Plan Review Notes
Plan Review Notes For Permit 06100032
Permit Number 06100032
Review Stop E
Sequence Number 1
Notes
Date Text
2006-10-13 07:19:21**** UNSAT ***
  
  
 1) NOTE: PLEASE SEE FBC CHAPTER 13 13-415.1.ABC.1.1,
 .1.2 AND .1.3.
 PLEASE ALSO SEE 13-415.2.ABC.1. PLEASE SEE THIS SPACE
 WAS A "SHELL" SPACE AND IS NOW BEING BUILT OUT UNDER
 THE 2004 FBC. PLEASE ADJUST AS NEEDED.
  
 2) NOTE: PLEASE VERIFY THE EXISTING EXIT LT BEING SHOWN
 FROM SPACE LEADING TO STAIR TOWER. PLEASE KNOW, THE
 CIRCUITING SHALL MEET 700.12E. PLEASE SHOW.
  
 3) NOTE: PLEASE CLARIFY THE PANEL SCHEDULE MENTIONS A
 "RECEPT" FOR THE INSTA-HOT. PLEASE SEE 430.30, 430.31
 ETC AS LOAD OF THIS SIZE WHEN UNIT IS REQUIRED TO
 CONTAIN A DISCONNECT , A PLUG MAY NOT BE USED. PLEASE
 ALSO VERIFY IF THE DISCONNECTING MEANS CONTAINS OCP, IF
 SO ,PLEASE SEE 110.26.
  
 4) NOTE: PLEASE SEE PLANS ARE CALLING THE ROOM WHERE
 THE ELECTRICAL PANELS ARE LOCATED AS "IT" ROOM?? PLEASE
 VERIFY AS IF THIS IS INDEED GOING TO BE AN "IT" ROOM,
 PLEASE SEE NFPA-75, AND NFPA-70 645 FOR REQUIREMENTS.
 PLEASE SEE CHAPTER TWO OF 75 AS TO DEFINITION AND
 CHARACTERISTICS OF SUCH A ROOM.
  
 5) NOTE: PLEASE SEE VALUE FOR COMPLETE SCOPE OF WORK
 SHALL BE BASED ON ALL LABOUR AND MATERIALS EVEN IF
 OWNER SUPPLIED.
 FBC 108.3
 PLEASE SEE $25K IS WAY LOW. PLEASE KNOW, USING TABLES
 BASED ON THE FBCONE WILL BE ASSESSED. FEES WILL BE
 OWED.
  
 6) NOTE: PLEASE KNOW, THIS INTERIOR BUILD OUT WILL
 REQUIRE A NEW NOTICE OF COMMENCEMENT AS THE ONE UDNER
 THE BUILDING AHS EXPIRED AND IS NOT PARTOF THIS SCOPE
 OF WORK. FS 713.13
  
 7) NOTE: PLEASE INDICATE AND SHOW LOAD SUMMARY AND
 CALCULATIONS INCLUDING ALL CONTINUOUS LOADS AT 125%.
 220.3,220.10,220.11,220.13, ETC 215.3, 230.42
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]