2006-10-26 17:54:05 | *** UNSAT **** |
| |
| ** PLEASE KNOW, PLANS HAVE ONLY BEEN SUBMITTED FOR |
| "PLAN REVIEW" AND HAVE NOT BEEN SUBMITTED FOR PERMIT AT |
| THIS TIME. PLANS EVEN IF CODE COMPLIANT CAN NOT BE |
| STAMPED OR SIGNED OFF UNTIL APPLICATION FOR PERMIT HAS |
| BEEN MADE. |
| |
| 1) NOTE: PLEASEPLACE ALL RELEVANT CODES ON PLANS |
| WHICH ARE CURRENT AND UNDER ADOPTION OF THE FBC. |
| NFPA-70 2002,ETC. |
| PLEASE KNOW THAT THE "LATEST EDITION" HAS NOT YET BEEN |
| ADOPTED PER THE STATE OF FLORIDA. |
| |
| 2) NOTE: PLEASE SEE FBC ADMIN SECT 106.1.3 WHICH |
| REQUIRES PLANS AT A MIN OF 1/8" SCALE. |
| |
| 3) NOTE: PLEASE SEE 700.12EWHICH REQUIRES THE BRANCH |
| CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL BE THE SAME |
| BRANCH CIRCUIT AS THAT SERVING THE NORMAL LIGHTING IN |
| THE AREA AND CONNECTED AHEAD OF ANY LOCAL SWITCHES. |
| |
| 4) NOTE: PLEASE PROVIDE INFORMATION ON THE 500 KVA 4160 |
| TRANSFORMER AS SHOWN. IS THISFPL OR ON SITE DOWN |
| STREAM FROM A 4160 SERVICE. |
| PLEASE SEE OTHER COMMENTS WHICH MAY REFLECTTHIS |
| INFORMATION WHICH IS NOT YET PROVIDED. |
| FBC 106.1.2 |
| |
| 5) NOTE; PLEASE SEE MISSING NEUTRAL CONDUCTOR FROM THIS |
| TRANSFORMER TO THE NEW MDP. PLEASE SEE THIS IS REQUIRED |
| WHETHER OR NOT THIS IS A FPL TRANSFORMER. |
| PLEASE SHOW AND INDICATE ALL GROUNDING ELECTRODE |
| SYSTEMS PER 250.20,250.30,250.66 ETC |
| PLEASE SEE 250.6, 250.24B. |
| IT IS UNCLEAR AT THIS TIME IF THESE ARE FEEDERS OR |
| SEC'S.? |
| |
| 6) NOTE: PLEASE PROVIDE LOAD CALCULATIONS ON ALL |
| SERVICE EQUIPMENT ON THE LINE SIDE OF THIS TRANSFORMER |
| IF NOT A FPL UNIT. |
| 220, FBC 106.1.2 |
| |
| 7) NOTE: PLEASE SUBMIT ALL INFORMATION ON THE EQUIPMENT |
| LISTING ETC FOR INSTALLING A NEW 600A MCB INSIDE THIS |
| EXISTING TRANSFORMER. |
| PLEASE KNOW ALL DISCONNECTING MEANS SHALL BE READILY |
| ACCESSIBLE ETC. AT THIS TIME THIS SCENARIO AS SHOWN |
| DOES NOT MEET CODE AND MORE INFORMATION IS NEEDED. |
| 110.3, 110.27, 90.7, 110.26,, 250.24B, 230.70,ETC |
| ETC. |
| PLEASE SUBMIT THE MANUFACTURES SPEC /CUT SHEETS ON THIS |
| EQUIPMENT. MUST INDICATE A LISTING FROM A NRTL BEFORE |
| THIS CAN BE REVIEWED. |
| |
| 8) NOTE: PLEASE INDICATE GROUNDING FOR TR1 250.66, |
| 250.30, 250.20 ETC. |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
| |