Plan Review Notes
Plan Review Notes For Permit 06100017
Permit Number 06100017
Review Stop M
Sequence Number 3
Notes
Date Text
2007-06-19 19:27:01************PROVISO**************
  
 REGARDING COMMENT #4 AND RESPONSE: IT IS THE
 DETERMINATION OF THE BUILDING OFFICIAL THAT AN AHU WITH
 A NOMINAL CAPACITY OF 2000 CFM HAS A DESIGN CAPACITY IN
 EXCESS OF 2000 CFM AND AS SUCH A DUCT SMOKE DETECTOR IS
 REQUIRED UNDER FBC, M 606.2.1. A FAN SHUT-DOWN TEST
 WITH AN AUDIO/VISUAL SIGNAL WILL BE REQUIRED AT FINAL
 INSPECTION.
  
 RONALD J REGUEIRO
 561.805.6719
 [email protected]