL BE |
| OWED. |
| |
| 6) NOTE: PLEASE KNOW, THIS INTERIOR BUILD OUT WILL |
| REQUIRE A NEW NOTICE OF COMMENCEMENT AS THE ONE UDNER |
| THE BUILDING AHS EXPIRED AND IS NOT PARTOF THIS SCOPE |
| OF WORK. FS 713.13 |
| |
| 7) NOTE: PLEASE INDICATE AND SHOW LOAD SUMMARY AND |
| CALCULATIONS INCLUDING ALL CONTINUOUS LOADS AT 125%. |
| 220.3,220.10,220.11,220.13, ETC 215.3, 230.42 |
| |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |