2007-03-20 10:04:16*****UNSAT*****
  
  
 PLEASE RE-ADDRESS THE FOLLOWING COMMENTS TAKEN FROM THE
 PREVIOUS FIRE PLAN REVIEW:
  
  
 4.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.ADD
 NFPA 241 TO CODE SUMMARY ON SHEET NO. A-1
  
 8.WHEN IT IS NECESSARY TO SHUT DOWN A FIRE PROTECTION
 SYSTEM , THE FIRE DEPARTMENT SHALL BE NOTIFIED WHEN THE
 SYSTEM IS SHUT DOWN AND WHEN IT IS RETURNED TO SERVICE.
 PLEASE ADD THIS STATEMENT TO SHEET NO. FP-1.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS