Plan Review Notes
Plan Review Notes For Permit 06100017
Permit Number 06100017
Review Stop P
Sequence Number 2
Notes
Date Text
2007-03-07 16:11:05DENIED
 REFERENCE: FBC-2004 PLUMBING
 CITY WEST PALM BEACH MUNICIPAL CODE
  
 1. SHT C-3 INDICATES A 1" RPZV BACKFLOW. PER TABLE
 60.1(D),ALL SECONDARY BACKFLOW ASSEMBLIES SHALL BE AT
 LEAST THE SAME SIZE AT THE WATER SERVICE LINE IN WHICH
 THEY ARE INSTALLED.
 ****RESPONSE NOTED, BUT AN RPZV BACKFLOW IS REQUIRED ON
 THE WATER SUPPLY TO THE BUILDING. SHEET C-3 NOW
 INDICATES THE WATER SUPPLY CONNECTING TO TWO SOURCES. A
 2" LINE AND A 1-1/2" LINE. PLEASE CLARIFY. SECTION
 608.13.2. ALSO SEE SHT P-3 AT THE INCOMING MINIMUM 2"
 WATER SUPPLY INDICATES A BACKFLOW REQUIRED.
  
 2. SHTS P-1 & P-2 A SAND/OIL INTERCEPTOR MAY BE
 REQUIRED. PLEASE CONTACT LYNN MASSON, ENVIRONMENTAL
 COMPLIANCE MANAGER AT (561) 822-2271, OR FAX (561)
 822-2279, OR E-MAIL [email protected]. UTILITY ORD.
 3434.
 ****RESPONSE NOTED, BUT THE REQUIREMENT FOR A SAND/OIL
 INTERCEPTOR SHALL BE DETERMINED BY ENVIRONMENTAL
 COMPLIANCE. ARTICLE III SECTION 90-124(7) OF THE
 MUNICIPAL CODE. LOOKING THROUGH APPENDIX "I", THERE ARE
 14 PAGES OF INFORMATION. IF THERE IS INFORMATION ON A
 SAND/OIL INTERCEPTOR IN THESE PAGES, PLEASE INDICATE
 WHICH PART AND SUBPART PRETAINS TO THIS INFORMATION.
 WILL THIS INFORMATION INDCATE IF THE OVERFLOWS WILL
 HAVE THE OIL INTERCEPTED?
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]