Plan Review Notes For Permit 06091035 |
Permit Number |
06091035 |
|
Review Stop |
ENG |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2007-04-05 14:23:52 | FAILED FOR FOLLOWING REASONS: | | | | 1. P.E. SEAL MUST BE MINIMUM 1 7/8" DIAMETER PER FBPE. | | MUST BE SIGNED PER FBPE | | 2. YOU MUST GIVE YOUR BUSINESS# IN YOUR HALEY ENG INC. | | TITLE BLOCK IN DRAWING. PERFBPR. | | 3.WATER QUALITY CAC MUST SHOW WHAT CRITERIA YOU USED | | EITHER 1" OR 2.5" OF WATER OVER SITE ETC.PLEASE SHOW | | HOW DID YOU COME UP WITH THE LENGTH OF EXFILTRATION | | TRENCH. | | 4. SILT HEIGHT WHY NOT 5 FEET HIGH? | | 5. SHEET LA-1, LA-2 IN SET NOT SEALED ?? | | 6. PLEASE SHOW LOCATION OF DUMPSTER ON DRAWING.IS IT | | ACCESSIBLE TO CITY PICK UP ? | | | | PLEASE RESPOND EACH COMMENT SEPARATELY. | | | | RASIK CHOKSHI 805-6723 |
|