Plan Review Notes
Plan Review Notes For Permit 06100017
Permit Number 06100017
Review Stop E
Sequence Number 1
Notes
Date Text
2006-10-26 17:54:05*** UNSAT ****
  
 ** PLEASE KNOW, PLANS HAVE ONLY BEEN SUBMITTED FOR
 "PLAN REVIEW" AND HAVE NOT BEEN SUBMITTED FOR PERMIT AT
 THIS TIME. PLANS EVEN IF CODE COMPLIANT CAN NOT BE
 STAMPED OR SIGNED OFF UNTIL APPLICATION FOR PERMIT HAS
 BEEN MADE.
  
 1) NOTE: PLEASEPLACE ALL RELEVANT CODES ON PLANS
 WHICH ARE CURRENT AND UNDER ADOPTION OF THE FBC.
 NFPA-70 2002,ETC.
 PLEASE KNOW THAT THE "LATEST EDITION" HAS NOT YET BEEN
 ADOPTED PER THE STATE OF FLORIDA.
  
 2) NOTE: PLEASE SEE FBC ADMIN SECT 106.1.3 WHICH
 REQUIRES PLANS AT A MIN OF 1/8" SCALE.
  
 3) NOTE: PLEASE SEE 700.12EWHICH REQUIRES THE BRANCH
 CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL BE THE SAME
 BRANCH CIRCUIT AS THAT SERVING THE NORMAL LIGHTING IN
 THE AREA AND CONNECTED AHEAD OF ANY LOCAL SWITCHES.
  
 4) NOTE: PLEASE PROVIDE INFORMATION ON THE 500 KVA 4160
 TRANSFORMER AS SHOWN. IS THISFPL OR ON SITE DOWN
 STREAM FROM A 4160 SERVICE.
 PLEASE SEE OTHER COMMENTS WHICH MAY REFLECTTHIS
 INFORMATION WHICH IS NOT YET PROVIDED.
 FBC 106.1.2
  
 5) NOTE; PLEASE SEE MISSING NEUTRAL CONDUCTOR FROM THIS
 TRANSFORMER TO THE NEW MDP. PLEASE SEE THIS IS REQUIRED
 WHETHER OR NOT THIS IS A FPL TRANSFORMER.
 PLEASE SHOW AND INDICATE ALL GROUNDING ELECTRODE
 SYSTEMS PER 250.20,250.30,250.66 ETC
 PLEASE SEE 250.6, 250.24B.
 IT IS UNCLEAR AT THIS TIME IF THESE ARE FEEDERS OR
 SEC'S.?
  
 6) NOTE: PLEASE PROVIDE LOAD CALCULATIONS ON ALL
 SERVICE EQUIPMENT ON THE LINE SIDE OF THIS TRANSFORMER
 IF NOT A FPL UNIT.
 220, FBC 106.1.2
  
 7) NOTE: PLEASE SUBMIT ALL INFORMATION ON THE EQUIPMENT
 LISTING ETC FOR INSTALLING A NEW 600A MCB INSIDE THIS
 EXISTING TRANSFORMER.
 PLEASE KNOW ALL DISCONNECTING MEANS SHALL BE READILY
 ACCESSIBLE ETC. AT THIS TIME THIS SCENARIO AS SHOWN
 DOES NOT MEET CODE AND MORE INFORMATION IS NEEDED.
 110.3, 110.27, 90.7, 110.26,, 250.24B, 230.70,ETC
 ETC.
 PLEASE SUBMIT THE MANUFACTURES SPEC /CUT SHEETS ON THIS
 EQUIPMENT. MUST INDICATE A LISTING FROM A NRTL BEFORE
 THIS CAN BE REVIEWED.
  
 8) NOTE: PLEASE INDICATE GROUNDING FOR TR1 250.66,
 250.30, 250.20 ETC.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  