2006-11-17 13:24:08 | BUILDING PLAN REVIEW |
| PERMIT: 06091006 |
| ADD: 505 BANYAN BLVD |
| CONT: THE WEITZ CO. |
| TEL: (561)309-7386 |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| * WEST PALM BEACH AMENDMENTS |
| |
| 1STREVIEW |
| ACTION: DENIED |
| |
| 1)--- VERY IMPORTANT STATEMENT --- |
| PLEASE DO NOT IGNORE! |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| 2)SHEET S1.0.0: |
| |
| 2A) THE WIND LOAD DESIGN CRITERIA INDICATES THE |
| DESIGNER IS USING ASCE 7-98. |
| THE REFRENCE STANDARD REFRENCED TO IN CHAPTER 35 |
| REFRENCES ASCE 7-02. |
| |
| 2B) WIND IMPORTANCE FACTOR, THE PLANS INDICATE AN |
| IMPORTANCE FACTOR (1)=1.00. |
| IF THE (1) IS REPRESENTATIVE OF THE IMPORTANCE FACTOR, |
| THIS IS TO BE USED FOR |
| AGRICULTURAL FACILITIES, TEMPORARY FACILITIES AND MINOR |
| STORAGE FACILITIES, PLEASE |
| REVISIT TABLE 1-1 FOR THE CORRECT IMPORTANCE FACTOR. |
| |
| 2C) WIND LOAD INFORMATION AS STATED IN (E) (1) (D) THE |
| INTERNAL |
| PRESSURE COEFFICIENT = + / -.55OR PARTIALLY ENCLOSED. |
| INTHE BODY OF THE TEXT |
| DIRECTLY BELOWTHE WIND DESIGN CRITERIA IT IS STATED |
| AS BEING DESIGNED AS AN |
| ENCLOSED STRUCTURE?PLEASE PROVIDE ADDITIONAL |
| INFORMATION? |
| |
| 2D) (I) FUTURE EXPANSION THE ORIGINAL DESIGN DRAWINGS |
| INDICATE |
| THAT THE STRUCTURE WAS DESIGNED FOR |
| TWO LEVELS OF FUTURE EXPANSION.ARE THE TWO NEW LEVELS |
| OF FUTURE |
| EXPANSION TO BE INCORPORATED INTO THE SCOPE OF WORK |
| COVERED BY |
| THISPERMIT APPLICATION? |
| |
| 2E) PLEASE PROVIDE (3) ORIGINAL SIGNED & SEALEDSOILS |
| REPORTS DATED JULY 14,2006 |
| (TIERRA FILE 6611- 05504. 1802.2.1 QUESTIONABLE SOIL. |
| WHERE THE SAFE-SUSTAINING POWER OF THE SOIL IS IN |
| DOUBT, OR WHERE A LOAD-BEARING |
| VALUE SUPERIOR TO THAT SPECIFIED IN THIS CODE IS |
| CLAIMED, THE BUILDING OFFICIAL SHALL |
| REQUIRE THAT THE NECESSARY INVESTIGATION BE MADE. SUCH |
| INVESTIGATION SHALL COMPLY |
| WITH THE PROVISIONS OF SECTIONS 1802.4 THROUGH 1802.6 |
| . |
| |
| |
| 2F) CONTRACTOR SUBSTITUTIONS: THE TERM ICBO IS NO |
| LONGER IN EXISTANCE, THE ICC CODE HAVE REPLACED ALL OF |
| THE LEGACY REPORTS . |
| |
| 3) PLANS DO NOT PROVIDE THE FOLLOWING INFORMATION: |
| 110.2* W. P. B. ADMINISTRATIVE |
| CODE, INFORMATION THAT IS REQUIRED FOR |
| RECORD KEEPING & FOR CERTIFICATE OF |
| OCCUPANCY: |
| A) THE EDITION OFTHE CODE UNDER WHICH |
| THE PERMIT WAS ISSUED. |
| B) THE USE AND OCCUPANCY, IN ACCORDANCE |
| WITH THE PROVISIONS OF CHAPTER 3. |
| C) THE TYPE OF CONSTRUCTION AS DEFINED |
| IN CHAPTER 6, TABLE 601. |
| D) THE OCCUPANT LOAD, SEE 1004. |
| E) IF AN AUTOMATIC SPRINKLER SYSTEM IS |
| PROVIDED, WHETHER THE SPRINKLER SYSTEM |
| IS REQUIRED. |
| F) ANY SPECIAL STIPULATIONS & CONDITIONS |
| OF THE BUILDING PERMIT. |
| ------------------------------------- |
| G ) NUMBER OF FLOORS |
| H ) SQ. FT. FOOTPRINT |
| I ) SQ. FT. UNDER ROOF (TOTAL) |
| |
| 4)FL S. S. 553.71(7) " THRESHOLD |
| BUILDING" MEANING ANY BUILDING WHICH IS |
| GREATER THAN (3) STORIES OR 50 FT IN |
| HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPAN |
| CY CLASSIFICATION AS DEINED IN THE |
| FLORIDA BUILDING CODE WHICH EXCEEDS |
| 5,000 SQ FT IN AREA AND AN OCCUPANT |
| CONTENT OF GREATER THAN 500 PERSONS. |
| 105.13.1 THE ENFORCING AGENCY SHALL |
| REQUIRE A SPECIAL INSPECTOR TO PERFORM |
| STRUCTURAL INSPECTIONS ON A THRESHOLD |
| BUILDING PURSUANT TO A STRUCTURAL |
| INSPECTION PLAN PREPARED BY THE |
| ENGINEER OF RECORD. THE STRUCTURAL |
| INSPECTION PLAN MUST BE SUBMITTED TO THE |
| ENFORCING AGENCY PRIOR TO THE ISSUANCE |
| OF A BUILDING PERMIT FOR THE |
| CONSTRUCTION OF A THRESHOLD BUILDING. |
| THE PURPOSE OF THE STRUCTURL INSPECTION |
| PLAN IS TO PROVIDE SPECIFIC INSPECTION |
| PROCEDURES AND SCHEDULES SO THAT THE |
| BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE |
| WITH THE PERMITTED DOCUMENTS. |
| |
| 5)WPB AMENDMENT 105.13.6. W.P.B. |
| CONSTRUCTION SERVICES DEPARTMENT |
| REQUEST FOR THRESHOLD BUILDINGS A |
| SPECIAL INSPECTOR AS REQUIRED BY S. |
| 553.79(5) FLORIDA STATUTES TO THE MIN- |
| IMUM INSPECTIONS REQUIRED BY THIS CODE. |
| CONTACT HAROLD PISKURA MANAGER OF THE |
| SPECIAL INSPECTOR PROGRAM AT (561) |
| 805-6711 FOR FURTHER INFORMATION BEFORE |
| THE PERMIT MAY BE ISSUED. |
| |
| 6)W.P.B. AMENDMENT 105.13.4.4 ALL |
| PLANS FOR THE BUILDING WHICH ARE |
| REQUIRED TO BE SIGNED AND SEALED BY THE |
| ARCHITECT OR ENGINEER OF RECORD CON- |
| TAIN A STATEMENT THAT, TO THE BEST OF |
| THE ARCHITECT'S PR ENGINEER'S KNOWLEDGE, |
| THE PLANS AND SPECIFICATIONS COMPLY WITH |
| THE APPLICABLE FIRE-SAFETY STANDARDS AS |
| DETERMINED BY THE LOCAL AUTHORITY IN |
| ACCORDANCE WITH THIS SECTION AND 633 |
| FLORIDA STATUTE. |
| |
| BUILDING PLAN REVIEW |