Plan Review Notes
Plan Review Notes For Permit 06100017
Permit Number 06100017
Review Stop B
Sequence Number 1
Notes
Date Text
2006-10-23 16:28:41DENIED BY BUILDING
 6255 N. JOG RD.
 SWA TRUCK WASH FACILITY
 TYPE II BCONSTRUCTION/ UNSPRINKLERED
  
 1) WHEN SUBMITTING FOR PERMIT SPECIFY THE VALUE OF THE
 PROJECT ON THE APPLICATION.
  
 2) RADON FEES WILL BE ASSESSED BASED ON THE SQUARE
 FOOTAGE UNDER ROOF.
  
 3) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 4) BEFORE A PERMIT TO CONSTRUCT CAN BE
 ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY.THE PLANS MUST BE
 STAMPED AND THE RECEIPT ATTACHED TO THE APPLICATION.
  
  
 5)FBC 1804.2.2AREA OF QUESTIONABLE
 SOIL.SUBMIT A GEOTECHNICAL REPORT
 TO VERIFY THE SAFE BEARING CAPACITY OF
 THE SOIL.
  
 6) PLEASE CORRECT THE TYPO ON SHEET A1. THE TEST
 PROTOCOLS SHOULD READ HVHZ NOT HVH2.
  
 7) THE ALLOWABLE HEIGHT AND AREA SPECIFIED ON SHEET A1
 ARE FOR A TYPE II GROUP S1 OCCUPANCY AND A GROUP B
 OCCUPANCY IS SPECIFIED. PLEASE CORRECT.
  
 8)FBC 704.3 BUILDINGS ON THE SAME LOT.
  
 FOR THE PURPOSES OF DETERMINING THE REQUIRED WALL AND
 OPENING PROTECTION AND ROOF-COVERING REQUIREMENTS,
 BUILDINGS ON THE SAME LOT SHALL BE ASSUMED TO HAVE AN
 IMAGINARY LINE BETWEEN THEM.
  
 WHERE A NEW BUILDING IS TO BE ERECTED ON THE SAME LOT
 AS AN EXISTING BUILDING, THE LOCATION OF THE ASSUMED
 IMAGINARY LINE WITH RELATION TO THE EXISTING BUILDING
 SHALL BE SUCH THAT THE EXTERIOR WALL AND OPENING
 PROTECTION OF THE EXISTING BUILDING MEET THE CRITERIA
 AS SET FORTH IN SECTIONS 704.5 AND 704.8 . EXCEPTION:
 TWO OR MORE BUILDINGS ON THE SAME LOT SHALL EITHER BE
 REGULATED AS SEPARATE BUILDINGS OR SHALL BE CONSIDERED
 AS PORTIONS OF ONE BUILDING IF THE AGGREGATE AREA OF
 SUCH BUILDINGS IS WITHIN THE LIMITS SPECIFIED IN
 CHAPTER 5 FOR A SINGLE BUILDING. WHERE THE BUILDINGS
 CONTAIN DIFFERENT OCCUPANCY GROUPS OR ARE OF DIFFERENT
 TYPES OF CONSTRUCTION, THE AREA SHALL BE THAT ALLOWED
 FOR THE MOST RESTRICTIVE OCCUPANCY OR CONSTRUCTION.
 PROVIDE A SITE PLAN INDICATING THE ASSUMED PROPERTY
 LINE BETWEEN THE TWO STRUCTURES. NOTE BOTH THE NEW AND
 EXISTING STRUCTURES ARE REQUIRED TO COMPLY WITH WALL
 CONSTRUCTION RATING AND ALLOWABLE OPENINGS. ALSO SEE
 FBC 702 FOR DEFINITION OF FIRE SEPARATION DISTANCE.
 SHOW COMPLIANCE.
  
 9) SUBMIT ENERGY CALCULATION FORMS AS REQUIRED BY FBC
 13-4.
  
 10) SPECIFY THE ROOF PITCH ON THE PLANS. FBC 106.1.2*
 CITY AMENDMENTS
  
 11) THE DESIGN WIND PRESSURES FOR COMPONENTS AND
 CLADDING LISTED IN THE TABLE ON SHEET S5 APPEAR TO BE
 TOO LOW FOR 140 MPH EXPOSURE B BASED ON FBC TABLE
 1609.6B. SUBMIT SIGNED AND SEALED CALCULATIONS. FBC
 106.1.2 * CITY AMENDMENTS
  
 12) SUBMIT PRODUCT APPROVALS FOR EXTERIOR WINDOWS,
 DOORS, OVERHEAD GARAGE DOORS, STORM PANELS, LOUVER
 VENTS, ROOFING MATERIALS, ETC. FOR PRODUCTS SPECIFIED
 BY FLORIDA ADMINISTRATIVE CODE RULE 9B-72.
  
 13) FBC 106.3.3* CITY AMENDMENTS REQUIRES THE PRODUCT
 APPROVALS TO BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD FOR THE PROJECT.
  
 14) FBC 1609.1.4 REQUIRES OPENINGS IN ENCLOSED
 STRUCTURES TO BE IMPACT RESISTANT OR PROTECTED WITH
 IMPACT RESISTANT COVERINGS. SHOW COMPLIANCE.
  
 15) FBC 1503.6 REQUIRES CONDENSATE LINES AND ROOF
 DOWNSPOUTS TO DISCHARGE AT LEAST ONE FOOT AWAY FROM THE
 STRUCTURE SIDEWALLS. SHOW COMPLIANCE.
  
 16) FBC 1816 REQUIRES TERMITE PROTECTION. SHOW
 COMPLIANCE.
  
 17) SUBMIT INFORMATION, PRODUCT APPROVAL, CALCULATIONS
 AND SPECIFICATIONS FOR THE OCTAFORM WALL SYSTEM. FBC
 106.1.2* CITY AMENDMENTS.
  
 18) SUBMIT SHOP DRAWINGS AND CALCULATIONS FOR THE
 PRECAST HOLLOW CORE CONCRETE ROOF DECK.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved