2006-10-02 00:00:00BUILDING REVIEW CHECKLIST:
 1- NOTICE OF COMMENCEMENT IS INCOMPLETE.
 THERE IS NOT INFORMATION GIVEN FOR
 CONTRACTOR. COMPLETE ALL INFORMATION AND
 RE-RECORD NOTICE OF COMMENCEMENT.
  
 2- BASE SHEET FASTENER SPACING PROVIDED
 FOR WOOD DECK DOESN'T WORK. PROVIDE
 COMPLETE RAS 117 CALCULATIONS AS
 REQUIRED BY GENERAL LIMITATION #7 TO
 SHOW FASTENER SPACING THAT MEETS THE
 CALCULATED DESIGN PRESSURES.
  
 ***NOTES:
 A) TAKE INTO CONSIDERATION THAT THE
 MIN. FASTENER SEPARATION SHALL NOT BE
 LESS THAN 4" O.C.. SEE SECTION 8.1 FROM
 RAS 117 STANDARD.
 B) THERE IS NOT NEED TO USE RAS 120
 STANDARD TO GET THE ROOF DESIGN
 PRESSURES. TABLE 1609.6B FROM 2004
 FLORIDA BUILDING CODE CAN BE USED ALSO.
 THE CITY OF WPB IS LOCATED IN BUILDING
 EXPOSURE B WITH 140MPH WIND LOAD.
  
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER