Plan Review Notes
Plan Review Notes For Permit 06100031
Permit Number 06100031
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2006-10-05 00:00:00*****APPROVED*****
  
  
  
 AS PER WEST PALM BEACH FIRE PREVENTION:
  
  
 1.) DUCT SMOKE DETECTORS SHALL INITIATE
 A GENERAL ALARM.
  
 2.) THE SILENCING OF THE FIRE ALARM
 SYSTEM SHALL IN NO WAY DEACTIVATE ANY
 VISUAL DEVICES.
  
 3.) COORDINATE WITH THE GENERAL AND/OR
 SPRINKLER CONTRACTOR THAT THE DOUBLE
 DETECTOR CHECK VALVE BE CHAINED AND
 LOCKEDAT THE END OF FINAL FIRE ALARM
 INSPECTION.
  
 4.) WATERFLOW TO ACTIVATE A GENERAL
 ALARM WITHIN 45 TO 60 SECONDS.
  
 5.) FIRE ALARM SYSTEM SHALL BE UL
 CERTIFIED FOR CENTRAL STATION. INSTALL
 AND/OR POST UL CERTIFICATE AT THE FIRE
 ALARM CONTROL PANEL AND PROVIDE A COPY
 TO WPBFR BY THE FINAL FIRE ALARM
 INSPECTION.
  
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved