Plan Review Notes For Permit 06091061 |
Permit Number |
06091061 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-10-13 13:33:09 | *****DENIED***** | | | | | | | | | | 1.)ADD VISUAL ALARM DEVICE (STROBE) TO THE FOLLOWING | | CONFERENCE/GATHERING ROOMS: SHEET FA-1, ROOM 139; | | SHEET FA-3, ROOM 321;SHEET FA-4, ROOM 408 . | | | | 2.)FIRE ALARM SYSTEM TO BE FULLY ADDRESSABLE. | | | | 3.)WATERFLOW TO ACTIVATE A GENERAL ALARM WITHIN 45 TO | | 60 SECONDS. | | | | 4.)DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL | | ALARM. | | | | 5.)FIRE ALARM SYSTEM SHALL BE UL CERTIFIED FOR | | CENTRAL STATION SERVICE.INSTALL UL CERTIFICATE AT THE | | FIRE ALARM CONTROL PANEL AND PROVIDE A COPY TO WPBFR BY | | FINAL FIRE ALARM INSPECTION. | | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|