2006-10-13 14:29:54BUILDING REVIEW SECOND CHECKLIST:
 1- COMPLETE RAS 117 CALCULATIONS WERE REQUESTED ON
 PREVIOUS CHECKLIST TO SHOW FASTENER SPACING THAT MEETS
 THE CALCULATED DESIGN PRESSURES. CALCULATIONS WERE NOT
 SUBMITTED. INSTEAD AN ENGINEER'SRECOMMENDED FASTENER
 SPACING WAS PROVIDED.
  
 2- FASTENER SPACING FROM FEDERAL ENGINEERING & TESTING
 DOESN'T WORK TO MEET THE CALCULATED DESIGN PRESSURES.
 ENGINEER TO PROVIDE COMPLETE RAS 117 CALCULATIONS TO
 SHOW HOW THE RECOMMENDED FASTENING PATTERN MEETS THE
 CALCULATED DESIGN PRESSURES. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 3- FEDERAL ENGINEERING & TESTING ENGINEERINGNEEDS TO
 PROVIDE THE FIRM'S CERTIFICATE OF AUTHORIZATION NUMBER
 AS REQUIRED BY FLORIDA ADMINISTRATIVE CODE SEC.
 61G15-23.002. SEE ATTACHED COPY.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712