Plan Review Notes For Permit 06100022 |
Permit Number |
06100022 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2007-06-03 14:59:29 | ** PROVISO/REVISION NEEDED ** | | | | 1) NOTE: PLEASE SEE PREVIOUS NOTE WHICH REQUESTED THE | | LOAD ON THE EXISTING SERVICE WITH THE NEW LOAD BEING | | ADDED/INCREASED. PLEASE SEE THIS IS THE LOAD ON THE | | EXISTING TENANT WIREWAY. | | 215.5, 220. | | | | | | ** PLEASE SUBMIT THE ABOVE INFORMATION ALONG WITH ANY | | OTHER REVISIONS BEFORE ROUGH ELECTRICAL INSPECTION. IF | | THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|