2006-12-13 16:03:35 | *****DENIED***** |
| |
| |
| |
| |
| 1.THE ADDRESS OF THE TRUCK WASH FACILITY SHALL BE IN |
| THE TITLE BLOCK OF EACH SUBMITTED PLAN. |
| |
| 2.SHOW/DISPLAY THE NUMERICAL ADDRESS ON THE |
| APPROPIATE ELEVATION (SHEET A-2).AS PER WEST PALM |
| BEACH CODE, THE NUMERICAL ADDRESS SHALL BE NO LESS THAN |
| 6" IN HEIGHT AND 1"IN WIDTH. |
| |
| 3.NFPA 101 (2003 EDITION) AND THE FLORIDA FIRE |
| PREVENTION CODE (2004 EDITION) SHALL BE REFERENCED. |
| |
| 4.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| |
| 5.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL NOT |
| INTERFERE OR HINDER EMERGENCY ACCESS TO THE SAID |
| PROPERTY OR VICINITY THEREOF (INCLUDING FIRE LANES). |
| |
| 6.ACCESS ROADS SHALL BE CAPABLE OF SUPPORTING AND |
| MAINTAINING 32 TONS OF FIRE EQUIPMENT. |
| |
| 7.SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR THE |
| FIRE SPRINKLER SYSTEM.NFPA 13 (2002 EDITION) SHALL BE |
| REFERENCED. |
| |
| 8.WHEN IT IS NECESSARY TO SHUT DOWN A FIRE PROTECTION |
| SYSTEM (IF NEEDED TO RELOCATE THE FIRE DEPT. CONN. AS |
| STATED ON SHEET FP-1.0) , THE FIRE DEPARTMENT SHALL BE |
| NOTIFIED WHEN THE SYSTEM IS SHUT DOWN AND WHEN IT IS |
| RETURNED TO SERVICE. |
| |
| |
| TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED. |
| |
| |