Plan Review Notes For Permit 06100017 |
Permit Number |
06100017 |
|
Review Stop |
M |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2007-06-19 19:27:01 | ************PROVISO************** | | | | REGARDING COMMENT #4 AND RESPONSE: IT IS THE | | DETERMINATION OF THE BUILDING OFFICIAL THAT AN AHU WITH | | A NOMINAL CAPACITY OF 2000 CFM HAS A DESIGN CAPACITY IN | | EXCESS OF 2000 CFM AND AS SUCH A DUCT SMOKE DETECTOR IS | | REQUIRED UNDER FBC, M 606.2.1. A FAN SHUT-DOWN TEST | | WITH AN AUDIO/VISUAL SIGNAL WILL BE REQUIRED AT FINAL | | INSPECTION. | | | | RONALD J REGUEIRO | | 561.805.6719 | | [email protected] |
|