2007-02-27 07:53:32 | *** UNSAT 2ND REVIEW*** |
| |
| |
| |
| 1) NOTE:PLEASE KNOW, PLANS HAVE STILL ONLY BEEN |
| SUBMITTED FOR "PLAN REVIEW" AND HAVE NOT BEEN SUBMITTED |
| FOR PERMIT AT THIS TIME. |
| AS PERMIT APPLICATION WAS NOT MADE BEFORE DECEMBER 8TH, |
| 2006 ALL PLANS, DESIGNS,AND CODES REFLECTED ON PLANS |
| WILL BE UNDER THE NEW CODES AS ADOPTED BY THE STATE OF |
| FLORIDA. |
| PLEASE SEE THAT THE PLANS ARE SHOWING INCORRECT CODES |
| AT THIS TIME. |
| 2004 FBC W/2006 REVISIONS. |
| 2005 NFPA-70 |
| PLEASE KNOW THAT THE "LATEST EDITION? MAY NOT BE STATED |
| ON PLANS. |
| THIS IS REQUIRED FOR ALL SHEETS AND TRADES WHETHER OR |
| NOT COMMENT IS MADE BY OTHER TRADES OR REVIEWS. |
| IF PLANS CONTAINED ALL THE CORRECT CODES AND WERE CODE |
| COMPLIANT, THE REVIEW COULD NOT BE ?PASSED? AS PERMIT |
| APPLICATION HAS NOT YET BEEN MADE AND REVIEW OF SCOPE, |
| PERMIT APPLICATION AND VALUATION OF PROJECT STILL NEEDS |
| TO TAKE PLACE. |
| |
| 2) NOTE: PLEASE PROVIDE LOAD CALCULATIONS ON ALL |
| SERVICE EQUIPMENT ON THE LINE SIDE OF THIS TRANSFORMER |
| IF NOT A FPL UNIT. |
| 220, FBC 106.1.2 |
| THIS WAS REQUESTED ON THE PREVIOUS REVIEW HOWEVER LOAD |
| SUMMARY OR CALCULATIONS FOR THE EXISTING MAIN DIST SWGR |
| HAS NOT BEEN PROVIDED. |
| |
| 3) NOTE: PLEASE INDICATE ALL BRANCH CIRCUIT CONDUCTORS |
| ON PANEL SCHEDULE. PLEASE SEE 310.16 FOR SIZING. |
| 240.4, 310.16, |
| FBC 106.5.3.1.2 |
| *SOME CONDUCTOR SIZES ARE SHOWN ON PLANS AND NOTE WAS |
| VIEWED FOR OTHER CONDUIT RUNS, HOWEVER NOT ALL AND |
| PLEASE PLACE ON PANEL SCHEDULE. |
| |
| . |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| |
| |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
2007-02-26 07:03:19 | 2007-02-25 07:03:19 |
| IN PROGRESS |
2007-02-25 14:55:45 | 2007-02-25 14:55:45 |
| REVIEW WILL CONTINUE, PLANS WILL FOLLOW INTO "F" STATUS |
| ONCE REVIEW IS COMPLETED. |