2006-12-06 14:22:35DENIED
 REFERENCE: FBC-2004 PLUMBING
 CITY WEST PALM BEACH MUNICIPAL CODE
  
 1. SHT C-3 INDICATES A 1" RPZV BACKFLOW. PER TABLE
 60.1(D),ALL SECONDARY BACKFLOW ASSEMBLIES SHALL BE AT
 LEAST THE SAME SIZE AT THE WATER SERVICE LINE IN WHICH
 THEY ARE INSTALLED.
  
 2. SHTS P-1 & P-2 A SAND/OIL INTERCEPTOR MAY BE
 REQUIRED. PLEASE CONTACT LYNN MASSON, ENVIRONMENTAL
 COMPLIANCE MANAGER AT (561) 822-2271, OR FAX (561)
 822-2279, OR E-MAIL [email protected]. UTILITY ORD.
 3434.
  
  