2006-12-06 14:22:35 | DENIED | | REFERENCE: FBC-2004 PLUMBING | | CITY WEST PALM BEACH MUNICIPAL CODE | | | | 1. SHT C-3 INDICATES A 1" RPZV BACKFLOW. PER TABLE | | 60.1(D),ALL SECONDARY BACKFLOW ASSEMBLIES SHALL BE AT | | LEAST THE SAME SIZE AT THE WATER SERVICE LINE IN WHICH | | THEY ARE INSTALLED. | | | | 2. SHTS P-1 & P-2 A SAND/OIL INTERCEPTOR MAY BE | | REQUIRED. PLEASE CONTACT LYNN MASSON, ENVIRONMENTAL | | COMPLIANCE MANAGER AT (561) 822-2271, OR FAX (561) | | 822-2279, OR E-MAIL [email protected]. UTILITY ORD. | | 3434. | | | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] |
|